| Plan Review Stops For Permit 00030836 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-25 |
Time |
13:13 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-25 00:00:00 | TRUSS SHOP DRAWINGS OK 9/25/01 JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-16 |
Time |
15:43 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2001-08-16 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2001-08-16 00:00:00 | BUILDING PLAN REVIEW: TRUSS PLAN | | | PERMIT # 00030836 | | | 2900 N AUSTRALIAN AV | | | | | | 1)- FL S.S. 471 ENGEENERED PLANS REQUIRE | | | SIGNED/ SEALED PLANS | | | | | | 2)- DETAIL OF ADDING A VERTICAL SUPPORT- | | | ING MEMBER NO GUSSET INFORMATION THICK- | | | NESS OF GUSSET SIZE OF AREA REQUIRED OR | | | NAILING SIZE,SPACING OR PATTERN? | | | | | | 3)- TRUSS DETAIL SHOWING THE LOADING | | | POINT LOADING? | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2000-12-18 |
Time |
12:09 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: PROVIDE PRODUCT APPROVAL FOR | | | WINDOWS, DOORS & ROOFING BEFORE FIRST | | | INSPECTION JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-18 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-18 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | 2ND REVIEW | | | ---------- | | | | | | PLEASE REFER TO ORIGINAL COMMENTS DATED | | | MAY 1,2000[COPY ATTACHED] | | | | | | 1]COMPIANCE WITH SBC TABLE 500 ALLOWABLE | | | BUILDING AREA HAS NOT BEEN PROVIDED. | | | LETTER FROM ENGINEER DATED 7/31/00 | | | CALLS FOR EXISTING WALL TO BE MODIFIED | | | TO 4HR CONSTRUCTION.FIRST VERIFY THAT | | | CLASS B-4 BLOCK EXIST,THEN EXPLAIN | | | WHAT THE CELLS WILL BE FILLED WITH AND | | | HOW THIS WILL BE PERFORMED. | | | 2]OK | | | 3]OK | | | 4]INFORMATION REQUESTED HAS NOT BEEN | | | PROVIDED. | | | 5]SUBMIT STORM SHUTTER TEST REPORTS. | | | 6]INFORMATION REQUESTED HAS NOT BEEN | | | PROVIDED. | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 561-659-8096#8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-05-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-05-01 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER ATTACHED TO PLAN |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-02-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-27 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-27 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2001-02-27 00:00:00 | ***************** REVISION/ PROVISO **** | | | | | | 1)NOTE: PLEASE HAVE PLANS REDRAWN BEFORE | | | | | | FINAL ELECTRICAL INSPECTION IS CALLED | | | IN. ALL CHNAGES THAT AHVE BEEN HAND | | | DRAWN NEED TO BE REDONE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE FINAL ELECTRICAL | | | INSPECTION. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-21 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-21 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | PLANS WERE RESUBMITTED W/ THE SAME THING | | | -S SHOWN FOR THE LAST REVIEW.?? | | | PLANS ARE STILL DATED FROM BEFORE THE | | | LAST REVIEW BY JAKE LEAHY?? | | | | | | PLEASE CALL TO SET UP AN APPOINTMENT FOR | | | CLARIFICATION ON CODES ISSUES WITH THE | | | CHIEF ELECTRICAL INSPECTOR AND MYSELF | | | THE ELECTRICAL PLAN REVIEWER.... | | | | | | PLEASE CALL!!. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-08-16 |
Time |
13:56 |
Rev Time |
1.30 |
| Received By |
dpalmer |
Date |
2000-08-16 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1-LOAD CALCULATION IS NO DONE IN ACCORDA | | | WITH THE CODE | | | 1- LIGHTING LOADS ARE FIGURED PER ART. | | | 220-3A FOR SERVICE CALCS. | | | 2- IF USING THE FIXTURES THEY ARE FIGU | | | USING THE HIGHEST AMPERAGE ON BALST | | | NOT BULB SIZE.THEN THEY HAVE TO B | | | A LARGER LOAD THAN 220-3A WOULD BE | | | 3- POWER OUTLETS ARE FIGURED AT 180VA | | | PER EACH BUT I CAN ONLY COUNT 57 OF | | | THEM. | | | 4- CONTINUOUS LOAD FACTORS AND MOTOR | | | CONTRIBUTION IS NOT SHOWN ALSO! | | | 2- MAINS ARE TO BE GROUPED AND LABELED!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-25 |
