Plan Review Details - Permit 00030730
Plan Review Stops For Permit 00030730
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-10 Cont ID  
Sent By dpalmer Date 2000-04-10 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2000-04-10 Time 18:40 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:SHOW A/C EQUIPMENT ON ELEC PALNS
 TO INCLUDE OUTSIDE COND.W/DISC 440-11
 NEED TO SHOW THE SIZE OF EXISTING MAIN.
 215-5 NEED TO SUBMIT REVISED RISER/AND
 PANEL SCHEDULES.
  
 2)NOTE: NEED TO SHOW ON PANEL SCHEDULE
 THE REQ`D DEDICATED CIRCUT FOR BATH(S)
 AS PER 210-11-C-3/215-5
  
 3)NOTE: NEED TO SHOW ALL SMOKE DETECTORS
 REQ`D BY NFPA-72 2-2.1.1.1 INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS AND ROOMS
 THAT MAY BE CONVERTED INTO SLEEPING
 ROOMS,(LIKE THE STUDIO).
 SMOKE DETETORS ARE REQ`D FOR BOTH FLOORS
 IN A COMMON AREA.
  
  
 4)NOTE: YOU SHOW ON YOUR LOAD CALCULAT-
 -ION EXISTING SQ.FT? PLEASE INCLUDE NEW
 SQ FOOTAGE YOU ARE ADDING IF NOT ALREADY
 220-3-C-1
  
 5)NOTE: PLEASE CHECK THE REQ`D OUTLET
 SPACING PER 210-522`6`12` RULE.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-03-23 Cont ID  
Sent By cthirben Date 2000-03-23 Time 09:12 Rev Time 0.00
Received By cthirben Date 2000-03-27 Time 10:11 Sent To  
Notes
2001-01-08 00:00:00 
 ***************PROVISO******************
  
  
 1. A/C UNIT TOOSMALL FOR THE CFM'S SHOWN
 ON PLANS.
  
  
 DOOR.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-20 Cont ID  
Sent By tlarge Date 2000-03-20 Time 07:08 Rev Time 0.33
Received By tlarge Date 2000-03-20 Time 07:08 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-16 Cont ID  
Sent By gjoyce Date 2000-03-16 Time 15:31 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved