Plan Review Details - Permit 00030112
Plan Review Stops For Permit 00030112
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2001-03-05 Cont ID  
Sent By jwitmer Date 2001-03-05 Time 10:51 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-05 00:00:00PRODUCT APPROVAL DOORS & WINDOWS JW
 PRODUCT APPROVAL DOORS & WINDOWSJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-03-05 Cont ID  
Sent By lmartine Date 2001-03-05 Time 09:19 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-05 00:00:00TRUSS ENGINEERING
 APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-12-20 Cont ID  
Sent By jwitmer Date 2000-12-20 Time 07:50 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING REVIEW 12/20/2000
  
 1). ARCHITECTURAL: ITEM# 10. SEE FLORIDA
 ACCESSIBILITY CODE ITEMS 5.1- 5.6.5.2
 COUNTER TOPS WHERE FOOD OR DRINK IS
 SERVED AT COUNTERS EXCEEDING 34" IN
 HEIGTH. 5.5 FOOD SERVICE LINES & 5.6
 TABLEWARE AND CONDIMENT AREAS.
  
 2). STRUCTURAL DRAWAINGS ITEM # 13.
 DRAWINGS ARE REQUIRED TO DETERMINE
 REVISIONS.
 BUILDING PLAN REVIEW:
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-12-07 Cont ID  
Sent By rmcdouga Date 2000-12-07 Time 11:22 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION FOR WHEEL CHAIR LIFT DENIED PER
 LOUIS MARTINEZ.
 1)APPROVED PLANS DO NOT SHOW ADEQUATE
 CLEARANCE FOR LIFT AND MAST.REVISE
 DRAWINGS TO ACCOMMODATE LIFT AND MAST.
  
 2)HAVE ENGINEER CERTIFY THAT EXISTING
 WALL WILL SUPPORT MAST AND WALL.
  
 3)PROVIDE ELECTRICAL INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-05 Cont ID  
Sent By lmartine Date 2000-09-05 Time 16:39 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 REVISE MARRIOTT HOTEL FROM METAL FRAME
 TO MASONRY
  
  
 PROVISO
 ---------
  
 1]SUPPLY 3 COPYS OF ENERGY EFF. CALCS.
 2]SUMBIT NEW THRESHOLD PLAN.
 3]SUBMIT SHORING PLAN.
 4]PROVIDE TEST REPORTS FOR EXTERIOR
 WINDOWS AND DOORS,ROOF COVER.EXTERIOR
 GLAZING SHALL COMPLY WITH IMPACT
 PROTECTION.
 5]SUBMIT ONE MORE SET OF DRAWINGS SIGNED
 AND SEALED.
  
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 659-8096#8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-09 Cont ID  
Sent By hpiskura Date 2000-04-07 Time 12:39 Rev Time 0.00
Received By lmartine Date 1900-04-07 Time 17:40 Sent To  
Notes
2001-01-08 00:00:00BUILDING PERMIT ONLY PER HHP

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2001-05-23 Cont ID  
Sent By dpalmer Date 2001-05-23 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2001-05-23 Time 16:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 10 Status N Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 22:51 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 22:47 Sent To  
Notes
2001-04-17 00:00:00ALREADY REVIEW ON 3/31

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2001-04-04 Cont ID  
Sent By dpalmer Date 2001-04-04 Time 19:39 Rev Time 0.00
Received By dpalmer Date 2001-04-04 Time 19:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2001-03-13 Cont ID  
Sent By dpalmer Date 2001-03-13 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2001-03-13 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 20:58 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT PLANS SHOWING
 OTHER CHANGES MENTIONED IN BULLETIN #2
  
 2)NOTE: PLEASE NOTE THAT THE SHEETS B2-7
 AND B2-8 ARE TO BE SIGNED AND SEALED BY
 ARCH/ENGINEER OF RECORD. PLEASE SEE THE
 F.A.CCHAPTERS 481 AND 471 FOR THE REQ`
 MENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096ETX 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-08-25 Cont ID  
Sent By dpalmer Date 2000-08-25 Time 09:53 Rev Time 0.00
Received By dpalmer Date 2000-08-25 Time 09:52 Sent To  
Notes
2001-01-08 00:00:00REV OK FOR THE FOLLOWING PAGES
 E----1.1,1.2,1.3,1.4,1.5,2.1,2.3,2.2,
 2.4,2.5,3.1,4.1,4.2,4.3,4.4,5.1,5.2,
  
 AIC RATINGS SHOWN AND ADDITIONAL LOADS
 SHOWN FOR PANELPE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-07-10 Cont ID  
Sent By jleahy Date   Time 13:02 Rev Time 1.30
Received By jleahy Date 2000-07-10 Time 13:00 Sent To  
Notes
2001-01-08 00:00:00REV #5 PAGES E1.2,.3,.4, 2.2, 4.1,4.2,
 4.4

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-06-28 Cont ID  
Sent By jleahy Date 2000-06-28 Time 13:05 Rev Time 0.00
Received By jleahy Date 2000-07-10 Time 12:28 Sent To  
Notes
2001-01-08 00:00:00ELECTRIC OKREV.#4

