Plan Review Details - Permit 00031578
Plan Review Stops For Permit 00031578
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 18:28 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 18:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-01 Cont ID  
Sent By dpalmer Date 2000-05-01 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2000-05-01 Time 12:44 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE:MISSING AIC RATING OF MAIN.110-9
  
 2)NOTE: MISSING SMOKE DETECTORS INSDIE
 ALL SLEEPING ROOMS NFPA-72 2-2.1.1.1
  
 3)NOTE:MISSING REQ`D BATH(S) CIRCUITS
 PER 210-11-C-3
  
 4)NOTE: OUTLET SPACING TO MEET CODE
 210-52
  
 5)NOTE:MISSING BLDG. STEEL AS PART OF
 THE GROUNDING ELECTRODE SYSTEM 250-50
  
 6)NOTE: PLANS SHOW MAIN DISCONNECT? BUT
 THE ELECTRICAL RISER SHOWS MAIN BRK
 PANEL? WHICH ONE? PLEASE CORRELATE.
  
 PLEASE ALL THE ABOVE FOR REVIEW. IF THER
 E ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-12 Cont ID  
Sent By cthirben Date 2000-04-12 Time 08:31 Rev Time 1.00
Received By cthirben Date 2000-04-12 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-01-12 Cont ID  
Sent By jleech Date 2001-01-12 Time 15:23 Rev Time 0.25
Received By jleech Date 2001-01-12 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-11-12 Cont ID  
Sent By pschmitz Date 2000-11-12 Time 12:12 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW REVISION OK

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 09:29 Rev Time 0.25
Received By tlarge Date 2000-10-29 Time 09:29 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 04:04 Rev Time 0.25
Received By tlarge Date 2000-10-20 Time 04:04 Sent To  
Notes
2001-01-08 00:00:001)FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 2)FIXTURE BRANCHES NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 3)LAUNDRY RAY SHALL BE STACKED AND
 VENTED PER SPC SEC.901.2.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-16 Cont ID  
Sent By tlarge Date 2000-05-16 Time 08:35 Rev Time 0.33
Received By tlarge Date 2000-05-16 Time 08:35 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SUBMIT REVISED SANITARY DIAGRAM
 PRIOR TO PLBG.INSPECTION THAT CORRELATES
 W/FLOOR PLAN,SHOWS ALL PLBG.FIXTURES,AND
 COMPLIES W/SPC.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-03 Cont ID  
Sent By tlarge Date 2000-04-18 Time 20:11 Rev Time 0.33
Received By pschmitz Date 2000-04-18 Time 20:11 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A SANITARY RISER THAT CORRELATES
 W/THE FLOOR PLAN AND COMPLIES W/STD.
 PLBG.CODE.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-07-24 Cont ID  
Sent By jgomez Date 2000-07-24 Time 14:13 Rev Time 0.00
Received By jgomez Date 2000-07-24 Time 14:23 Sent To  
Notes
2001-01-08 00:00:00SUBMITTALS CHECKLIST:
 1-GARAGE DOOR PRODUCT APPROVAL DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT/ENGINEER OF RECORD.
 SEE ARCHITECTURAL PLANS.
 2-PRODUCT APPROVAL FOR SLIDING GLASS
 DOORS IS EXPIRED.
 -DRAWINGS ARE NOT LEGIBLE.
 -CLARIFY ARCHITECTURAL DRAWINGS. FLOOR
 PLAN SHOWS SLIDING GLASS DOORS WITH
 2 PANELS, WHILE, REAR ELEVATION SHOWS
 SLIDING GLASS DOORS WITH FOUR PANELS.
 REVISE DRAWINGS AS REQUIRED.
 3-PROVIDE PRODUCT APPROVAL FOR GLASS
 BLOCK. INFORMATION SUBMITTED IS PART
 OF MANUFACTURER'S SPECS BUT NOT THE
 ACTUAL PRODUCT APPROVAL.
 4-PROVIDE PRODUCT APPROVAL FOR ROUND
 WINDOW. PRODUCT APPROVAL SUBMITTED IS
 FOR HALF CIRCLE ONLY. SEE DRAWINGS.
 5-PROVIDE PRODUCT APPROVAL FOR SINGLE
 ENTRY DOOR AS SHOWN ON PLAN. PRODUCT
 APPROVAL SUBMITTED IS FOR SINGLE DOOR
 WITH SIDELITES ASSEMBLY.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By jgomez Date 2000-05-24 Time 20:39 Rev Time 2.50
Received By jgomez Date 2000-05-24 Time 20:39 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ENERGY CALCULATIONS:
 -REVISE NUMBER OF BEDROOMS. REVISE ALL
 AREA CALCULATIONS AT ALL WALL TYPES
 AND CEILING TYPES. SEE ARCHITECTURAL
 PLANS AND SECTIONS 604 AND 605 OF FLA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 -COMPLETELY FILL INFORMATION ON TOP OF
 ENERGY CALCULATIONS FORM.
 2-FLOOD ZONE "AO". WILL NEED TO PROVIDE
 AN ELEVATION CERTIFICATE AFTER SLAB
 IS POURED.
 3-MASTER BEDROOM TO HAVE A DOOR WITH 29"
 MINIMUM CLEAR OPENING AS PER CHAPTER
 11 OF FLORIDA ACCESSIBILITY CODE FOR
 BUILDING CONSTRUCTION, 1997 EDITION.
 4-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT FRONT AND
 BACK PORCHES. INCLUDING FASTENER TYPE
 AND SPACING. SEC 2504 SBC 1997.
 5-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AND KEY PLAN. CLEARLY SPECIFY MOUNTING
 CONDITIONS AND ANCHORS TO BE USED
 ACCORDING TO BUILDING CONSTRUCTION,
 DESIGN PRESSURES, MEAN ROOF HEIGHT,
 STORM PANEL SPAN AND EDGE DISTANCE.
 6-PROVIDE PRODUCT APPROVALS FOR: SINGLE
 ENTRY DOOR, ROUND WINDOWS, WINDOW
 MULLIONS, SLIDING GLASS DOORS, GLASS
 BLOCK AND GARAGE DOOR.
 7-TRUSS DRAWINGS:
 -MEAN ROOF HEIGHT IS 22'-6" PLUS OR
 MINUS (MEAN ROOF HEIGHT IS TAKEN FROM
 GRADE, NOT FROM FINISH FLOOR, TO THE
 AVERAGE POINT OF THE HIGHEST ROOF. AND
 THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 -CLARIFY WHY THE SIGNATURE ON TRUSS
 LAYOUT IS DIFFERENT FROM THE ONE ON
 ENGINEERED TRUSSES. ALSO, ENGINEER IS
 TO SIGN AND DATE DOCUMENTS AT TIME OF
 SEALING THEM.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By jgomez Date 2000-05-24 Time 20:37 Rev Time 0.25
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY GRACE JOYCE 4/5/00. SEE
 APPLICATION AND SURVEY.