Plan Review Details - Permit 00030957
Plan Review Stops For Permit 00030957
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-04 Cont ID  
Sent By dpalmer Date 2000-05-04 Time 16:43 Rev Time 0.00
Received By dpalmer Date 2000-05-04 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-10 Cont ID  
Sent By dpalmer Date 2000-04-10 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2000-04-10 Time 19:25 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 MAIN. MAINS ARE TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9/215-5
 PLEASE SHOW.
  
 2)NOTE: BLDG.STEEL MUST BE PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250-50
 PLEASE SHOW. 215-5
  
 3)NOTE: PLEASE NOTE THAT ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.210-8-A-6 THIS INCLUDE
 -S BREAKFAST AREA.
  
 4)NOTE: CHECK FOR 2` OF WALL IN KITCHEN
 AREA 210-52 AND ALSO OUTLET FOR KITCHEN
 HALL EITHER 2` RULE OR HALL REQ`MENT
 210-52H
  
 PLANS WOULD HAVE PASSED WITH PROVISO
 AND RED LINES BUT AIC RATINGS MUST BE ON
 ALL PLANS.
 PLEASE SUBMIT THE ABOVE FOR REIVEW. IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-23 Cont ID  
Sent By cthirben Date 2000-03-23 Time 07:46 Rev Time 1.00
Received By cthirben Date 2000-03-23 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-06-07 Cont ID  
Sent By tlarge Date 2000-06-07 Time 14:08 Rev Time 0.25
Received By tlarge Date 2000-06-07 Time 14:08 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-05-30 Cont ID  
Sent By tlarge Date 2000-05-30 Time 10:04 Rev Time 0.25
Received By tlarge Date 2000-05-30 Time 10:04 Sent To  
Notes
2001-01-08 00:00:00SANITARY RISER SHALL BE SIGNED AND
 SEALED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-17 Cont ID  
Sent By tlarge Date 2000-03-17 Time 17:27 Rev Time 0.50
Received By tlarge Date 2000-03-17 Time 17:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-04 Cont ID  
Sent By fknapp Date 2000-05-04 Time 11:28 Rev Time 5.00
Received By fknapp Date 2000-05-04 Time 09:33 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR ALL
 EXTERIOR SWING DOOR ASSEMBLIES.
  
 2)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR
 ALL MULLIONS.
  
 3)PROVIDE ROOF SHEATHING NAILING ZONES
 THAT COMPLY WITH CITY AMENDMENTS
 FIG. 2306.1 4" OC ZONE 3 EDGES.
  
 4)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-04 Cont ID  
Sent By gjoyce Date 2000-05-04 Time 14:03 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***