Plan Review Details - Permit 00031556
| Plan Review Stops For Permit 00031556 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-06 |
Time |
10:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-29 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-29 |
Time |
15:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-04-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-04-13 |
Time |
20:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-04-13 |
Time |
20:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-04-05 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-04-05 |
Time |
10:26 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-04-05 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-28 |
Time |
07:00 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-08-28 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2000-09-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-09-20 |
Time |
20:26 |
Rev Time |
0.30 |
| Received By |
jgomez |
Date |
2000-09-20 |
Time |
20:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DOOR BUCK DETAIL: | | | -REVISE DETAIL ON SHEET A-4. CLARIFY HOW | | | IS THE 2X4 ATTACHED TO THE STRUCTURE | | | WITH 1-1/2" NAILS?. REVISE DETAIL. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-08-24 |
Time |
12:12 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2000-08-24 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE "AO". WILL NEED TO PROVIDE | | | AN ELEVATION CERTIFICATE. | | | 2-REVISE AGAIN THE ATTIC ACCESS SIZE. | | | MINIMUM SIZE TO BE 22"X36" AS PER | | | SECTION 2309.6 SBC 1997. | | | 3-UPDATE/REVISE DRAWINGS AS REQUIRED. | | | -SHOW ELEVATION THAT APPLIES TO TABLE | | | 600 OF SBC 1997 AND CALCULATIONS | | | SHOWN ON SHEET A-8. NOTE THAT REAR | | | ELEVATION SHOWN, FLOOR PLAN ON SHEET | | | A-8 AND TABLE 600 CALCULATIONS DON'T | | | MATCH. THEREFORE, PROVIDE DRAWINGS | | | WITH THE CORRECT INFORMATION TO AVOID | | | MORE CONFUSIONS. | | | 4-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOOR WITH SIDELITE AND MAKE SURE | | | DRAWINGS ARE LEGIBLE. | | | 5-SLIDING GLASS DOORS BY NORANDEX: | | | -PROVIDE COPIES OF TESTS RESULTS DONE | | | AS PER ASTM E-330. | | | SECTION 1706 SBC 1997. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2000-05-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-05-24 |
Time |
21:43 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2000-05-24 |
Time |
21:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COMMENTS FROM PREVIOUS CHECKLIST WERE | | | NOT PROPERLY CORRECTED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-05-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-05-17 |
Time |
18:17 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2000-05-17 |
Time |
18:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-EGRESS WINDOW IN BEDROOM #2 DOESN'T | | | COMPLY WITH SECTION 1005.4 SBC 1997. | | | 2-OPENINGS AT REAR ELEVATION EXCEED THE | | | PERCENTAGE ALLOWED BY TABLE 600 SBC/97 | | | CALCULATIONS ON SHEET A-8 ARE MISSING | | | THE SH H36 WINDOW BY BREAKFAST AREA. | | | ALSO, SEE WINDOW AND DOOR PRODUCT | | | APPROVAL FOR ACTUAL OPENING REQUIRED. | | | THOSE ARE THE RIGHT NUMBERS TO USE FOR | | | OPENING CALCULATIONS. | | | 3-UPDATE/REVISE ALL DRAWINGS AS REQUIRED | | | SEE COMMENTS ON PLANS.USE SBC 97 NO 99 | | | 4-ATTIC ACCESS TO BE 22"X36" MINIMUM. | | | SECTION 2309.6 SBC 1997. | | | 5-PRODUCT APPROVALS: | | | -PROVIDE COPIES OF TEST RESULTS FOR | | | SLIDING GLASS DOORS AS PER ASTM E 330. | | | SECTION 1706 SBC 1997. | | | -DRAWINGS FOR OUTSWING ENTRY DOOR WITH | | | LITES PRODUCT APPROVAL ARE NOT LEGIBLE | | | 6-STORM PANELS: | | | -REVISE KEY PLAN AND INSTALLATION SCHED | | | TO MATCH ARCHITECT'S PLAN ON SHEET A-8 | | | NOTE: WAIT TILL ARCHITECT REVISES PLAN | | | TO MEET THE TABLE 600 REQUIREMENTS. | | | -USE MASONRY ANCHOR SPACING WHEN PANELS | | | ARE TO BE ATTACHED TO MASONRY COLUMNS | | | WITH FILLED CELLS. | | | 7-FLOOD ZONE "AO". WILL NEED TO PROVIDE | | | ELEVATION CERTIFICATE. | | | 8-OWES ADDITIONAL MONEY FOR BUILDING | | | VALUATION AND RADON FEES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-03-30 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-03-30 |
Time |
16:30 |
Rev Time |
0.10 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|