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-06-09 Cont ID  
Sent By dpalmer Date 2000-06-09 Time 14:10 Rev Time 0.00
Received By dpalmer Date 2000-06-09 Time 14:10 Sent To  
Notes
2001-01-08 00:00:00ELECTRICAL PLANS AND PERMIT TO BE RESUB-
 SEP.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-22 Cont ID  
Sent By jleahy Date 2000-03-22 Time 14:30 Rev Time 4.00
Received By jleahy Date 2000-03-22 Time 14:24 Sent To  
Notes
2001-01-08 00:00:001-PAGES E1.2,E1.3,E1.4 ALL SHOW PANELS
 MOUNTED IN THE LINEN STORAGE ROOM SEE
 SECTIONS 240-24D, AND 384-7 WHY THEY
 CAN NOT BE LOCATED THERE!
  
 2-PAGE E4.2 SHOWS A PANEL LABLED "PE"
 HOW IS THIS FED AND IT SHOWS NO LOADS
 OTHER THAN LIGHTING.ALSO THIS IS IN
 A SEPARATE STRUCTURE PLEASE TREAT AS
 PER CODE.
  
 3-NO LOAD FOR "PE" SHOWN IN LOAD
 CALCULATION PLEASE CHECK
  
 4-FAULT CURRENT RATING NEEDED FOR ALL
 SERVICE AND DISTRIBUTION EQUIPMENT!!!
 110-9,10

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-08-22 Cont ID  
Sent By mgonzale Date 2000-08-22 Time 15:19 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 ALL PREVIOUS COMMENTS HAVE BEEN REVISED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-06-09 Cont ID  
Sent By lsmith Date 2000-06-09 Time 13:12 Rev Time 0.10
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ATTACHED PER UTILITIES4/3/2000
 BY MG

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-05-24 Cont ID  
Sent By mcarsill Date 2001-05-24 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2001-05-24 Time 16:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-03-07 Cont ID  
Sent By mcarsill Date 2001-03-07 Time 08:01 Rev Time 0.00
Received By mcarsill Date 2001-03-07 Time 08:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-08-14 Cont ID  
Sent By rturnque Date 2000-08-14 Time 15:56 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001. PROVIDE TAMPER SWITCHES ON DOUBLE
 DETECTOR CHECK VALVES.
 2.FIRE ALARM SYSTEM SHALL BE CLASS "A"
 OR ADDRESSABLE.
 3.FIRE ALARM SYSTEM SHALL BE 15 DECIBELS
 ABOVE AMBIENT NOISE THROUGHOUT.
 4. PROVIDE FIRE ALARM STROBE LIGHTS IN
 ALL PUBLIC RESTROOMS.
 5. PROVIDE APPROVED DOOR CLOSERS ON ALL
 RATED FIRE DOORS.
 6. PROVIDE APPROVED WIRED-IN SMOKE
 DETECTORS IN ALL GUESTROOMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-05-31 Cont ID  
Sent By rturnque Date 2000-05-31 Time 16:24 Rev Time 0.35
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ndenmark Date 2000-05-23 Time 09:44 Sent To  
Notes
2001-01-08 00:00:00FIRE SPRINKLER PROTECTION FOR ATTIC
 TO COMPLY WITH NFPA 13. PLANS SHOWED
 ONLY HEAD LOCATIONS IN THE ATTIC.
 FIRE SPRINKLER PIPING, AND HANGERS
 NOT SHOWN.
 PLAN REVIEWED BY LT. CARSILLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-03-17 Cont ID  
Sent By rturnque Date 2000-03-17 Time 09:30 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE ALARM SYSTEM SHALL BE CLASS "A" OR
 ADDRESSABLE
  
 PROVIDE FIRE SPRINKLER DRAWINGS
  
 PROVIDE STANDPIPE
  
 FIRE HYDRANT SHALL BE LOCATED WITHIN
 150 FEET OF FIRE DEPARTMENT CONNECTION
  
 PROVIDE SHOP DRAWINGS FOR KITCHEN HOOD
 AND EXTINGUISHING SYSTEM

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-03-23 Cont ID  
Sent By pkrauss Date 2001-03-23 Time 11:26 Rev Time 0.35
Received By pkrauss Date 2001-03-23 Time 11:26 Sent To  
Notes
2001-03-23 00:00:00REVISION - REVISED CAPACITIES FOR FCU-6
 ON FCU SCHEDULE. DELETED EF-14 FROM THE
 FAN SCHEDULE.(M1.1)DELETE EF-14.
 REVISED DUCTWORK AT "GRAB-N-GO" 116.
 REVIED PLAN NOTE #36 AND ADD PLAN NOTE
 #44.(M2.1)

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-08-14 Cont ID  
Sent By ndenmark Date 2000-08-14 Time 14:00 Rev Time 0.50
Received By ndenmark Date 2000-08-14 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-07-24 Cont ID  
Sent By ndenmark Date 2000-07-24 Time 14:28 Rev Time 2.00
Received By ndenmark Date 2000-07-24 Time 14:28 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED BY REVISIONS DATED 6/15/00
 PRIOR COMMENTS CORRECTED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-06-02 Cont ID  
Sent By ndenmark Date 2000-06-02 Time 14:31 Rev Time 1.00
Received By ndenmark Date 2000-06-02 Time 12:20 Sent To  
Notes
2001-01-08 00:00:00 
 DENIED FOR MECHANICAL
  