Time |
20:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-25 |
Time |
20:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************PROVISO ***************** | | | | | | 1)NOTE: SHOW ALL MEANS OF EGRESS LIGHT-N | | | -ING. 210-70 | | | | | | 2)NOTE:SHOW RECEPT ON ROOF REQ`D FOR | | | A/C 210-63. | | | | | | 3)NOTE: ON E-1 FOR KITCHEN EXHAUST YOU | | | SHOW 180 HP? PLEASE CORRECT. | | | | | | 4)NOTE:PLEASE NOTE ART 362-4 FOR SIZING | | | OF WIREWAY FOR 600 MCM | | | | | | 5)NOTE: PLEASE SHOW THE BREAK DOWN ON | | | THE LOAD CALCULATION. PLEASE SHOW THE | | | CONTINUOUS LOADS (LIGHTING ETC) FIGURED | | | AT 125% PER 210-20 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. THE PLANS WOULD HAVE PASSED WITH | | | A PROVISO BUT WERE COMING BACK FOR PLUMB | | | CORRECTIONS. PLEASE MAKE THE ELECTRICAL | | | CHANGES. IF THERE ARE ANY QUESTIONS CALL | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-03-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-05 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-03-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-01 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-01 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-14 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-14 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PROVIDE DETAILS OF FIRE RATING OF | | | WALLS PROVIDING EXITING FROM WORSHIP | | | CENTER. | | | 2) ADDRESS ON BUILDING REQUIRED PER | | | CITY CODE REQUIREMENTS. | | | 3) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR THE FIRE ALARM SYSTEM. | | | 4) PROVIDE COMPLETE HOOD, DUCT AND | | | EXTINGUISHING SYSTEM PLANS TO THIS | | | OFFICE. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-03-24 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-03-24 |
Time |
15:31 |
Rev Time |
0.40 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FIRE ALARM SYSTEM SHALL BE CLASS "A" | | | PROVIDE SHOP DRAWINGS AND PERMIT FOR | | | HOOD AND EXTINGUISHING SYSTEM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-02-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-28 |
Time |
13:30 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-02-28 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2001-02-28 00:00:00 | NOTE:MINIMUM OF 10' BETWEEN INTAKE AND | | | EXHAUST OPENINGS. | | | | | | FAN SHUT DOWN BY DUCT SMOKE | | | DETECTOR REQUIRED WITH NOTIFI- | | | CATION TO HORN/STROBE IN OCCUPIED | | | AREAS, AS PER NFPA 90A 4-4.4.3. | | | OPERATION TO BE TESTED BEFORE | | | FINAL C.O. | | | | | | IS THE WALL RATED BETWEEN FELLOW- | | | SHIP HALL AND HALLWAY TOWARDS THE | | | LIBRARY?IF SO, FIRE DAMPER | | | REQUIRED.ALSO, ACOUSTICAL | | | CEILING JUST IN FELLOWSHIP HALL | | | OR INTO THE HALLWAY?ACCESS- | | | IBILITY TO AHU'S. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-19 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-19 |
Time |
10:09 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-12-19 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-14 |
Time |
14:46 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-08-14 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1.PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89 | | | 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3.NO ROOFTOP DRAWING INDICATING LOCATION | | | OF RTU'S AND EXHAUST FAN TERMINATION AND | | | REQUIRED DISTANCE FROM EACH OTHER | | | 4. IF EXHAUST FANS WORK WITH LIGHT | | | SWITCH PER A/C 1, THEY CAN NOT BE USED | | | AS PART OF THE AIR BALANCE SCHEDULE REQ- | | | UIRED IN NOTE 2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-03-30 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-03-27 |
