Plan Review Details - Permit 00031388
Plan Review Stops For Permit 00031388
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-04-10 Cont ID  
Sent By dpalmer Date 2000-04-10 Time 20:56 Rev Time 0.00
Received By dpalmer Date 2000-04-10 Time 20:56 Sent To  
Notes
2001-01-08 00:00:00WIRE SIZE FOR AHU 11 KW AND BRKR SIZE
 NOT CORRECT
 MISSING GFI FOR A/C `S

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-13 Cont ID  
Sent By jleech Date 2000-09-13 Time 19:11 Rev Time 0.33
Received By jleech Date 2000-09-13 Time 19:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By cthirben Date 2000-04-05 Time 14:41 Rev Time 1.00
Received By cthirben Date 2000-04-05 Time 14:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-31 Cont ID  
Sent By tlarge Date 2000-03-31 Time 18:45 Rev Time 0.50
Received By tlarge Date 2000-03-31 Time 18:45 Sent To  
Notes
2001-01-08 00:00:00SUBMIT REVISED SAN.RISER PRIOR TO RGH.
 PLBG.INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-05-31 Cont ID  
Sent By rmcdouga Date 2000-05-31 Time 13:52 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-05-12 Cont ID  
Sent By rmcdouga Date 2000-05-12 Time 10:07 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)FORM 600 A-97 OF ENERGY CODE LISTS
 3726 S.F.OF CONDITIONED FLOOR AREA AND
 SHEET C-1 OF PLANS LIST AREA UNDER AIR
 AS 3513 S.F.; CLARIFY
  
 2)SHEET A-5 SPECIFIES R-30 INSULATION
 AND ENERGY CALCULATIONS ARE BASED ON
 R-19 INSULATION,SEE EPL DISPLAY CARD;
 CLARIFY
  
 3)SHEET A-3 SHOWS MEAN ROOF HEIGHT OF
 +17'8",SHEET S-2 LISTS M.R.H.OF 15'-0",
 DESIGN COMPLIANCE FORM SHOWS 24" AND I
 CALCULATE IT TO BE +OR- 18'; CLARIFY
  
 4)SHEET S-3 STATES ASCE 7-93 WAS USED
 FOR CALCULATIONS, THE REFERENCED DESIGN
 STANDARD FOR USE WITH THE 97 SBC IS ASCE
 7-95, WHICH USES WIND LOADS IN EXCESS OF
 140 MPH.CLARIFY
  
 5)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR STORM
 PANELS
  
 6)PRODUCT APPROVALS FOR MULLIONS EXPIRED
 ON 5-1-00. PROVIDE 2 CURRENT COPIES.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-28 Cont ID  
Sent By gjoyce Date 2000-03-28 Time 14:51 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***