| Plan Review Stops For Permit 00030999 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-27 |
Time |
11:45 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-27 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-05-30 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-05-30 |
Time |
10:39 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | A. SPOKE TO CONTRACTOR 786-412-0688 | | | THE FOLLOWING ITEMS ARE REQUIRED. | | | 2. ALL EXTERIOR GLASZING IS BY CITYPLACE | | | OK GLAZING INSTALLED BY CITYPLACE AND | | | IS NOW IN PLACEOK 5/30/00 OWNER. | | | 3. FIRE SPRINKLER CONTRACTOR TO SUBMIT | | | PERMIT. | | | 4. INFORMATION ON IMPACT GLAZING IS NOT | | | SEE ABOVE OK 5/30/00 | | | SYSTEM IS TO BE CONSIDERED FOR USE. | | | 5. CONTRACTOR TO APPLY FOR PERMIT AND | | | PAY ALL FEES DUE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-04-26 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-04-26 |
Time |
15:29 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 4/26/00 | | | 1. FLORIDA ENERGY SHEETS | | | 2. LETTER FROM SPECIAL INSPECTOR | | | RELEASING THE PERMIT. | | | 3. FP-1 & 2 NOT SIGNED AND SEALED. | | | 4. FIRE SPRINKLER PERMIT NOT APPLIED FOR | | | 5. CONTRACTOR TO MAKE APPLICATION FOR | | | PERMIT AND PAY FEES DUE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-23 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-03-23 |
Time |
12:13 |
Rev Time |
2.50 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ANY EXTERIOR GLAZING INSTALLED SHALL BE | | | IMPACT RESISTANT. SUBMIT PRODUCT | | | APPROVAL INFORMATION PRIOR TO INSTALLING | | | | | | SIGNS ARE NOT COVERED BY THIS PERMIT. | | | | | | ESCULATOR OPEANING SHALL COMPLY WITH | | | 1997 SBC SECTION 705.2.2(8), A OR B. | | | | | | ALL WOOD SHALL BE PRESSURE TREATED FIRE | | | RETARDANT LUMBER. SEE 1997 SBC TYPE II | | | BUILDINGS SECTION 604. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-22 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-22 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-04-26 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-04-26 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-21 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-21 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR MAIN AND EACH PANEL. | | | | | | 2)NOTE: SUBMIT AIC RATINGS OF ALL MAINS | | | AND RATINGS OF BRANCH BRKRS. PER 110-9 | | | | | | 3)NOTE; NEED TO SUBMIT LINE DIAGRAM OF | | | SERVICE .TO INCLUDECONDUITS, WIRE SIZE | | | COMPLETE GROUNDING SYSTEM. | | | | | | 4)NOTE: SUBMIT PANEL SCHEDULES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-21 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-21 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-03-23 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-03-23 |
Time |
12:12 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE REVIEW NOTES ATTACHED TO PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-27 |
Time |
11:33 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-09-27 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-23 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-03-23 |
Time |
14:22 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-03-23 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE FIRE DEPT NOTES ON KITCHEN EQUIPMENT |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-09-22 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-22 |
Time |
18:24 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-09-22 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ********************PROVISO************* | | | 1)SHT.P-3-RESTROOM AND CAFE ISOMETRIC.- | | | DESIGN OF THE SANITARY SYSTEM SHALL | | | COMPLY W/SPC SEC.914.1,920.3 FOR CIRCUIT | | | AND LOOP SYSTEM. | | | | | | 2)WATER HEATER SHALL BE READILY | | | ACCESSIBLE.SUPPLY SHIP'S LADDER AND | | | PLATFORM OR RELOCATE WATER HEATER TO | | | FLOOR.SPC SEC.501.7. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-04-25 |
Time |
15:37 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION REVIEWED AS / UPDATE 4-6-00 | | | FROM NOTES BY T/L 3-23-00.PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-03-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-23 |
Time |
06:38 |
Rev Time |
6.00 |
| Received By |
tlarge |
Date |
2000-03-23 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT REVISED OCCUPANT LOAD | | | CALCULATIONS TO ENSURE COMPLIANCE W/SPC | | | TABLE 407 FOR MIN.NUMBER OF REQD. | | | SANITARY FACILITIES.(ADD'L.LAVS MAY BE | | | REQD.)SPC SEC.407.1.3. IS SPECIFIC TO | | | THE AREAS ALLOWED TO BE DEDUCTED. | | | | | | SHT.A-100-SHOW REQD.WHEELCHAIR TURNING | | | SPACE IN THE TOILET ROOM AND RESTROOMS | | | PER FACBC SEC.4.2.3. | | | | | | BREAKROOM SINK SHALL COMPLY W/FACBC SEC. | | | 4.24.1.-4.24.7. | | | | | | A FLOOR DRAIN IS REQD.IN THE 1ST FLR. | | | TOILET ROOM PER SPC SEC.409.4.1.1. | | | | | | WALLS AND FLOOR IN FIRST FLOOR TOILET | | | ROOM SHALL BE NONABSORBENT MATERIAL TO A | | | HEIGHT OF 4'PER SPC SEC.1204.2. | | | | | | URINAL SHALL COMPLY W/FACBC SECS.4.18.1- | | | 4.18.4. | | | | | | SHT.A200-TOWEL DISPENSER W/O WASTE SHALL | | | COMPLY W/FACBC SEC.4.2.5.,4.2.6 AND FIG. | | | 6. | | | | | | SHT.A200-THE LAVS IN THE HANDICAP TOILET | | | STALLS SHALL COMPLY W/FACBC SEC.4.17.3. | | | (CANNOT INFRINGE ON CLEAR FLOOR SPACE | | | FOR WATER CLOSET.) | | | | | | WATER SOFTENER SHALL BE NSF APPROVED PER | | | SPC SEC.615. | | | | | | SHT.A-220-CAFE EQUIP.SCHEDULE #27 NOTES | | | GREASE TRAP IN FLOOR.GREASE TRAP CANNOT | | | BE LOCATED IN FOOD PREP AREA PER BOARD | | | OF HEALTH REQS.AND CITY ORDINANCE. | | | | | | SUBMIT WATER SUPPLY RISER PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | RELIEF DRAINS SHALL DISCHARGE TO EXTER- | | | IOR PER COUNTYWIDE AMENDMENTS TO SPC SEC | | | 507.6(3). | | | | | | SHT.P-3.1-1/2" VENT NOT PERMITTED ON | | | GREASY WASTE PER TABLE 920.4. | | | | | | DESIGN OF CIRCUIT AND LOOP SYSTEM FOR | | | RESTROOMS SHALL COMPLY W/SPC SEC.914. | | | | | | PLANS SHALL BE ROUTED TO DEPT. OF | | | BUSINESS REGULATION FOR REVIEW PER | | | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 | | | | | | | | | | | | SUBMIT ENLARGED ARCH.PLAN VIEW AND | | | PLUMBING PLAN VIEW FOR THE 1ST.FLR. | | | TOILET ROOM PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1. |
|
|