 BASED ON PLAN REVIEW 00030112 THE FOLLOW
 ING ITEMS NEED TO BE REVISED ON THE MECH
 DRAWINGS:
 1) PROVIDE INFORMATION ON BATH EXHAUST
 DUCT MATERIAL FOR CODE COMPLIANCE
 2) OUTSIDE AIR CALCULATIONS LOCATED ON
 SKM-9 NEED TO BE PERMANTLY ATTACHED TO
 APPROVED DRAWINGS
 3) AIR BALANCE SCHEDULE LOCATED ON SKM-
 10 NEEDS TO BE PERMANENTLY ATTACHED TO
 APPROVED DRAWINGS
 4) ALL FIRE DAMPER LOCATIONS TO BE SHOWN
 AND PROPERLY IDENTIFIED ON PLANS PER
 1997 SMC 610.6
 5) FIRE DAMPERS REQUIRED AT ALL WALL
 PENETRATIONS OF 1 HOUR OR MORE PER 1997
 SMC 610.1.2 SEE PRIOR LIST FOR SPECIFIC
  
 THE FOLLOWING ARE PROVISO ITEMS:
 1) KITCHEN HOOD AND EXHAUST DUCT WILL
 REQUIRE SEPARATE MECHANICAL PERMIT
 2) SEPARATE PERMITS REQUIRED FOR HOOD,
 SUPPRESSION, WALK IN COOLER/FREEZER,ETC.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By ndenmark Date 2000-03-20 Time 15:27 Rev Time 0.00
Received By ndenmark Date 2000-05-22 Time 11:17 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 1)PROVIDE INFORMATION ON EXHAUST DUCT
 RISER MATERIAL
 2)KITCHEN HOOD AND EXHAUST DUCT WILL RE-
 QUIRE SEPARATE PERMIT AND MORE DETAILED
 PLANS
 3)PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 4)PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2
 5)1997 SMC 304.8.6.1 REQUIRES SECONDARY
 DRAIN LINE TO BE RUN SEPARATELY FROM
 PRIMARY CONDENSATE DRAIN LINE
 6)PROVIDE DETAIL FOR PROTECTION OF DRYER
 VENT IN RATED WALL
 7)1997 SMC 610.6 REQUIRES SPECIFIC LOCA-
 TION AND INSTALLATION DETAILS FOR EACH
 FIRE DAMPER, FIRE DOOR, ETC. TO BE SHOWN
 AND PROPERLY IDENTIFIED ON THE BUILDING
 PLANS BY THE DESIGNER. THE FOLLOWING
 LOCATIONS DO NOT INDICATE FIRE DAMPERS
 M2.1 2-18X12 THRU RATED WALLS 2 PLACES
 2-14X12 THRU RATED MEETING ROOM
 WALLS
 2-12X8 THRU MEN'S AND WOMEN'S ROOM
 RATED WALLS
 NO FIRE DAMPERS AT COMBUSTION AIR
 OPENING
 2-18X10 IN RATED MAINTANANCE ROOM
 WALL
 PROVIDE DETAIL FOR FIRE PROTECTION OF
 OPENING @ 14" FLUE PIPE PENETRATING
 RATED WALL BY WATER HEATER ROOM
 M2-2 FIVE DUCTS LEAVING MECH ROOM 217
 ON 2ND FLOOR PLAN NO FIRE DAMPERS SHOWN
 M2-3 10X8 R/A DUCT @ STORAGE ROOM 318A
 RATED WALL
 10X8 R/A DUCT @ RM 320 RATED WALL
 M2-4 12X8 R/A DUCT @ RM 418 AND RM 420
  
 SEPARATE PERMITS AND PLANS WILL BE
 REQUIRED FOR WALK IN COOLERS/FREEZERS,
 KITCHEN HOOD, FIRE SUPPRESSION SYSTEM

Review Stop P PLUMBING
Rev No 17 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 16 Status N Date 2001-06-08 Cont ID  
Sent By kstevens Date 2001-06-08 Time 15:57 Rev Time 0.25
Received By kstevens Date 2001-06-08 Time 15:57 Sent To  
Notes
2001-06-08 00:00:00REVIEW NOTES:
  
 NO PLUMBING TO REVIEW ON THIS REVIEW
 REFERED TO ENGINEERING.
  
 KSTEVENS

Review Stop P PLUMBING
Rev No 15 Status P Date 2001-06-02 Cont ID  
Sent By jleech Date 2001-06-02 Time 08:32 Rev Time 2.00
Received By jleech Date 2001-06-02 Time 08:32 Sent To  
Notes
2001-06-02 00:00:00PROVISO;
  
 1.SHT. P-4.3 AND P-4.4; SANITARY RISER
 DIAGRAMS ARE NOT SIZED PROPERLY.
  
