| Plan Review Stops For Permit 00030713 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-06-28 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-06-28 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-04-04 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-07-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-07-03 |
Time |
09:20 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2000-07-03 |
Time |
09:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-06-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-27 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-27 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | OF PANELS INCLUDING ALL CONTINUOUS | | | LOADS AT 125% (LIGHTING ETC ) | | | | | | THIS WAS ASKED FOR ON THE FIRST TWO | | | REVIEWS. PLEASE SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 EXT | | | 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-04-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-04-27 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-04-27 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | | | | 1)NOTE: AS ASKED FOR ON FIRST REVIEW | | | OF PLANS,,,PLEASE SUBMIT COMPLETE LOAD | | | CALCUALTIONS OF PANELS. PLEASE SHOW ALL | | | CONTINUOUS LOADS AT 125%. SHOW THE LOAD | | | CALC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. THIS MUST BE SUBMITTED BEFORE | | | ANY ROUGH ELECTRICAL INSPECTIOB IS CALL- | | | -ED IN. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-31 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-31 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PANEL SCHEDULES NOT COMPLETE.?? | | | NEED TO SHOW MDP.E-2 IS MISSING LC AND | | | IS SHOWING MDP?? | | | 2)NOTE: NEED TO SUBMIT COMPLETE POWER | | | RISER DIAGRAM.YOU ARE MISSING LC | | | | | | 3)NOTE: ALSO SUBMIT THE AIC RATINGS OF | | | MDP/MAIN.110-9 /215-5 | | | | | | 4)NOTE: MISSING LOAD CALCULATIONS?? | | | NEED TO SUBMIT LOAD CALCS AND INCLUDING | | | CONTIUOUS LOADS SUCH AS LIGHTING.215-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFROMATION FOR | | | REIVEW. IF THERE ARE ANY QUESTIONS PLEAS | | | CALL.659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-03-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-03-21 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-31 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-03-31 |
Time |
08:01 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-03-31 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ********PROVISO************************ | | | | | | PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | EXISTING DUCT AND MECHANICAL EQUIPMENT | | | TO BE REUSED ARE TO BE INSPECTED FOR | | | CLEANLINESS AND IF DEEMED NEEDED, CLEANE | | | AND SANITIZED BY LICENSED MECHANICAL | | | CONTRACTOR |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2000-07-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-02 |
Time |
07:48 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-07-02 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-06-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-27 |
Time |
17:27 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-06-27 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CLEARLY SHOW THE LENGTH AND WIDTH OF THE | | | HANDICAP TOILET STALLS IN THE TOILET | | | ROOMS.COMPLY W/FACBC SEC.4.17.3. | | | | | | LAYOUT OF TOILET ROOM #110 ON SHT.P-2 | | | DOESN'T MATCH SHEETS A-1,A-2. | | | | | | THE TOILET STALL IN ROOM #110 DOESN'T | | | COMPLY W/FACBC.IF A STALL IS GOING TO BE | | | UTILIZED IT MUST COMPLY W/FACBC SEC. | | | 4.17.3. | | | | | | AN ADDITIONAL H.C .STALL IS REQD.IN THE | | | WOMEN'S RESTROOM PER FACBC SEC.4.22.4. | | | | | | FIXTURES DOWNSTREAM OF WATER CLOSETS | | | SHALL BE VENTED PER SPC SEC.913.2. | | | (SEE ROOM #101) | | | | | | RISER #6/P-2 DOESN'T MATCH 3/P-2. | | | | | | WATER CLOSETS NOT PERMITTED ON WET VENTS | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 911.1.1. | | | | | | MAKE ALL CHANGESFROM ORIGINAL PLANS | | | ON REVISED SET.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-05-15 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-15 |
