| Plan Review Stops For Permit 00030112 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2001-03-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-05 |
Time |
10:51 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-05 00:00:00 | PRODUCT APPROVAL DOORS & WINDOWS JW | | | PRODUCT APPROVAL DOORS & WINDOWSJW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-03-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-03-05 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-05 00:00:00 | TRUSS ENGINEERING | | | APPROVED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2000-12-20 |
Time |
07:50 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING REVIEW 12/20/2000 | | | | | | 1). ARCHITECTURAL: ITEM# 10. SEE FLORIDA | | | ACCESSIBILITY CODE ITEMS 5.1- 5.6.5.2 | | | COUNTER TOPS WHERE FOOD OR DRINK IS | | | SERVED AT COUNTERS EXCEEDING 34" IN | | | HEIGTH. 5.5 FOOD SERVICE LINES & 5.6 | | | TABLEWARE AND CONDIMENT AREAS. | | | | | | 2). STRUCTURAL DRAWAINGS ITEM # 13. | | | DRAWINGS ARE REQUIRED TO DETERMINE | | | REVISIONS. | | | BUILDING PLAN REVIEW: | | | JIM WITMER | | | (561) 659-8096 EX 8412. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-12-07 |
Time |
11:22 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION FOR WHEEL CHAIR LIFT DENIED PER | | | LOUIS MARTINEZ. | | | 1)APPROVED PLANS DO NOT SHOW ADEQUATE | | | CLEARANCE FOR LIFT AND MAST.REVISE | | | DRAWINGS TO ACCOMMODATE LIFT AND MAST. | | | | | | 2)HAVE ENGINEER CERTIFY THAT EXISTING | | | WALL WILL SUPPORT MAST AND WALL. | | | | | | 3)PROVIDE ELECTRICAL INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-05 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | REVISE MARRIOTT HOTEL FROM METAL FRAME | | | TO MASONRY | | | | | | | | | PROVISO | | | --------- | | | | | | 1]SUPPLY 3 COPYS OF ENERGY EFF. CALCS. | | | 2]SUMBIT NEW THRESHOLD PLAN. | | | 3]SUBMIT SHORING PLAN. | | | 4]PROVIDE TEST REPORTS FOR EXTERIOR | | | WINDOWS AND DOORS,ROOF COVER.EXTERIOR | | | GLAZING SHALL COMPLY WITH IMPACT | | | PROTECTION. | | | 5]SUBMIT ONE MORE SET OF DRAWINGS SIGNED | | | AND SEALED. | | | | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 659-8096#8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-06-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-04-07 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
1900-04-07 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING PERMIT ONLY PER HHP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
P |
Date |
2001-05-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-23 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-23 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
N |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-17 |
Time |
22:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-17 |
Time |
22:47 |
Sent To |
|
|
| Notes |
| 2001-04-17 00:00:00 | ALREADY REVIEW ON 3/31 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2001-04-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-04 |
Time |
19:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-04 |
Time |
19:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2001-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-26 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-26 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-13 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-13 |
Time |
09:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
20:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-11 |
Time |
20:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: NEED TO SUBMIT PLANS SHOWING | | | OTHER CHANGES MENTIONED IN BULLETIN #2 | | | | | | 2)NOTE: PLEASE NOTE THAT THE SHEETS B2-7 | | | AND B2-8 ARE TO BE SIGNED AND SEALED BY | | | ARCH/ENGINEER OF RECORD. PLEASE SEE THE | | | F.A.CCHAPTERS 481 AND 471 FOR THE REQ` | | | MENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096ETX 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-25 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-25 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REV OK FOR THE FOLLOWING PAGES | | | E----1.1,1.2,1.3,1.4,1.5,2.1,2.3,2.2, | | | 2.4,2.5,3.1,4.1,4.2,4.3,4.4,5.1,5.2, | | | | | | AIC RATINGS SHOWN AND ADDITIONAL LOADS | | | SHOWN FOR PANELPE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-07-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
|
Time |
13:02 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2000-07-10 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REV #5 PAGES E1.2,.3,.4, 2.2, 4.1,4.2, | | | 4.4 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-06-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-06-28 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-07-10 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ELECTRIC OKREV.#4 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2000-06-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-09 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-09 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ELECTRICAL PLANS AND PERMIT TO BE RESUB- | | | SEP. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-03-22 |
Time |
14:30 |
Rev Time |
4.00 |
| Received By |
jleahy |
Date |
2000-03-22 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1-PAGES E1.2,E1.3,E1.4 ALL SHOW PANELS | | | MOUNTED IN THE LINEN STORAGE ROOM SEE | | | SECTIONS 240-24D, AND 384-7 WHY THEY | | | CAN NOT BE LOCATED THERE! | | | | | | 2-PAGE E4.2 SHOWS A PANEL LABLED "PE" | | | HOW IS THIS FED AND IT SHOWS NO LOADS | | | OTHER THAN LIGHTING.ALSO THIS IS IN | | | A SEPARATE STRUCTURE PLEASE TREAT AS | | | PER CODE. | | | | | | 3-NO LOAD FOR "PE" SHOWN IN LOAD | | | CALCULATION PLEASE CHECK | | | | | | 4-FAULT CURRENT RATING NEEDED FOR ALL | | | SERVICE AND DISTRIBUTION EQUIPMENT!!! | | | 110-9,10 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-08-22 |
Time |
15:19 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED | | | ALL PREVIOUS COMMENTS HAVE BEEN REVISED. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2000-06-09 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2000-06-09 |
Time |
13:12 |
Rev Time |
0.10 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE NOTES ATTACHED PER UTILITIES4/3/2000 | | | BY MG |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-24 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-24 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2001-03-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-07 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-07 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-08-14 |
Time |
15:56 |
Rev Time |
1.00 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. PROVIDE TAMPER SWITCHES ON DOUBLE | | | DETECTOR CHECK VALVES. | | | 2.FIRE ALARM SYSTEM SHALL BE CLASS "A" | | | OR ADDRESSABLE. | | | 3.FIRE ALARM SYSTEM SHALL BE 15 DECIBELS | | | ABOVE AMBIENT NOISE THROUGHOUT. | | | 4. PROVIDE FIRE ALARM STROBE LIGHTS IN | | | ALL PUBLIC RESTROOMS. | | | 5. PROVIDE APPROVED DOOR CLOSERS ON ALL | | | RATED FIRE DOORS. | | | 6. PROVIDE APPROVED WIRED-IN SMOKE | | | DETECTORS IN ALL GUESTROOMS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-05-31 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-05-31 |
Time |
16:24 |
Rev Time |
0.35 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
ndenmark |
Date |
2000-05-23 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FIRE SPRINKLER PROTECTION FOR ATTIC | | | TO COMPLY WITH NFPA 13. PLANS SHOWED | | | ONLY HEAD LOCATIONS IN THE ATTIC. | | | FIRE SPRINKLER PIPING, AND HANGERS | | | NOT SHOWN. | | | PLAN REVIEWED BY LT. CARSILLO |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-03-17 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-03-17 |
Time |
09:30 |
Rev Time |