 REVIEW BY JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 14 Status P Date 2001-05-07 Cont ID  
Sent By jleech Date 2001-05-07 Time 16:31 Rev Time 2.00
Received By jleech Date 2001-05-07 Time 16:30 Sent To  
Notes
2001-05-07 00:00:00REVISIONS; PAGE; P-1.1, P-2.1, P-2.2
 P-2.6, P-4.4, & P-4.5 OK
 P-4.2 & P-4.3 UNSAT.
 PIPE SIZES NOT CORRECT ON RISER DIAGRAMS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 13 Status P Date 2001-04-28 Cont ID  
Sent By jleech Date 2001-04-28 Time 13:09 Rev Time 1.00
Received By jleech Date 2001-04-28 Time 13:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 12 Status F Date 2001-03-29 Cont ID  
Sent By jleech Date 2001-03-29 Time 16:41 Rev Time 2.00
Received By jleech Date 2001-03-15 Time 17:27 Sent To  
Notes
2001-03-29 00:00:00DENIED;
  
 1.NEED APPROVAL FROM HEALTH DEPARTMENT
 BEFORE BATHROOM BY POOL CAN BE DELETED
 POOL PLANS HAVE BEEN APPROVED BY THE
 HEALTH DEPARTMENT WITH THE BATHROOM
 ON THE PLAN.
  
 2.WHAT IS THE BTU RATING OF THE FIRE-
 PLACE? NOT ADDED TO TOTAL BTU'S.
  
 3.PAGE P-4.2 SANITARY STACKS SHALL
 COMPLY WITH 94 SPC 714.2.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 11 Status P Date 2000-12-10 Cont ID  
Sent By pschmitz Date 2000-12-10 Time 12:35 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION: COMPLY W/SPC 94 SEC 601.1
 PROVIDE A ANTI SYPHON DEVICE FOR SOAP
 DISPENSING SYSTEM,WATTS 36-N.

Review Stop P PLUMBING
Rev No 10 Status F Date 2000-11-01 Cont ID  
Sent By tlarge Date 2000-11-01 Time 18:06 Rev Time 0.65
Received By tlarge Date 2000-11-01 Time 18:06 Sent To  
Notes
2001-01-08 00:00:001)PLUMBING SYSTEM DESIGN APPEARS TO
 BE BASED UPON THE 1997 PLUMBING CODE.
 THE CODE IN EFFECT IS THE 1994 STANDARD
 PLUMBING CODE.COUNTYWIDE AMENDMENTS TO
 SPC SEC.101.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 9 Status P Date 2000-09-05 Cont ID  
Sent By tlarge Date 2000-09-05 Time 10:12 Rev Time 3.50
Received By tlarge Date 2000-09-05 Time 06:57 Sent To  
Notes
2001-01-08 00:00:00H**************PROVISO******************
 1)SHEET P-4.3 REFERS TO SHT.P-4.2 FOR
 POOL HOUSE PLUMBING RISER.PLUMBING RISER
 FOR POOL HOUSE IS NOT ON THIS SHEET.
 SUBMIT SIGNED AND SEALED SANITARY AND
 WATER RISERS FOR REVIEW.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 2)A WATER USE PERMIT FOR THE IRRIGATION
 SYSTEM IS REQD.FROM SFWMD PER F.S.
 373.219.THE PERMIT SHALL BE OBTAINED
 PRIOR TO THE ISSUANCE OF THE IRRIGATION
 PERMIT.
  
 3)A WELL DRILLING PERMIT MAY ALSO BE
 REQD.FROM SFWMD AND THE PALM BEACH
 COUNTY HEALTH DEPT.VERIFICATION SHALL
 BE SUBMITTED FOR REVIEW.
  
 4)DETAIL/MANUF.SHEETS FOR LINT INTER-
 CEPTOR SHALL BE SUBMITTED FOR REVIEW
 PRIOR TO INSTALLATION.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 5)ADDITIONAL PLUMBING FIXTURES MAY BE
 REQD.IN THE POOL TOILET ROOM PENDING
 REVIEW BY THEPALM BEACH COUNTY HEALTH
 DEPT.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 8 Status P Date 2000-08-16 Cont ID  
Sent By tlarge Date 2000-08-16 Time 13:10 Rev Time 3.00
Received By tlarge Date 2000-08-16 Time 13:10 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 THE PLUMBING PLANS ARE REVIEWED FOR THE
 INSTALLATION OF THE UNDERGROUND DRAIN-
 AGE SYSTEM ONLY (INCLUDES SANITARY AND
 STORM).UPON SUBMITTAL AND REVIEWOF
 THE REVISED DRAWINGS THE PLUMBING WILL
 BE RELEASED FOR THE COMPLETE SYSTEMS.NO
 ABOVE SLAB WORK SHALL BE INSTALLED UNDER
 THIS PROVISO.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 7 Status F Date 2000-08-13 Cont ID  
Sent By tlarge Date 2000-08-13 Time 10:20 Rev Time 6.00
Received By tlarge Date 2000-08-13 Time 06:42 Sent To  
Notes
2001-01-08 00:00:001)IRRIGATION PLANS SHAL BE SIGNED AND
 SEALED IF VALUE IS OVER $50,000 PER F.S.
 553.79.
  