Time |
07:11 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-05-15 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLANS SHALL BE SIGNED AND SEALED PER | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3 | | | | | | SUBMIT WATER SUPPLY RISER FOR REVIEW. | | | COMPLY W/SPC SEC.610.4.1,610.4.2. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-05-09 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-09 |
Time |
07:57 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-05-09 |
Time |
07:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-04-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-28 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-04-28 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT THE AVERAGE DAILY ATTENDANCE | | | FOR THE EDUCTIONAL AREA PER TABLE 407 OF | | | SPC. | | | | | | ALL PUBLIC AND COMMON USE TOILET ROOMS | | | SHALL COMPLY W/FACBC SEC.4.22 PER FACBC | | | SEC.4.1.3(11).SEE ROOMS #110,111. | | | | | | CLEARLY SHOW DIMENSIONS (LXW) OF H.C. | | | STALLS.COMPLY W/FACBC SEC.4.17.3(NEW | | | CONSTRUCTION.) | | | | | | SHT.A-2-SHOW CLEAR FLOOR SPACE UNDER | | | DRINKING FOUNTAIN.(GENERAL REFERENCE OR | | | NOTE TO CODE IS UNACCEPTABLE PER COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | FLOOR DRAINS SHALL BE EQUIPPED W/TRAP | | | PRIMERS PER SPC SEC.409.4.1.1. | | | | | | SUBMIT SANITARY AND WATER RISER DIAGRAMS | | | FOR SNACK SHOP AREA AND DETAIL TYPE OF | | | ITEMS TO BE SOLD/DISTRIBUTED AT THIS | | | AREA.APPROVAL FROM DEPT.OF BUSINESS MAY | | | BE REQD. | | | | | | DESIGN OF THE SANITARY SYSTEM SHALL | | | COMPLY W/SPC SEC.906.2.1.THE DRAWING | | | (PLAN VIEW AND ISOMETRIC STILL SHOW THE | | | VENTS OFFSETTING HORIZONTALLY BELOW THE | | | SLAB.) | | | | | | SHT.P-2- WATER CLOSETS NOT PERMITTED ON | | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.911.1.1.CONNECT W.C.'S TO STACK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-04-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-01 |
Time |
05:39 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-04-01 |
Time |
05:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | MINIMUM NUMBER OF TOILET FACILITIES | | | SHALL COMPLY W/SPC SEC.407.1.3.AND TABLE | | | 407. | | | | | | SUBMIT U.L.ASSEMBLY NUMBERS FOR FIRE | | | SAFING DETAILS SHOWN ON A-3.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.4. | | | | | | ALL PUBLIC AND COMMON AREA TOILET ROOMS | | | SHALL COMPLY W/FACBC SECS.4.1.3(11), | | | 4.22. | | | | | | HANDICAP STALLS SHALL COMPLY W/FACBC | | | SEC.4.17.3(SEE EXCEPTION:NEW | | | CONSTRUCTION)4.1.6.(B). | | | | | | SHT.A-2-CLEAR FLOOR SPACE UNDER H.C. | | | LAV.SHALL BE 29" PER FACBC SEC.4.19.2. | | | | | | SHT.A-2-CLEAR FLOOR SPACE UNDER DRINKING | | | FOUNTAINS SHALL COMPLY W/FACBC SEC. | | | 4.15.5. | | | | | | DRINKING FOUNTAINS SHALL COMPLY W/FACBC | | | SEC.4.1.3(10)(A). | | | | | | PIPES UNDER LAVS.SHALL COVERED PER FACBC | | | SEC.4.19.4. | | | | | | RM.111-STALL DOOR INFRINGES ON CLEAR | | | FLOOR SPACE FOR URINAL.COMPLY W/FACBC | | | 4.18.3,4.22.2. | | | | | | WALLS IN TOILET ROOMS SHALL BE | | | NONABSORBENT TO A HEIGHT OF 4' PER SBC | | | SEC.1204.2. | | | | | | TOILET ROOMS SHALL BE EQUIPPED W/FLOOR | | | DRAINS PER SPC SEC.409.4.1.1. | | | | | | HEIGHT OF COUNTER IN EMPLOYEE LOUNGE | | | SHALL COMPLY W/FACBC SEC.4.2.5,4.2.6.& | | | FIGS.#5 & 6. | | | | | | VENTS FOR WATER CLOSETS IN ROOMS #115 & | | | 116 SHALL COMPLY W/FACBC SEC.905.2.1. | | | (BASE MUST BE WASHED BY A FIXTURE) | | | | | | SIZE ALL SECTIONS OF THE SANITARY RISERS | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | DOMESTIC WATER RISER SHOWS 1-1/4" LINE | | | SUPPLYING A 2" LINE.CLARIFY. |
|
|