Plan Review Details - Permit 00030283
Plan Review Stops For Permit 00030283
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-06 Cont ID  
Sent By dpalmer Date 2000-10-06 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2000-10-06 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By dpalmer Date 2000-04-05 Time 22:32 Rev Time 0.00
Received By dpalmer Date 2000-04-05 Time 22:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-15 Cont ID  
Sent By cthirben Date 2000-03-15 Time 12:20 Rev Time 1.00
Received By cthirben Date 2000-03-15 Time 12:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-11 Cont ID  
Sent By tlarge Date 2000-03-11 Time 11:25 Rev Time 0.33
Received By tlarge Date 2000-03-11 Time 11:25 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-07-19 Cont ID  
Sent By jgomez Date 2000-07-19 Time 17:26 Rev Time 0.25
Received By jgomez Date 2000-07-19 Time 17:26 Sent To  
Notes
2001-01-08 00:00:00TRUSS DRAWINGS SUBMITTAL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-06-27 Cont ID  
Sent By jgomez Date 2000-06-27 Time 13:09 Rev Time 0.50
Received By jgomez Date 2000-06-27 Time 13:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-03 Cont ID  
Sent By jgomez Date 2000-05-03 Time 19:22 Rev Time 2.00
Received By jgomez Date 2000-05-03 Time 19:22 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO" NEED TO PROVIDE
 ELEVATION CERTIFICATE.
 2-REVISE SIZE OF EGRESS WINDOW IN BEDRM
 #2. IT DOESN'T COMPLY WITH SECTION
 1005.4.4 SBC 1997.
 3-REVISE SIZE OF ATTIC ACCESS PANEL.
 MINIMUM SIZE TO BE 22"X36" AS PER
 SECTION 2309.6 SBC 1997.
 4-STORM PANELS:
 -CLARIFY WHY THE INSTALLATION SCHEDULE
 SPECIFIES ANCHOR SPACING 12" AT ALL
 PANELS, BUT ANCHOR SCHEDULE ON SHEET
 6 OF 15 OF APPROVED DRAWINGS IS
 HIGHLIGHTED DIFFERENTLY.
 5-CLEARLY INDICATE ON ORIGINAL DRAWINGS
 THE WINDOWS TO HAVE SAFETY GLASS AS
 PER SECTION 2405.2 SBC 1997.
 6-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY.
 7-UPDATE/REVISE ORIGINAL DRAWINGS. SEE
 COMMENTS ON DRAWINGS, INCLUDING THE
 COVER SHEET.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-09 Cont ID  
Sent By gjoyce Date 2000-03-09 Time 11:31 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***