 2)ARCHITECTURAL PLANS SHALL BE SIGNED
 AND DATED.(PLANS ARE SEALED.)PER FLA.
 STATUTE 481.221.
  
 3)A WATER USE PERMIT IS REQD.FROM SFWMD
 FOR THE IRRIGATION SYSTEM.FLA.STATUTE
 373.219.
  
  
 4)SIZE OF GREASE TRAP SHALL BE APPROVED
 BY CITY OF WPB UTILITIES.CONTACT RODNEY
 COMPO AT 561-835-7423.SUBMIT COPY OF
 APPROVAL FORM.
  
 5)SANITARY SYSTEM REQUIRES ONE MAIN VENT
 THROUGH THE ROOF PER SPC SEC.904.3.1.
  
 6)CALCULATIONS FOR COMBUSTION AIR SHALL
 BE ON THE PLANS.PROVISIONS SHALL BE MADE
 FOR FUTURE DRYER.SGC.SEC.402.4.4.4,NFPA
 54 SEC.5.3.5.
  
 7)SUBMIT DETAIL OF LINT INTERCEPTOR.
 COMPLY W/SPC 1004.10.1.1.
  
 8)FLOOR DRAINS ARE REQD.IN THE LAUNDRY
 ROOM PER SPC SEC.409.4.5.
  
 9)SHT.P4.2-MIN.SIZE VENT SHALL BE 3"PER
 SPC SEC.911.3,TABLE 911.3.SEE RISER "D".
  
 10)APPROVAL FROM DEPT.OF BUSINESS REG.
 REQD.PRIOR TO APPROVAL FROM THIS DEPT.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
 11)DESIGN OF WASTE FOR KITCHEN SHALL
 COMPLY W/SPC SEC.921 FOR HORIZ.WASTE AND
 VENT SYSTEM.
  
 12)ALL RISERS ARE SHOWN WITH FLAT DRY
 MAIN VENTS.COMPLY W/SPC SEC.906.2.1.
  
 13)DELETED.8/13/00.TKL.
  
 14)DRAINS AT TRENCH DRAIN SHALL BE
 EQUIPPED W/AIR GAPS PER SPC SEC.806.
  
 15)CONTACT R.COMPO AT 561-835-7423 FOR
 APPROVAL OF OIL INTERCEPTOR.
  
  
 16)TWO WAY CLEANOUTS ARE REQD.ON THE
 INLET AND OUTLET OF THE GREASE INTER-
 CEPTOR.SPC 710.4.SEE ATTACHED.
  
 17)THE MIN.NUMBER OF PLUMBING FIXTURES
 FOR THE POOL SHALL COMPLY W/FLA.DEPT.OF
 HEALTH CHAPTER 64E-9.IF POOL AND POOL
 BUILDING WILL BE PERMITTED SEPARATELY,
 NOTE SUCH ON THE PLANS..
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 6 Status F Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 12:48 Rev Time 1.00
Received By tlarge Date 2000-07-12 Time 12:48 Sent To  
Notes
2001-01-08 00:00:00SAME COMMENTS DATED 7/5/00.

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-07-05 Cont ID  
Sent By tlarge Date 2000-07-05 Time 09:53 Rev Time 8.25
Received By tlarge Date 2000-07-03 Time 11:43 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A COMPLETE SET OF PLUMBING
 DRAWINGS FOR REVIEW.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.(INCLUDE CON-
 DENSATE RISER AND WATER RISERS.)
  
 SUBMIT A COMPLETE GAS ISOMETRIC FOR
 REVIEW. SHOW TYPE OF PIPING,ALL CUT
 SECTIONS OF PIPE,DISTANCE TO MOST REMOTE
 OUTLET,BTU LOAD OF EACH APPLIANCE,TOTAL
 BTU LOAD ON THE SYSTEM.SUBMIT COPY OF/OR
 REFERENCE APPLICABLE SIZING TABLE USED
 IN SYSTEM DESIGN,SHOW LOCATION OF METER.
  
 OIL INTERCEPTOR DESIGN SHALL COMPLY W/
 CITY OF WEST PALM BEACH DEPT.OF
 ENGINEERING STANDARDS.
  
 SANITARY SYSTEM REQUIRES ONE MAIN VENT
 THROUGH ROOF.(THIS IS NOT CLEARLY SHOWN
 ON THE PLANS.)SPC SEC.904.3.1.
  
 WASTE STACKS SHALL COMPLY W/SPC SEC.
 714.2.(SEE STACK"B" AND CHECK ALL OTHER
 STACKS).
  
 DESIGN AND CAPACITY OF GREASE TRAP SHALL
 BE APPROVED BY THE CITY OF WEST PALM
 BEACH UTILITIES.CONTACT R.COMPO AT
 561-835-7423.SUBMIT COPY OF APPROVAL
 FORM FROM UTILITIES.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR ALL GAS EQUIPMENT.COMPLY W/SGC SEC.
 402.4.`
  
 A LINT INTERCEPTOR IS REQUIRED FOR THE
 WASHING MACHINES LOCATED IN THE LAUNDRY
 ROOMS.SUBMIT DETAIL OF INTERCEPTOR.
 COMPLY W/SPC SEC.1004.10.1.1.AND FLOOR
 DRAINS ARE REQD.IN THE LAUNDRY ROOMS PER
 SPC SEC.409.4.5.
  
