Plan Review Details - Permit 00031205
Plan Review Stops For Permit 00031205
Review Stop    
Rev No 1 Status N Date 2000-12-08 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 15:14 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-11-28 Cont ID  
Sent By hpiskura Date 2000-11-28 Time 08:49 Rev Time 0.00
Received By hpiskura Date 2000-11-28 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-28 Cont ID  
Sent By hpiskura Date 2000-09-20 Time 07:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2001-01-08 00:00:00NEEDS IMPACT FEES & RADON PAID

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 19:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 20:52 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 20:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-12-12 Cont ID  
Sent By mgonzale Date 2000-12-12 Time 06:55 Rev Time 0.50
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-04-27 Cont ID  
Sent By mgonzale Date 2000-04-27 Time 15:40 Rev Time 3.00
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
  
 METER SIZE: 1 1/2"
 NSTALLED BY:CONTRACTOR
 IRRIGATION METER:1"
 INSTALLED BY:CONTRACTOR
 PFL SIZE:0"
 INSTALLED BY:CONTRACTOR
 GRAVITY SEWER: 6"
 INSTALLED BY:CONTRACTOR
 SPECIAL COMMENTS:
  
 PASSED WITH PROVISOS:
 STORMWATER:
 CALCULATIONS SUBMITTED ON REPORT ALONG
 WITH PLANS, OK PER JOSE DEL RIOS.
 DRIVEWAY APPROACHES PER CITY OF WEST
 PALM BEACH ALONG WITH COORDINATION WITH
 PLEASE KEEP IN MIND THAT A PERMIT IS
 REQUIRED TO PERFORM WORK ON EITHER OF
 THESE ROW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 15:14 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 15:14 Sent To  
Notes
2001-11-21 00:00:00CANOPY PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-04-04 Cont ID  
Sent By mcarsill Date 2001-04-04 Time 15:22 Rev Time 0.00
Received By mcarsill Date 2001-04-04 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-11-15 Cont ID  
Sent By mcarsill Date 2000-11-15 Time 10:25 Rev Time 0.00
Received By mcarsill Date 2000-11-15 Time 10:25 Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE NOTED ON PLAN
 REVIEW COMMENTS BECAUSE OF TYPOGRAPHICAL
 ERROR. SHOULD HAVE READ NFPA 101-LIFE
 SAFETY CODE, 1985 EDITION.
 2) THE FLAME SPREAD CHARACTERISTICS FOR
 THE CANOPY IS TO BE FURTHER DEFINED.
 THE ONE PAGE INFORMATION SHEET WAS
 LOCATED ATTACHED TO CANOPY PLANS COVER
 SHEET.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF UNDERGROUND
 FUEL TANKS.
  
