Plan Review Details - Permit 00031184
Plan Review Stops For Permit 00031184
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-20 Cont ID  
Sent By lsmith Date 2000-03-28 Time 07:34 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-05-02 Cont ID  
Sent By dpalmer Date 2000-05-02 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2000-05-02 Time 20:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-13 Cont ID  
Sent By dpalmer Date 2000-04-13 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2000-04-13 Time 18:35 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: SERVICE SIZE IS OF SUFFICIENT
 SIZE, BUT YOU STILL NEED TO SUBMIT LOAD
 CALCUALTION TO SHOW ALL LIGHTING AT
 125% FOR CONTINUOUS DUTY.
  
 PLEASE SUBMIT THIS BEFORE YOUR ROUGH
 ELECTRICAL INDPECTION. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 17:10 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 17:10 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUT
 #`S ON PLANS AND SUBMIT NEW REVISED
 PANEL SCHEDULE. SHOW EXISTING SERVICE
 SIZE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS CALL
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-27 Cont ID  
Sent By rturnque Date 2000-03-27 Time 10:36 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-04-14 Cont ID  
Sent By ndenmark Date 2000-04-14 Time 07:16 Rev Time 0.25
Received By ndenmark Date 2000-04-14 Time 07:16 Sent To  
Notes
2001-01-08 00:00:00NO MECH INFORMATION INCLUDED. PROVIDE
 MECH PLANS AT TIME OF MECH PERMIT APPLI-
 CATION PRIOR TO ANY MECH WORK BEING DONE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-04-10 Cont ID  
Sent By ndenmark Date 2000-04-10 Time 07:54 Rev Time 0.25
Received By ndenmark Date 2000-04-10 Time 07:54 Sent To  
Notes
2001-01-08 00:00:00NO MECH PROVIDED TO REVIEW SUBMIT PLANS
 AT TIME OF MECHANICAL PERMIT APPLICATION
 PRIOR TO ANY MECH WORK BEING DONE

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-05-20 Cont ID  
Sent By tlarge Date 2000-05-20 Time 05:37 Rev Time 0.50
Received By tlarge Date 2000-05-20 Time 05:37 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW REQD.30"X 48"CLEAR FLOOR
 SPACE FOR DRINKING FOUNTAIN ON PLAN.DOOR
 SHALL NOT SWING INTO CLEAR FLOOR SPACE
 REQD.FOR FIXTURE PER FACBC SEC.4.22.2.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.INDICATE ON PLAN HOW THIS
 WILL BE ACCOMPLISHED.
  
 TOILET PAPER DISPENSER SHALL BE A MIN.OF
 19"TO CENTER PER FACBC SEC.4.16.6.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-05-03 Cont ID  
Sent By tlarge Date 2000-05-03 Time 06:23 Rev Time 0.25
Received By tlarge Date 2000-05-03 Time 06:23 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY AND WATER RISER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-20 Cont ID  
Sent By tlarge Date 2000-04-18 Time 18:01 Rev Time 0.50
Received By tlarge Date 2000-04-18 Time 18:01 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SIGNED AND SEALED SANITARY AND
 WATER SUPPLY DIAGRAMS FOR REVIEW.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(PROVISIONS SHALL BE MADE FOR
 PERSONS WHO HAVE TROUBLE BENDING OR
 STOOPING.)
  
 DOOR CANNOT SWING INTO CLEAR FLOOR SPACE
 FOR DRINKING FOUNTAIN PER FACBC SEC.
 4.22.2.
  
 ***************PROVISO******************

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-23 Cont ID  
Sent By tlarge Date 2000-03-23 Time 18:06 Rev Time 0.65
Received By tlarge Date 2000-03-23 Time 18:06 Sent To  
Notes
2001-01-08 00:00:00SHOW SIZE OF TOILET STALLS.COMPLY W/
 FACBC SEC.4.1.6 AND FIG.30(B)(C).
  
 URINAL SHALL BE INSTALLED AT HANDICAP
 HEIGHT.CLEARLY SHOW COMPLIANCE ON PLANS.
 COMPLY W/FACBC SEC.4.18.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).
  
 WALLS AND FLOOR IN TOILET ROOM SHALL BE
 NONABSORBENT PER SBC 1204.2.
  
 SUBMIT ELEVATION DETAILS FOR ALL
 HANDICAP FIXTURES.COMPLY W/FACBC FOR ALL
 REQS.