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET LINES OF THE INTERCEPTORS PER
 SPC 710.4.
  
 VACUUM RELIEF VALVES ARE REQUIRED ON THE
 WATER HEATERS AND STORAGE TANK PER SPC
 SEC.507.1.2.
  
 SHT.4.2-RISER "D"-MIN.SIZE VENT SHALL BE
 3"PER SPC SEC.911.3,TABLE 911.3.
  
 INDICATE SLOPE OF PIPE ON PLANS.COMPLY
 W/TABLE 714.1,714.2.
  
 WHIRLPOOL TUBS IN ROOMS 105,107 NOT
 PROPERLY VENTED.SPC SEC.901.2.
  
 SHT.P4.3-LAYOUT OF RISER DIAGRAM DOESN'T
 CORRELATE W/SHT.P2.1.(SEE 4"SAN.BY
 TOILET ROOMS.)
  
 WHERE IS APPROVAL FROM DEPT.OF BUSINESS
 AND PROFESSIONAL REGULATION FOR
 RESTAURANT? SUBMIT COPY OF APPROVAL.
 COUNTYWIDE AMENDMENT TO SPC SEC.101.4.7.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.

Review Stop P PLUMBING
Rev No 4 Status N Date 2000-06-06 Cont ID  
Sent By tlarge Date 2000-06-06 Time 14:20 Rev Time 0.00
Received By tlarge Date 2000-06-06 Time 14:20 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PERMIT NOT TO BE ISSUED UNTIL
 ALL PLAN REVIEW ITEMS HAVE BEEN
 CORRECTED.6/5/00.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-05-25 Cont ID  
Sent By tlarge Date 2000-05-25 Time 14:59 Rev Time 6.75
Received By tlarge Date 2000-05-25 Time 14:36 Sent To  
Notes
2001-01-08 00:00:001)PLANS SHALL BE APPROVED BY CITY OF
 WEST PALM BEACH ENGINEERING DEPT.FOR THE
 WATER SEWER,AND STORM DRAINAGE.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 2)SUBMIT COPIESOF APPROVALS FROM P.B.
 COUNTY HEALTH DEPT.AND DEP,(NOT INCLUDED
 W/RESPONSE SHEET.)COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7
  
 3)FLOOR DRAINS SHALL BE INSTALLED SO
 INLET IS AT ALL TIMES IN FULL VIEW.SEE
 F.D.IN 1ST.FLR.VENDING AREA.SPC SEC.
 409.4.1.2.
  
 4)SUBMIT COMPLETE GAS ISOMETRIC FOR
 REVIEW.SHOW TYPE OF PIPING,ALL CUT
 SECTIONS OF PIPE,DISTANCE TO MOST REMOTE
 OUTLET,BTU LOAD OF EACH APPLIANCE,TOTAL
 LOAD ON SYSTEM.SUBMITAPPLICABLE
 SIZING TABLE USED T0 DESIGN THE SYSTEM.
  
 5)SUBMIT DETAIL OF OIL INTERCEPTOR FOR
 ELEVATOR SUMP AND PUMP.VENTS SHALL
 COMPLY W/SPC SEC.906.2.1.
  
 6)SANITARY SYSTEM REQUIRES ONE MAIN VENT
 THROUGH THE ROOF.(DOES NOT APPEAR TO BE
 ON THE PLANS.)
  
 7)SHT.P-4-VENTS FOR TUBS SHALL COMPLY W/
 SPC SEC.906.2.1.(THEY SHALL BE A MIN.OF
 6"ABOVE THE FLOOD LEVEL RIM OF THE
 FIXTURE BEFORE OFFSETTING HORIZONTALLY.)
  
 8)VENT STACKS FOR WASTE AND SOIL STACKS
 SHALL COMPLY W/SPC 906.2.2, 918.
  
 9)KITCHEN STACK DIAGRAM-FIXTURES SHALL
 DISCHARGE TO GREASY WASTE,NOT TO
 SANITARY PER SPC SEC.1004.1, 1004.4.
 DRY VENTS NOT PERMITTED.
  
 10)SHT.P-4.3-TUBS,W.C.'S AND SHOWERS
 SHALL COMPLY W/SPC SEC.906.2.2.(VENTS)
  
 11)DESIGNAND CAPACITY OF GREASE TRAP
 SHALL BE APPROVED BY CITY OF WEST PALM
 UTILITIES.CALL R.COMPO AT (561)835-7423
 SUBMIT COPY OF APPROVAL FORM FROM
 UTILITIES.
  
 12)DESIGN OF CONDENSATE SYSTEM SHALL
 COMPLY W/SPC 304.8.3,304.8.4. OF SMC.
  