 APPROVED PROVISO:
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-21 Cont ID  
Sent By mcarsill Date 2000-08-21 Time 11:40 Rev Time 0.00
Received By mcarsill Date 2000-08-21 Time 11:40 Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED IN
 DESIGN CODE BOX. SHOULD READ NFPA 101-
 LIFE SAFETY CODE, 1985 INSTEAD OF NFPA
 101-LIFE SAFETY CODE, 1994.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 IS TO COMPLY WITH CITY CODE REQUIREMENTS
 3) SERVICE STATION IS TO COMPLY WITH
 THE REQUIREMENTS OF NFPA 30A, THE
 STANDARD FOR AUTOMOTIVE AND MARINE
 SERVICE STATION CODE, AND UNIFORM FIRE
 SAFETY RULES AND STANDARDS, CHAPTER
 4A-49.
 4) THE UNDERGROUND FUEL TANKS ARE TO
 COMPLY WITH NFPA 30, THE STANDARD FOR
 THE STORAGE AND HANDLING OF FLAMMABLE
 AND COMBUSTIBLE LIQUIDS.
 5) PLEASE IDENTIFY TYPE SIGNAGE FOR
 EMERGENCY SHUT OFFS FOR FUEL
 DISPENSING EQUIPMENT.
 6) PLEASE INDICATE ON THE PLANS, THE
 LENGTHS OF FUEL HOSES PLANNED FOR USE.
 7) PLEASE IDENTIFY THE LOCATIONS FOR
 WARNING SIGNS AT THE FUEL DISPENSING
 AREA. WHAT WORDING IS PLANNED FOR THESE
 SIGNS.
 8) PLEASE INDICATE BREAKAWAY DEVICE
 LOCATIONS.
 9) PLEASE INDICATE TYPES AND LOCATIONS
 OF FIRE EXTINGUISHERS.
 10) PROVIDE LISTING INFORMATION ON
 DEVICES PLANNED FOR USE AT FUEL
 DISPENSING AREA.
 11) PLEASE PROVIDE INFORMATION ON
 PROPANE STORAGE AREA.
 12) PLEASE PROVIDE FLAME SPREAD
 CHARACTERISTICS ON CANOPY.
 13) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-04 Cont ID  
Sent By ndenmark Date 2000-12-04 Time 15:27 Rev Time 0.50
Received By ndenmark Date 2000-12-04 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 SEPARATE PERMITS ARE REQUIRED FOR FUEL,
 AND WALK IN COOLER AND FREEZER BOXES.
 SUBMIT PLANS FOR THESE AT TIME OF MECH.
 PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-09-05 Cont ID  
Sent By ndenmark Date 2000-09-05 Time 08:53 Rev Time 1.00
Received By ndenmark Date 2000-09-05 Time 08:53 Sent To  
Notes
2001-01-08 00:00:00**************DENIED*******************
 1.PROVIDE INFORMATION ON OUTSIDE AIR PER
 ASHRAE 62-89
 2 PROVIDE AIR BALANCE CALCULATIONS SHOW-
 ING COMPLIANCE WITH 1997 SMC 501.2
 3.PROVIDE DETAIL ON ROOF CURB AND PENE-
 TRATION
 4. NOTE: SEPARATE PERMITS REQUIRED FOR
 WALK- IN COOLER/FREEZERS AND FUEL TANKS
 AND RELATED PIPING.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-03-12 Cont ID  
Sent By jleech Date 2001-03-12 Time 17:19 Rev Time 2.50
Received By jleech Date 2001-03-12 Time 17:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 16:45 Rev Time 1.50
Received By jleech Date 2000-11-14 Time 16:45 Sent To  
Notes
2001-01-08 00:00:001.TIMOTHY LARGE'S NOTE 4 RELOCATE W.H.
 TO FLOOR OR INSTALL A FIXED LADDER.
 6 1/2 FT OFF FLOOR IS NOT READILY
 ACCESSIBLE.
 2.CONDENSATE FROM A/C AND COOLERS
 CANNOT GO TO SANITARY SEWER SYSTEM.
 CONDENSATE SHOULD GO TO STORM OR TO
 A DRYWELL.
 3.IF NATURAL GAS IS NOT TO BE USED
 REMOVE GAS PIPING DIAGRAM FROM
 SHEET #27.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-26 Cont ID  
Sent By tlarge Date 2000-08-26 Time 08:04 Rev Time 1.75
Received By tlarge Date 2000-08-26 Time 06:19 Sent To  
Notes
2001-01-08 00:00:001)CIVIL DRAWING #6-RELOCATE CLEANOUTS
 IN STORM SEWER TO ALIGN WITH THE FLOW.
 SPC SEC.307.5.
  
 2)SHT.FM-1,P-1-MIN.SIZE OF BUILDING
 SEWER SHALL BE 4" PER SPC SEC.714.1,
 FOOTNOTE #2.
  
 3)GREASE TRAP MIN.SIZE SHALL BE 750 GAL.
 PER CITY OF WPB ORDINANCE.CANNOT BE
 INSIDE FOOD PREP AREA.CONTACT R.COMPO
 AT 561-835-7423.SUBMIT APPROVAL FORM
 FROM UTILITIES.
  
 4)WATER HEATERS SHALL BE READILY
 ACCESSIBLE PER SPC SEC.501.7.SUPPLY
 FIXED LADDER OR PLATFORM OR RELOCATE
 W.H.TO FLOOR.
  
 5)RECEPTORS RECEIVING DISCHARGE FROM
 INDIRECT WASTES SHALL BE FLOOR SINKS,NOT
 FLOOR DRAINS.SPC SEC.804.1,807.1.
  
 6)WATER FILTER SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1.
  
 7)TRAP PRIMERS FOR FLOOR DRAINS SHALL
 COMPLY W/SPC SEC.409.4.1.1.
  
 8)DIELECTRIC UNIONS NOT PERMITTED.USE
 DIELECTRIC NIPPLES OR COUPLINGS.SPC
 309.3.
  
 9)GREASY WASTE SYSTEM SHALL COMPLY W/
 SPC SEC.921 FOR COMBINATION WASTE AND
 VENT.
  
 10)SEE ATTACHED REQS.FOR GAS INSTALL-
 ATION.
  
 11)LOCATION AND INSTALLATION OF LP
 SYSTEM SHALL COMPLY W/NFPA 58.SHOW SIZE
 OF LP TANKS(CAPACITY),LOCATION TO
 SOURCES OF IGNITION,BUILDING OPENINGS,
 ETC.SEE NFPA 58,TABLE 3-2.2.2.,
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 07:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-13 Cont ID  
Sent By hpiskura Date 2000-11-28 Time 08:44 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***