Plan Review Details - Permit 00030224
Plan Review Stops For Permit 00030224
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-19 Cont ID  
Sent By dpalmer Date 2000-04-19 Time 18:10 Rev Time 0.00
Received By dpalmer Date 2000-04-19 Time 18:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 21:33 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 21:33 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF THE
 EQUIPMENT MAINS. MAIN MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT, 110-9
  
 2)NOTE: NEED TO INCLUDE THE BLDG. STEEL
 AS PART OF THE GROUNDINGELECTRODE
 SYSTEM AS PER 250-50
  
 3)NOTE: NEED TO HAVE THE REQ`D DEDICATED
 BATH(S) CIRCUT(S) AS PER 210-11-C-3
 NEED TO BE #12 AND 20AMP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-09 Cont ID  
Sent By cthirben Date 2000-03-09 Time 12:55 Rev Time 1.00
Received By cthirben Date 2000-03-09 Time 12:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 15:55 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 15:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-08 Cont ID  
Sent By tlarge Date 2000-03-08 Time 18:28 Rev Time 0.50
Received By tlarge Date 2000-03-08 Time 18:27 Sent To  
Notes
2001-01-08 00:00:00KITCHEN SINK NOT PROPERLY VENTED.SPC SEC
 901.2.
  
 SHOWER/TUBS ON 2ND.FLR.NOT PROPERLY
 VENTED.SPC 901.2.
  
 WATER CLOSET IN MASTER BATH EXCEEDS
 DISTANCE FROM VENT PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.908.1,FOOTNOTE#2.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-04-20 Cont ID  
Sent By fknapp Date 2000-04-20 Time 10:28 Rev Time 4.00
Received By fknapp Date 2000-04-20 Time 10:25 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 FRONT ENTRY DOOR ASSEMBLY
 CIRCLE WINDOWS
 MULLIONS
  
 2)PROVIDE SPECIFICATIONS FOR 1HR RATED
 GLASS BLOCK.
  
 3)PROVIDE ROOF SHEATHING NAILING ZONES
 COMPLYING WITH CITY AMENDMENTS 2306.1
 ZONE 3 EDGES 4"OC
  
 4)PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLY.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-06 Cont ID  
Sent By gjoyce Date 2000-03-06 Time 15:34 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***