 13)SUBMIT DETAILS ON GAS VENTS.SHOW
 TERMINATION POINTS.COMPLY W/SGC SEC.
 608.
  
 14)SIZING OF BRANCH VENT FOR 1ST.FLR.
 TOILET ROOM SHALL COMPLY W/SPC TABLE
 920.4.
  
 15)ALL ADDENDUMS SHALL BE DRAWN ON FULL
 SHEETS AND SIGNED AND SEALED PER FLA.
 STATUTE.
  
 16)A LINT INTERCEPTOR IS REQUIRED FOR
 THE DISCHARGE FROM THE LAUNDRY ROOMS.SPC
 SEC.1004.11
  
 17)THE GREASE TRAP SHALL COMPLY W/
 CITY OF WEST PALM BEACH UTILITIES.
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET DRAIN LINES,AND MANHOLES ARE
 REQD.ON THE INLET AND OUTLET.
  
 18)WATER SUPPLY BRANCHES TO THE ROOMS
 SHALL BE VALVED PER SPC SEC.610.4.1.
  
 19)A WELL DRILLING PERMIT IS REQD.FROM
 DEP FOR THE WELL AND A WATER USE PERMIT
 IS REQD. FROM SFWMD FOR THE IRRIGATION
 SYSTEM PER FLA.STATUTE 373.219.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-03-16 Cont ID  
Sent By tlarge Date 2000-03-16 Time 15:29 Rev Time 7.50
Received By tlarge Date 2000-03-16 Time 15:29 Sent To  
Notes
2001-01-08 00:00:00CONTINUATION OF PLUMBING PLAN REVIEW:
 SHT.P-1.1.-MIN.SIZE OF WASHING MACHINE
 DRAIN AND STANDPIPE SHALL BE 2" PER SPC
 TABLE 713.1.
  
 SHT.P-2.1-FLOOR DRAIN IN LAUNDRY ROOM
 #112 SHALL BE IN FULL VIEW PER SPC
 409.4.1.2.
  
 DISCHARGE OF SUMP PUMP SHALL BE TO
 SANITARY SYSTEM,NOT TO STORM AND SHALL
 DISCHARGE THROUGH AN INTERCEPTOR PER
 SPC SEC.1004.1.
  
 RELIEF LINES FROM WATER HEATERS SHALL
 DISCHARGE TO EXTERIOR PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.6(3).SEE JOB
 SPEC.15486-3.02(F).
  
 SHT.P-3.3.-SHOWS SANITARY TO GREASE INT.
 COMPLY W/SPC SEC.1004.3.
  
 SHT.P-4.1-WATER RISER #4 DOESN'T MATCH
 FLOOR PLAN ON P-2.2.
  
 WATER SUPPLY CONTROL FOR RISERS AND
 BRANCHES SHALL COMPLY W/SPC SEC.610.4.1,
 610.4.2.
  
 SUBMIT WATER RISER DIAGRAMS FOR ALL
 AREAS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 SANITARY SYSTEM REQS.ONE MAIN VENT THRU
 ROOF PER SPC SEC.904.3.1.SHOW TERM-
 INATION POINT OF ALL VENTS.
  
 SHT.P-4.2-VENTS FOR TUBS SHALL COMPLY W/
 SPC SEC.906.2.1.(SEE RISER "C"-DOESN'T
 MATCH FLOOR PLAN.)
  
 VENT STACKS FOR WASTE AND SOIL STACKS
 SHALL COMPLY W/SPC SEC.906.2.2,918.
 DRY VENTS NOT PERMITTED.
  
 SHT.P-4.2-KIT.STACK DIAGRAM-FIXTURES
 SHALL DISCHARGE TO GREASY WASTE,NOT TO
 SANITARY PER SPC SEC.1004.1,1004.4.
 DRY VENTS NOT PERMITTED.
  
 VENTS FOR FLOOR DRAINS SHALL COMPLY W/
 SPC SEC.904.2.1.
  
 SHT.P-4.3-VENTS FOR TUBS,W.C.'S,SHOWERS
 SHALL COMPLY W/SPC SEC.906.2.2.
  
 ANTI-SCALD VALVES ARE REQD.IN SHOWERS
 PER SPC SEC.613.1.
  
 DESIGN AND CAPACITY OF GREASE TRAP SHALL
 COMPLY W/CITY OF WPB UTILITIES REQS.
 CONTACT RODNEY COMPO AT (561)835-7423.
 SUBMIT APPROVAL FORM FROM UTILITIES DEPT
  
 SIZING OF CONDENSATE DRAINS FROM PTAC
 UNITS SHALL COMPLY W/SMC SEC.304.8.4.
 (SEE SHT.M-3.1.)
  
 SUBMIT DETAILS ON VENTS FOR GAS EQUIP.
 TERMINATION OF GAS VENTS SHALL COMPLY W/
 SGC SEC.608,609
  
 END OF COMMENTS.
 TIMOTHY LARGE-PLUMBING PLANS EXAMINER
 (561)659-8096,EXT.8377.
  
