Plan Review Details - Permit 00031237
Plan Review Stops For Permit 00031237
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-04-10 Cont ID  
Sent By dpalmer Date 2000-04-10 Time 20:36 Rev Time 0.00
Received By dpalmer Date 2000-04-10 Time 20:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-29 Cont ID  
Sent By cthirben Date 2000-03-29 Time 13:11 Rev Time 1.00
Received By cthirben Date 2000-03-29 Time 13:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-28 Cont ID  
Sent By tlarge Date 2000-03-28 Time 20:05 Rev Time 0.33
Received By tlarge Date 2000-03-28 Time 20:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-08-26 Cont ID  
Sent By jgomez Date 2000-08-26 Time 16:34 Rev Time 1.00
Received By jgomez Date 2000-08-26 Time 15:47 Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVAL SUBMITAL AND UPDATED
 ARCHITECTURAL PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-07-19 Cont ID  
Sent By jgomez Date 2000-07-19 Time 18:04 Rev Time 0.25
Received By jgomez Date 2000-07-19 Time 18:04 Sent To  
Notes
2001-01-08 00:00:00TRUSS DRAWINGS SUBMITTAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-17 Cont ID  
Sent By jgomez Date 2000-05-17 Time 21:45 Rev Time 1.50
Received By jgomez Date 2000-05-17 Time 21:45 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". WILL NEED ELEVATION
 CERTIFICATE.
 2-CLEARLY INDICATE ON PLANS GLAZING
 AREAS TO HAVE SAFETY GLAZING. SEE
 COMMENTS ON PLANS.
 SECTION 2405.2 SBC 1997.
 3-PROVIDE PRODUCT APPROVAL FOR OUTSWING
 ENTRY DOOR WITH SIDELITE ASSEMBLY.
 PLEASE MAKE SURE DRAWINGS ARE LEGIBLE.
 4-PROVIDE COPIES OF THE TEST RESULTS FOR
 SLIDING GLASS DOORS AS PER ASTM E-330.
 SECTION 1706 SBC 1997.
 5-STORM PANELS:
 -REVISE KEY PLAN AND INSTALLATION SCHED
 TO MATCH ARCHITECT'S PLAN ON SHEET A-8
 -USE MASONRY ANCHOR SPACING WHEN PANELS
 ARE TO BE ATTACHED TO MASONRY COLUMNS
 WITH FILLED CELLS.
 6-UPDATE ALL DRAWINGS. SEE COMMENTS ON
 PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-27 Cont ID  
Sent By gjoyce Date 2000-03-27 Time 13:13 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***