Time |
15:02 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-03-27 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | **************(DENIED)****************** | | | | | | AIR CONDITIONING SYSTEM TO BE DESIGNED | | | BY LICENSED ENGINEER PER F.S. 471.003(2) | | | I | | | NOTE: | | | 2. SEPERATE PERMIT REQUIRED FOR HOOD | | | INSTALLATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-03-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-03-04 |
Time |
07:50 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-04 00:00:00 | PLUMBING PLAN REVIEW RE-SUB,PROVISO | | | SEE SHT P-1 & P-2 | | | END OF COMMENTS PAUL SCHMITZ | | | 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-14 |
Time |
16:12 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2000-12-14 |
Time |
16:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-16 |
Time |
16:18 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-08-16 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT APPROVAL FROM CITY OF WEST PALM | | | BEACH UTILITIES FOR GREASE TRAP.CONTACT | | | R.COMPO AT 561-835-7423. | | | | | | 2)SUBMIT DETAIL OF GREASE TRAP.SEE | | | ATTACHED. | | | | | | 3)SIZING OF GAS PIPE TO RANGE SHALL | | | COMPLY W/TABLE 305.4(A).LOAD SHALL BE | | | BASED ON 70'FROM FURTHEST OUTLET. | | | | | | 4)A UNION IS REQD.DOWNSTREAM OF THE SHUT | | | OFF VALVES PER NFPA 54,SEC.5.5.2. | | | | | | 5)SHOW LOACTION OF AUTOMATIC SHUTOFF | | | VALVE (FIRE VALVE)ON GAS LINE PER NFPA | | | 96,SEC.7-4. | | | | | | 6)MIN.SIZE DRAIN U/G SHALL BE 2" PER | | | SPC SEC.714.4. | | | | | | 7)SUBMIT CALCULATIONS FOR STORM DRAIN- | | | AGE SYSTEM.SHOW SQ.FT.AREA DRAINED BY | | | EACH DRAIN,AND INCLUDE 1/2 THE AREA OF | | | PARAPET WALLS TO THE HORIZONTAL PROJECT- | | | ION.SUBMIT CALCULATIONS FOR SECONDARY | | | DRAINAGE.SIZE PER SPC SEC.1109.3 AND | | | APPENDIX "A". | | | | | | NOTE:PLEASE PUT THESE PLANS TOGETHER IN | | | AN ORDERLY MANNER AND SUBMIT 2 COMPLETE | | | SETS. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-03-24 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-24 |
Time |
17:11 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
2000-03-24 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVAL REQD.FROM CITY OF WPB UTILITIES | | | FOR GREASE TRAP.CONTACT R.COMPO OR | | | B.KAMP AT 561-835-7423.SUBMIT APPROVAL | | | FORM FROM UTILITIES. | | | | | | MIN.REQD.SANITARY FACILITIES SHALL | | | COMPLY W/SPC SEC.407.1.3.OCCUPANT LOAD | | | FOR HALL AND CLASSROOMS REQD.TO ENSURE | | | COMPLIANCE W/TABLE 407. | | | | | | MOP DRAIN NOT SHOWN ON FLOOR PLAN & CAN | | | WASH & MOP DRAIN NOT PROPERLY VENTED. | | | SPC SEC.901.2. | | | | | | D.W.CANNOT DISCHARGE INTO GREASE INTER- | | | CEPTOR PER CITY OF WPB ORDINANCE. | | | | | | DISHWASHER SHALL COMPLY W/SPC SEC. | | | 409.1.2. | | | | | | DRINKING FOUNTAINS REQD.AMOUNT SHALL | | | COMPLY W/SPC TABLE 407. | | | | | | SUBMIT DETAIL OF GREASE TRAP.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | SIZING OF GAS PIPE TO RANGE SHALL COMPLY | | | W/SGC TABLE 305.4(A). | | | | | | AUTOMATIC SHUT-OFF VALVE (FIRE VALVE)AND | | | UNION REQD.UPSTREAMOF GAS EQUIPMENT | | | PER NFPA 96,SEC.7-4,NFPA 54 SEC.5.5.4. | | | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPD SEC.409.4.1.1. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-03-21 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2000-03-21 |
Time |
10:49 |
Rev Time |
0.25 |
| Received By |
ajones |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|