 SIZING OF BRANCH VENT FOR 1ST.FLR.TOILET
 ROOMS SHALL COMPLY W/SPC TABLE 920.4.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-16 Cont ID  
Sent By tlarge Date 2000-03-14 Time 19:39 Rev Time 4.50
Received By tlarge Date 2000-03-14 Time 19:39 Sent To  
Notes
2001-01-08 00:00:00SHOW WATER SOURCE FOR IRRIGATION SYSTEM.
 IF FROM A WELL OR ARTIFICIAL BODY OF
 WATER A WATER USE PERMIT WILL BE REQD.
 FROM SO.FLA.WATER MNGMT.DISTRICT PER
 FLA.STATUTE 373.219.
  
 A RAIN SENSOR AND CONTROLLER SHALL BE
 INSTALLED ON THE IRRIGATION SYSTEM PER
 FLA.STATUTE SEC.373.62.
  
 CIVIL PLANS SHALL BE APPROVED BY CITY OF
 WEST PALM BEACH ENGINEERING DEPT.FOR THE
 WATER,SEWER AND STORM DRAINAGE.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 SUBMIT COPIES OF APPROVALS FROM DEP AND
 HEALTH DEPT.FOR INSTALLATION OF WATER
 MAIN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 PLANS SHALL BE ROUTED TO THE DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 SPEC.15140-PART 3.09(E).-HORIZONTAL
 COPPER PIPING SHALL BE SUPPORTED PER
 SPC SEC.310.3.4.
  
 SPEC.15430-3.01(G)-SPACING AND SIZE OF
 CLEANOUTS IN THE DRAINAGE SYSTEM SHALL
 COMPLY W/ SPC SEC.710.2.4.(1)(2),711.
  
 SPEC.15430-3.01(T)-TWOWAY CLEANOUTS
 ARE REQD.ON THE INLET AND OUTLET OF THE
 GREASE TRAP PER SPC 710.4.
  
 SHOW WIDTH AND LENGTH OF STANDARD SHOWER
 AND HANDICAP SHOWER STALLS.COMPLY W/
 COUNTYWIDE AMENDMENTS TO SPC SEC,
 409.8.2.1.,FACBC SEC.4.21.2 - 4.21.8.
 FIG.57,(A) OR (B).
  
 SHT.A-3.6-SHOW FIXTURE CLEARANCE OF
 WATER CLOSETS IN ACCESSIBLE BATHROOMS.
  
 GRAB BARS IN SLEEPING UNITS SHALL COMPLY
 W/FACBC SEC.4.26 & FIGS.33 & 34.VERTICAL
 BARS NOT ACCEPTABLE.SEE SHT.A-3.9.
  
 EQUIVALENT FACILITATION SHALL BE
 PROVIDED PER FACBC SEC.9.1.4.
 ACCESSIBLE ROOMS SHALL BE EVENLY DIS-
 PERSED.
  
 TOILETS IN ALL ACCESSIBLE ROOMS SHALL BE
 PROVIDED W/A PORTABLE OR ATTACHED SEAT
 PER FACBC SEC.9.2.3.
  
 KITCHENS,KITCHENETTES,OR WET BARS IN
 SLEEPING UNITS SHALL COMPLY W/FACBC SEC.
 9.2.2.(7)
  
 SHT.A-4.1-FLOOR DRAIN SHOWN UNDER ICE
 MACHINE-INLET SHALL BE IN FULL VIEW PER
 SPC SEC.409.4.1.2.
  
 SHT.A-8.4-DETAIL #6-CLEAR FLOOR SPACE
 SHALL BE PROVIDED FOR SINK AND SHALL BE
 CENTERED ON THE FIXTURE AND COMPLY W/
 FACBC SEC.4.24.1-4.24.7.
  
 GUEST LAUNDRY SHALL COMPLY W/FACBC SEC.
 9.1.1.
  
 WALLS AND FLOOR IN EMPLOYEE TOILET SHALL
 BE NONABSORBENT TO A HEIGHT OF 4' PER
 SBC SEC.1204.2.
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT.
 EQUIPMENT SHALL BE LISTED PER SGC SEC.
 402.1
  
 SUBMIT COMPLETE GAS DRAWING FOR REVIEW.
 SHOW TYPE OF PIPING,SIZES,BTU RATING OF
 EACH APPLIANCE,ETC.COMPLY W/SGC CHAPTS.
 3-6 & NFPA 54,58.INCLUDE CALCULATIONS
 FOR COMBUSTION AIR.
  
 MAX.TEMP.TO PUBLIC RESTROOMS SHALL NOT
 EXCEED 110 DEG.PER FLA.ENERGY CODE SEC.
 412.1.ABCD.2.3.2.
  
 SHT.P-1.1.-REMOVE VACUUM BREAKERS FROM
 WASHING MACHINE.
  
 SEE PLUMBING PLAN REVIEW STEP #2 FOR
 CONTINUATION OF PLUMBING COMMENTS.

Review Stop Z ZONING
Rev No 2 Status P Date 2000-09-19 Cont ID  
Sent By lmartine Date 2000-09-19 Time 15:56 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE APPROVAL ON NEW SITE PLAN

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-19 Cont ID  
Sent By gjoyce Date 2000-05-26 Time 15:12 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***