Plan Review Details - Permit 00030836
Plan Review Stops For Permit 00030836
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-09-25 Cont ID  
Sent By jwitmer Date 2001-09-25 Time 13:13 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-09-25 00:00:00TRUSS SHOP DRAWINGS OK 9/25/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-08-16 Cont ID  
Sent By jwitmer Date 2001-08-16 Time 15:43 Rev Time 0.50
Received By jwitmer Date 2001-08-16 Time 15:43 Sent To  
Notes
2001-08-16 00:00:00BUILDING PLAN REVIEW: TRUSS PLAN
 PERMIT # 00030836
 2900 N AUSTRALIAN AV
  
 1)- FL S.S. 471 ENGEENERED PLANS REQUIRE
 SIGNED/ SEALED PLANS
  
 2)- DETAIL OF ADDING A VERTICAL SUPPORT-
 ING MEMBER NO GUSSET INFORMATION THICK-
 NESS OF GUSSET SIZE OF AREA REQUIRED OR
 NAILING SIZE,SPACING OR PATTERN?
  
 3)- TRUSS DETAIL SHOWING THE LOADING
 POINT LOADING?
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-12-18 Cont ID  
Sent By jwitmer Date 2000-12-18 Time 12:09 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: PROVIDE PRODUCT APPROVAL FOR
 WINDOWS, DOORS & ROOFING BEFORE FIRST
 INSPECTION JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-18 Cont ID  
Sent By lmartine Date 2000-09-18 Time 10:31 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 2ND REVIEW
 ----------
  
 PLEASE REFER TO ORIGINAL COMMENTS DATED
 MAY 1,2000[COPY ATTACHED]
  
 1]COMPIANCE WITH SBC TABLE 500 ALLOWABLE
 BUILDING AREA HAS NOT BEEN PROVIDED.
 LETTER FROM ENGINEER DATED 7/31/00
 CALLS FOR EXISTING WALL TO BE MODIFIED
 TO 4HR CONSTRUCTION.FIRST VERIFY THAT
 CLASS B-4 BLOCK EXIST,THEN EXPLAIN
 WHAT THE CELLS WILL BE FILLED WITH AND
 HOW THIS WILL BE PERFORMED.
 2]OK
 3]OK
 4]INFORMATION REQUESTED HAS NOT BEEN
 PROVIDED.
 5]SUBMIT STORM SHUTTER TEST REPORTS.
 6]INFORMATION REQUESTED HAS NOT BEEN
 PROVIDED.
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096#8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-05-01 Cont ID  
Sent By hpiskura Date 2000-05-01 Time 16:48 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER ATTACHED TO PLAN

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-02-27 Cont ID  
Sent By dpalmer Date 2001-02-27 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2001-02-27 Time 11:07 Sent To  
Notes
2001-02-27 00:00:00***************** REVISION/ PROVISO ****
  
 1)NOTE: PLEASE HAVE PLANS REDRAWN BEFORE
  
 FINAL ELECTRICAL INSPECTION IS CALLED
 IN. ALL CHNAGES THAT AHVE BEEN HAND
 DRAWN NEED TO BE REDONE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-11-21 Cont ID  
Sent By dpalmer Date 2000-11-21 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 18:32 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 PLANS WERE RESUBMITTED W/ THE SAME THING
 -S SHOWN FOR THE LAST REVIEW.??
 PLANS ARE STILL DATED FROM BEFORE THE
 LAST REVIEW BY JAKE LEAHY??
  
 PLEASE CALL TO SET UP AN APPOINTMENT FOR
 CLARIFICATION ON CODES ISSUES WITH THE
 CHIEF ELECTRICAL INSPECTOR AND MYSELF
 THE ELECTRICAL PLAN REVIEWER....
  
 PLEASE CALL!!.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-16 Cont ID  
Sent By jleahy Date 2000-08-16 Time 13:56 Rev Time 1.30
Received By dpalmer Date 2000-08-16 Time 13:23 Sent To  
Notes
2001-01-08 00:00:001-LOAD CALCULATION IS NO DONE IN ACCORDA
 WITH THE CODE
 1- LIGHTING LOADS ARE FIGURED PER ART.
 220-3A FOR SERVICE CALCS.
 2- IF USING THE FIXTURES THEY ARE FIGU
 USING THE HIGHEST AMPERAGE ON BALST
 NOT BULB SIZE.THEN THEY HAVE TO B
 A LARGER LOAD THAN 220-3A WOULD BE
 3- POWER OUTLETS ARE FIGURED AT 180VA
 PER EACH BUT I CAN ONLY COUNT 57 OF
 THEM.
 4- CONTINUOUS LOAD FACTORS AND MOTOR
 CONTRIBUTION IS NOT SHOWN ALSO!
 2- MAINS ARE TO BE GROUPED AND LABELED!!

