| Plan Review Stops For Permit 00030135 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-03 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-03-03 |
Time |
07:43 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-03-03 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) REFRIGERANT LEAK DETECTION AND VENTI- | | | LATION FANS ARE LIFE SAFETY COMPONENTS | | | OF THE BUILDING SYSTEM AND REQUIRE | | | CONNECTION TO THE EMERGENCY POWER SYSTEM | | | 2) INTERIOR NOTIFICATION OF REFIGERANT | | | LEAK TO BE BY HORN AND STROBE AND TO BE | | | INITIATED AT TIME OF EXTERIOR NOTIFICA- | | | TION |
|
|
|