Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By ndenmark Date 2000-03-03 Time 07:43 Rev Time 1.00
Received By ndenmark Date 2000-03-03 Time 07:43 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) REFRIGERANT LEAK DETECTION AND VENTI-
 LATION FANS ARE LIFE SAFETY COMPONENTS
 OF THE BUILDING SYSTEM AND REQUIRE
 CONNECTION TO THE EMERGENCY POWER SYSTEM
 2) INTERIOR NOTIFICATION OF REFIGERANT
 LEAK TO BE BY HORN AND STROBE AND TO BE
 INITIATED AT TIME OF EXTERIOR NOTIFICA-
 TION