| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-PROVIDE PROFESSIONAL SURVEY SHOWING |
| | BUILDING LAYOUT. SIGNED, SEALED AND |
| | DATED. |
| | 2-PROVIDE COMPLETE INSTALLATION DETAIL |
| | OF WINDOWS AT BREAKFAST AREA THAT ARE |
| | ATTACHED TO STEEL COLUMN. |
| | 3-FOOTING F2: |
| | -PROVIDE DETAIL SHOWING THE WIDTH AND |
| | DEPTH DIMENSIONS. |
| | NOTE: 16" MIN. DEPTH AS PER SECTION |
| | 1804.1.3 SBC 1997 AND MINIMUM WIDTH OF |
| | 16" AS PER SOIL TEST REPORT. |
| | 4-REVISE DESIGN CERTIFICATION FOR BLDG |
| | CODE COMPLIANCE FORM: |
| | -MEAN ROOF HEIGHT IS 18'-6" PLUS OR |
| | MINUS. MEAN ROOF HEIGHT IS TAKEN FROM |
| | GRADE, NOT FROM FINISH FLOOR, TO THE |
| | AVERAGE POINT OF HIGHEST ROOF. |
| | -CLARIFY WHY IS THERE ANOTHER ENGINEER |
| | SEALING THIS FORM BUT HE IS NOT |
| | SEALING THE STRUCTURAL PLANS. |
| | 5-SEE COMMENTS ON PLANS AND REVISE AND |
| | UPDATE ALL PLANS AS REQUIRED. |
| | NOTE: ARCHITECT NEEDS TO DATE ALL |
| | DRAWINGS AT TIME OF STAMPING HIS SEAL. |
| | 6-PROVIDE PRODUCT APPROVAL FOR OVAL AND |
| | ARCHED WINDOWS, SLIDING GLASS DOORS |
| | WITH TRANSOM ABOVE COMPLETE ASSEMBLY. |
| | NOTE: PRODUCT APPROVAL FOR RECTANGULAR |
| | WINDOWS DOESN'T INCLUDE ROUND, OVAL OR |
| | ARCHED WINDOWS. |
| | 7-PROVIDE THE DESIGN PRESSURES AT ALL |
| | EXTERIOR OPENINGS. SEC. 1606 SBC 1997. |
| | 8-SPECIFY CEILING CONSTRUCTION AT FRONT |
| | AND REAR PORCHES. SPECIFY FASTENERS |
| | AND SPACING.SEC. 2504.2 SBC 1997. |
| | 9-TRUSS ANCHOR SCHEDULE IS NOT LEGIBLE. |
| | 10-ROOF TRUSSES: |
| | -REVISE MEAN ROOF HEIGHT.18'-6". |
| | -THERE ARE SOME ROOF TRUSSES DESIGNED |
| | AT 16'-0" AND SOME AT 23'-0". THERE |
| | IS ONLY ONE MEAN ROOF HEIGHT FOR |
| | ENTIRE BUILDING. TABLE 1606.2A SBC/97. |
| | 11-STORM PANELS: |
| | -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS |
| | AND ANCHOR SPACING TO BE USED. |