Plan Review Details - Permit 00030713
Plan Review Stops For Permit 00030713
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-06-28 Cont ID  
Sent By lmartine Date 2000-06-28 Time 10:52 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-04 Cont ID  
Sent By lmartine Date 2000-04-04 Time 09:17 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-07-03 Cont ID  
Sent By jleahy Date 2000-07-03 Time 09:20 Rev Time 1.00
Received By jleahy Date 2000-07-03 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-06-27 Cont ID  
Sent By dpalmer Date 2000-06-27 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2000-06-27 Time 09:55 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 OF PANELS INCLUDING ALL CONTINUOUS
 LOADS AT 125% (LIGHTING ETC )
  
 THIS WAS ASKED FOR ON THE FIRST TWO
 REVIEWS. PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-27 Cont ID  
Sent By dpalmer Date 2000-04-27 Time 07:15 Rev Time 0.00
Received By dpalmer Date 2000-04-27 Time 07:15 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: AS ASKED FOR ON FIRST REVIEW
 OF PLANS,,,PLEASE SUBMIT COMPLETE LOAD
 CALCUALTIONS OF PANELS. PLEASE SHOW ALL
 CONTINUOUS LOADS AT 125%. SHOW THE LOAD
 CALC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. THIS MUST BE SUBMITTED BEFORE
 ANY ROUGH ELECTRICAL INSPECTIOB IS CALL-
 -ED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-31 Cont ID  
Sent By dpalmer Date 2000-03-31 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2000-03-31 Time 16:51 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PANEL SCHEDULES NOT COMPLETE.??
 NEED TO SHOW MDP.E-2 IS MISSING LC AND
 IS SHOWING MDP??
 2)NOTE: NEED TO SUBMIT COMPLETE POWER
 RISER DIAGRAM.YOU ARE MISSING LC
  
 3)NOTE: ALSO SUBMIT THE AIC RATINGS OF
 MDP/MAIN.110-9 /215-5
  
 4)NOTE: MISSING LOAD CALCULATIONS??
 NEED TO SUBMIT LOAD CALCS AND INCLUDING
 CONTIUOUS LOADS SUCH AS LIGHTING.215-5
  
  
 PLEASE SUBMIT THE ABOVE INFROMATION FOR
 REIVEW. IF THERE ARE ANY QUESTIONS PLEAS
 CALL.659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-21 Cont ID  
Sent By lmartine Date 2000-03-21 Time 09:24 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-31 Cont ID  
Sent By ndenmark Date 2000-03-31 Time 08:01 Rev Time 0.33
Received By ndenmark Date 2000-03-31 Time 08:01 Sent To  
Notes
2001-01-08 00:00:00********PROVISO************************
  
 PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 EXISTING DUCT AND MECHANICAL EQUIPMENT
 TO BE REUSED ARE TO BE INSPECTED FOR
 CLEANLINESS AND IF DEEMED NEEDED, CLEANE
 AND SANITIZED BY LICENSED MECHANICAL
 CONTRACTOR

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-07-02 Cont ID  
Sent By tlarge Date 2000-07-02 Time 07:48 Rev Time 0.33
Received By tlarge Date 2000-07-02 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-06-27 Cont ID  
Sent By tlarge Date 2000-06-27 Time 17:27 Rev Time 1.25
Received By tlarge Date 2000-06-27 Time 17:27 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW THE LENGTH AND WIDTH OF THE
 HANDICAP TOILET STALLS IN THE TOILET
 ROOMS.COMPLY W/FACBC SEC.4.17.3.
  
 LAYOUT OF TOILET ROOM #110 ON SHT.P-2
 DOESN'T MATCH SHEETS A-1,A-2.
  
 THE TOILET STALL IN ROOM #110 DOESN'T
 COMPLY W/FACBC.IF A STALL IS GOING TO BE
 UTILIZED IT MUST COMPLY W/FACBC SEC.
 4.17.3.
  