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 20:09 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 20:09 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO *****************
  
 1)NOTE: SHOW ALL MEANS OF EGRESS LIGHT-N
 -ING. 210-70
  
 2)NOTE:SHOW RECEPT ON ROOF REQ`D FOR
 A/C 210-63.
  
 3)NOTE: ON E-1 FOR KITCHEN EXHAUST YOU
 SHOW 180 HP? PLEASE CORRECT.
  
 4)NOTE:PLEASE NOTE ART 362-4 FOR SIZING
 OF WIREWAY FOR 600 MCM
  
 5)NOTE: PLEASE SHOW THE BREAK DOWN ON
 THE LOAD CALCULATION. PLEASE SHOW THE
 CONTINUOUS LOADS (LIGHTING ETC) FIGURED
 AT 125% PER 210-20
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. THE PLANS WOULD HAVE PASSED WITH
 A PROVISO BUT WERE COMING BACK FOR PLUMB
 CORRECTIONS. PLEASE MAKE THE ELECTRICAL
 CHANGES. IF THERE ARE ANY QUESTIONS CALL
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-05 Cont ID  
Sent By pkrauss Date 2001-03-05 Time 14:28 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-03-01 Cont ID  
Sent By mcarsill Date 2001-03-01 Time 12:23 Rev Time 0.00
Received By mcarsill Date 2001-03-01 Time 12:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-12-14 Cont ID  
Sent By mcarsill Date 2000-12-14 Time 14:13 Rev Time 0.00
Received By mcarsill Date 2000-12-14 Time 14:12 Sent To  
Notes
2001-01-08 00:00:001) PROVIDE DETAILS OF FIRE RATING OF
 WALLS PROVIDING EXITING FROM WORSHIP
 CENTER.
 2) ADDRESS ON BUILDING REQUIRED PER
 CITY CODE REQUIREMENTS.
 3) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR THE FIRE ALARM SYSTEM.
 4) PROVIDE COMPLETE HOOD, DUCT AND
 EXTINGUISHING SYSTEM PLANS TO THIS
 OFFICE.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-24 Cont ID  
Sent By rturnque Date 2000-03-24 Time 15:31 Rev Time 0.40
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE ALARM SYSTEM SHALL BE CLASS "A"
 PROVIDE SHOP DRAWINGS AND PERMIT FOR
 HOOD AND EXTINGUISHING SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-02-28 Cont ID  
Sent By pkrauss Date 2001-02-28 Time 13:30 Rev Time 0.45
Received By pkrauss Date 2001-02-28 Time 11:38 Sent To  
Notes
2001-02-28 00:00:00NOTE:MINIMUM OF 10' BETWEEN INTAKE AND
 EXHAUST OPENINGS.
  
 FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR REQUIRED WITH NOTIFI-
 CATION TO HORN/STROBE IN OCCUPIED
 AREAS, AS PER NFPA 90A 4-4.4.3.
 OPERATION TO BE TESTED BEFORE
 FINAL C.O.
  
 IS THE WALL RATED BETWEEN FELLOW-
 SHIP HALL AND HALLWAY TOWARDS THE
 LIBRARY?IF SO, FIRE DAMPER
 REQUIRED.ALSO, ACOUSTICAL
 CEILING JUST IN FELLOWSHIP HALL
 OR INTO THE HALLWAY?ACCESS-
 IBILITY TO AHU'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-19 Cont ID  
Sent By ndenmark Date 2000-12-19 Time 10:09 Rev Time 0.50
Received By ndenmark Date 2000-12-19 Time 10:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-08-14 Cont ID  
Sent By ndenmark Date 2000-08-14 Time 14:46 Rev Time 0.50
Received By ndenmark Date 2000-08-14 Time 14:46 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89
 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2
 3.NO ROOFTOP DRAWING INDICATING LOCATION
 OF RTU'S AND EXHAUST FAN TERMINATION AND
 REQUIRED DISTANCE FROM EACH OTHER
 4. IF EXHAUST FANS WORK WITH LIGHT
 SWITCH PER A/C 1, THEY CAN NOT BE USED
 AS PART OF THE AIR BALANCE SCHEDULE REQ-
 UIRED IN NOTE 2.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-03-30 Cont ID  
Sent By cthirben Date 2000-03-27 Time 15:02 Rev Time 1.00
Received By ndenmark Date 2000-03-27 Time 14:44 Sent To  
Notes
2001-01-08 00:00:00 
 **************(DENIED)******************
  
 AIR CONDITIONING SYSTEM TO BE DESIGNED
 BY LICENSED ENGINEER PER F.S. 471.003(2)
 I
 NOTE:
 2. SEPERATE PERMIT REQUIRED FOR HOOD
 INSTALLATION.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-03-04 Cont ID  
Sent By pschmitz Date 2001-03-04 Time 07:50 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-03-04 00:00:00PLUMBING PLAN REVIEW RE-SUB,PROVISO
 SEE SHT P-1 & P-2
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-12-14 Cont ID  
Sent By jleech Date 2000-12-14 Time 16:12 Rev Time 1.00
Received By pschmitz Date 2000-12-14 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-16 Cont ID  
Sent By tlarge Date 2000-08-16 Time 16:18 Rev Time 1.50
Received By tlarge Date 2000-08-16 Time 16:18 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT APPROVAL FROM CITY OF WEST PALM
 BEACH UTILITIES FOR GREASE TRAP.CONTACT
 R.COMPO AT 561-835-7423.
  
 2)SUBMIT DETAIL OF GREASE TRAP.SEE
 ATTACHED.
  
 3)SIZING OF GAS PIPE TO RANGE SHALL
 COMPLY W/TABLE 305.4(A).LOAD SHALL BE
 BASED ON 70'FROM FURTHEST OUTLET.
  
 4)A UNION IS REQD.DOWNSTREAM OF THE SHUT
 OFF VALVES PER NFPA 54,SEC.5.5.2.
  
 5)SHOW LOACTION OF AUTOMATIC SHUTOFF
 VALVE (FIRE VALVE)ON GAS LINE PER NFPA
 96,SEC.7-4.
  
 6)MIN.SIZE DRAIN U/G SHALL BE 2" PER
 SPC SEC.714.4.
  
 7)SUBMIT CALCULATIONS FOR STORM DRAIN-
 AGE SYSTEM.SHOW SQ.FT.AREA DRAINED BY
 EACH DRAIN,AND INCLUDE 1/2 THE AREA OF
 PARAPET WALLS TO THE HORIZONTAL PROJECT-
 ION.SUBMIT CALCULATIONS FOR SECONDARY
 DRAINAGE.SIZE PER SPC SEC.1109.3 AND
 APPENDIX "A".
  
 NOTE:PLEASE PUT THESE PLANS TOGETHER IN
 AN ORDERLY MANNER AND SUBMIT 2 COMPLETE
 SETS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-24 Cont ID  
Sent By tlarge Date 2000-03-24 Time 17:11 Rev Time 1.50
Received By pschmitz Date 2000-03-24 Time 17:11 Sent To  
Notes
2001-01-08 00:00:00APPROVAL REQD.FROM CITY OF WPB UTILITIES
 FOR GREASE TRAP.CONTACT R.COMPO OR
 B.KAMP AT 561-835-7423.SUBMIT APPROVAL
 FORM FROM UTILITIES.
  
 MIN.REQD.SANITARY FACILITIES SHALL
 COMPLY W/SPC SEC.407.1.3.OCCUPANT LOAD
 FOR HALL AND CLASSROOMS REQD.TO ENSURE
 COMPLIANCE W/TABLE 407.
  
 MOP DRAIN NOT SHOWN ON FLOOR PLAN & CAN
 WASH & MOP DRAIN NOT PROPERLY VENTED.
 SPC SEC.901.2.
  
 D.W.CANNOT DISCHARGE INTO GREASE INTER-
 CEPTOR PER CITY OF WPB ORDINANCE.
  
 DISHWASHER SHALL COMPLY W/SPC SEC.
 409.1.2.
  
 DRINKING FOUNTAINS REQD.AMOUNT SHALL
 COMPLY W/SPC TABLE 407.
  
 SUBMIT DETAIL OF GREASE TRAP.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SIZING OF GAS PIPE TO RANGE SHALL COMPLY
 W/SGC TABLE 305.4(A).
  
 AUTOMATIC SHUT-OFF VALVE (FIRE VALVE)AND
 UNION REQD.UPSTREAMOF GAS EQUIPMENT
 PER NFPA 96,SEC.7-4,NFPA 54 SEC.5.5.4.
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPD SEC.409.4.1.1.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-21 Cont ID  
Sent By ajones Date 2000-03-21 Time 10:49 Rev Time 0.25
Received By ajones Date   Time   Sent To  
Notes
***NONE***