Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-12 Cont ID  
Sent By hpiskura Date 2000-07-12 Time 16:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-07 Cont ID  
Sent By dpalmer Date 2000-07-07 Time 09:12 Rev Time 0.00
Received By dpalmer Date 2000-07-07 Time 09:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-28 Cont ID  
Sent By dpalmer Date 2000-06-28 Time 21:06 Rev Time 0.00
Received By dpalmer Date 2000-06-28 Time 21:06 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: NOTE ENOUGH INFORMATION ON ALL
 LOCATIONS OF EQUIPMENT? PLEASE SHOW
 WHERE MAINS WILL BE GROUPED WITH THE
 EXISTING SERVICE FOR BLDG. 230-72
  
 2)NOTE: PLEASE SHOW LOCATIONS OF EQUIP.
 ON E-1 AND MAINS.,
 SUBMIT AIC RATINGS FOR ALL PANELS AND
 MAIN DISCONNECT BEING INSTALLED. MAINS/
 PANELS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. 110-9
  
 PLEASE SUBMIT ALL THEABOVE INFOMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-29 Cont ID  
Sent By rturnque Date 2000-06-29 Time 12:41 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-15 Cont ID  
Sent By gjoyce Date 2000-03-24 Time 11:44 Rev Time 0.50
Received By gjoyce Date 2000-03-24 Time 11:43 Sent To  
Notes
2001-01-08 00:00:00CLASS B REQUIRED FOR PERMIT AS SHOWN