 AN ADDITIONAL H.C .STALL IS REQD.IN THE
 WOMEN'S RESTROOM PER FACBC SEC.4.22.4.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
 (SEE ROOM #101)
  
 RISER #6/P-2 DOESN'T MATCH 3/P-2.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 MAKE ALL CHANGESFROM ORIGINAL PLANS
 ON REVISED SET.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-05-15 Cont ID  
Sent By tlarge Date 2000-05-15 Time 07:11 Rev Time 0.30
Received By tlarge Date 2000-05-15 Time 07:11 Sent To  
Notes
2001-01-08 00:00:00PLANS SHALL BE SIGNED AND SEALED PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3
  
 SUBMIT WATER SUPPLY RISER FOR REVIEW.
 COMPLY W/SPC SEC.610.4.1,610.4.2.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-05-09 Cont ID  
Sent By tlarge Date 2000-05-09 Time 07:57 Rev Time 2.00
Received By tlarge Date 2000-05-09 Time 07:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-04-28 Cont ID  
Sent By tlarge Date 2000-04-28 Time 16:24 Rev Time 0.00
Received By tlarge Date 2000-04-28 Time 16:23 Sent To  
Notes
2001-01-08 00:00:00SUBMIT THE AVERAGE DAILY ATTENDANCE
 FOR THE EDUCTIONAL AREA PER TABLE 407 OF
 SPC.
  
 ALL PUBLIC AND COMMON USE TOILET ROOMS
 SHALL COMPLY W/FACBC SEC.4.22 PER FACBC
 SEC.4.1.3(11).SEE ROOMS #110,111.
  
 CLEARLY SHOW DIMENSIONS (LXW) OF H.C.
 STALLS.COMPLY W/FACBC SEC.4.17.3(NEW
 CONSTRUCTION.)
  
 SHT.A-2-SHOW CLEAR FLOOR SPACE UNDER
 DRINKING FOUNTAIN.(GENERAL REFERENCE OR
 NOTE TO CODE IS UNACCEPTABLE PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 FLOOR DRAINS SHALL BE EQUIPPED W/TRAP
 PRIMERS PER SPC SEC.409.4.1.1.
  
 SUBMIT SANITARY AND WATER RISER DIAGRAMS
 FOR SNACK SHOP AREA AND DETAIL TYPE OF
 ITEMS TO BE SOLD/DISTRIBUTED AT THIS
 AREA.APPROVAL FROM DEPT.OF BUSINESS MAY
 BE REQD.
  
 DESIGN OF THE SANITARY SYSTEM SHALL
 COMPLY W/SPC SEC.906.2.1.THE DRAWING
 (PLAN VIEW AND ISOMETRIC STILL SHOW THE
 VENTS OFFSETTING HORIZONTALLY BELOW THE
 SLAB.)
  
 SHT.P-2- WATER CLOSETS NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.CONNECT W.C.'S TO STACK.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-04-01 Cont ID  
Sent By tlarge Date 2000-04-01 Time 05:39 Rev Time 1.50
Received By tlarge Date 2000-04-01 Time 05:38 Sent To  
Notes
2001-01-08 00:00:00MINIMUM NUMBER OF TOILET FACILITIES
 SHALL COMPLY W/SPC SEC.407.1.3.AND TABLE
 407.
  
 SUBMIT U.L.ASSEMBLY NUMBERS FOR FIRE
 SAFING DETAILS SHOWN ON A-3.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.4.
  
 ALL PUBLIC AND COMMON AREA TOILET ROOMS
 SHALL COMPLY W/FACBC SECS.4.1.3(11),
 4.22.
  
 HANDICAP STALLS SHALL COMPLY W/FACBC
 SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION)4.1.6.(B).
  
 SHT.A-2-CLEAR FLOOR SPACE UNDER H.C.
 LAV.SHALL BE 29" PER FACBC SEC.4.19.2.
  
 SHT.A-2-CLEAR FLOOR SPACE UNDER DRINKING
 FOUNTAINS SHALL COMPLY W/FACBC SEC.
 4.15.5.
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
  
 PIPES UNDER LAVS.SHALL COVERED PER FACBC
 SEC.4.19.4.
  
 RM.111-STALL DOOR INFRINGES ON CLEAR
 FLOOR SPACE FOR URINAL.COMPLY W/FACBC
 4.18.3,4.22.2.
  
 WALLS IN TOILET ROOMS SHALL BE
 NONABSORBENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 TOILET ROOMS SHALL BE EQUIPPED W/FLOOR
 DRAINS PER SPC SEC.409.4.1.1.
  
 HEIGHT OF COUNTER IN EMPLOYEE LOUNGE
 SHALL COMPLY W/FACBC SEC.4.2.5,4.2.6.&
 FIGS.#5 & 6.
  
 VENTS FOR WATER CLOSETS IN ROOMS #115 &
 116 SHALL COMPLY W/FACBC SEC.905.2.1.
 (BASE MUST BE WASHED BY A FIXTURE)
  
 SIZE ALL SECTIONS OF THE SANITARY RISERS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 DOMESTIC WATER RISER SHOWS 1-1/4" LINE
 SUPPLYING A 2" LINE.CLARIFY.