1.00 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FIRE ALARM SYSTEM SHALL BE CLASS "A" OR | | | ADDRESSABLE | | | | | | PROVIDE FIRE SPRINKLER DRAWINGS | | | | | | PROVIDE STANDPIPE | | | | | | FIRE HYDRANT SHALL BE LOCATED WITHIN | | | 150 FEET OF FIRE DEPARTMENT CONNECTION | | | | | | PROVIDE SHOP DRAWINGS FOR KITCHEN HOOD | | | AND EXTINGUISHING SYSTEM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-03-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-23 |
Time |
11:26 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-03-23 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2001-03-23 00:00:00 | REVISION - REVISED CAPACITIES FOR FCU-6 | | | ON FCU SCHEDULE. DELETED EF-14 FROM THE | | | FAN SCHEDULE.(M1.1)DELETE EF-14. | | | REVISED DUCTWORK AT "GRAB-N-GO" 116. | | | REVIED PLAN NOTE #36 AND ADD PLAN NOTE | | | #44.(M2.1) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-14 |
Time |
14:00 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-08-14 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-07-24 |
Time |
14:28 |
Rev Time |
2.00 |
| Received By |
ndenmark |
Date |
2000-07-24 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ACCEPTED BY REVISIONS DATED 6/15/00 | | | PRIOR COMMENTS CORRECTED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2000-06-02 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-06-02 |
Time |
14:31 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-06-02 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | DENIED FOR MECHANICAL | | | | | | BASED ON PLAN REVIEW 00030112 THE FOLLOW | | | ING ITEMS NEED TO BE REVISED ON THE MECH | | | DRAWINGS: | | | 1) PROVIDE INFORMATION ON BATH EXHAUST | | | DUCT MATERIAL FOR CODE COMPLIANCE | | | 2) OUTSIDE AIR CALCULATIONS LOCATED ON | | | SKM-9 NEED TO BE PERMANTLY ATTACHED TO | | | APPROVED DRAWINGS | | | 3) AIR BALANCE SCHEDULE LOCATED ON SKM- | | | 10 NEEDS TO BE PERMANENTLY ATTACHED TO | | | APPROVED DRAWINGS | | | 4) ALL FIRE DAMPER LOCATIONS TO BE SHOWN | | | AND PROPERLY IDENTIFIED ON PLANS PER | | | 1997 SMC 610.6 | | | 5) FIRE DAMPERS REQUIRED AT ALL WALL | | | PENETRATIONS OF 1 HOUR OR MORE PER 1997 | | | SMC 610.1.2 SEE PRIOR LIST FOR SPECIFIC | | | | | | THE FOLLOWING ARE PROVISO ITEMS: | | | 1) KITCHEN HOOD AND EXHAUST DUCT WILL | | | REQUIRE SEPARATE MECHANICAL PERMIT | | | 2) SEPARATE PERMITS REQUIRED FOR HOOD, | | | SUPPRESSION, WALK IN COOLER/FREEZER,ETC. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-03-20 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-03-20 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
ndenmark |
Date |
2000-05-22 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | | | | 1)PROVIDE INFORMATION ON EXHAUST DUCT | | | RISER MATERIAL | | | 2)KITCHEN HOOD AND EXHAUST DUCT WILL RE- | | | QUIRE SEPARATE PERMIT AND MORE DETAILED | | | PLANS | | | 3)PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 4)PROVIDE AIR BALANCE SCHEDULE PER 1997 | | | SMC 501.2 | | | 5)1997 SMC 304.8.6.1 REQUIRES SECONDARY | | | DRAIN LINE TO BE RUN SEPARATELY FROM | | | PRIMARY CONDENSATE DRAIN LINE | | | 6)PROVIDE DETAIL FOR PROTECTION OF DRYER | | | VENT IN RATED WALL | | | 7)1997 SMC 610.6 REQUIRES SPECIFIC LOCA- | | | TION AND INSTALLATION DETAILS FOR EACH | | | FIRE DAMPER, FIRE DOOR, ETC. TO BE SHOWN | | | AND PROPERLY IDENTIFIED ON THE BUILDING | | | PLANS BY THE DESIGNER. THE FOLLOWING | | | LOCATIONS DO NOT INDICATE FIRE DAMPERS | | | M2.1 2-18X12 THRU RATED WALLS 2 PLACES | | | 2-14X12 THRU RATED MEETING ROOM | | | WALLS | | | 2-12X8 THRU MEN'S AND WOMEN'S ROOM | | | RATED WALLS | | | NO FIRE DAMPERS AT COMBUSTION AIR | | | OPENING | | | 2-18X10 IN RATED MAINTANANCE ROOM | | | WALL | | | PROVIDE DETAIL FOR FIRE PROTECTION OF | | | OPENING @ 14" FLUE PIPE PENETRATING | | | RATED WALL BY WATER HEATER ROOM | | | M2-2 FIVE DUCTS LEAVING MECH ROOM 217 | | | ON 2ND FLOOR PLAN NO FIRE DAMPERS SHOWN | | | M2-3 10X8 R/A DUCT @ STORAGE ROOM 318A | | | RATED WALL | | | 10X8 R/A DUCT @ RM 320 RATED WALL | | | M2-4 12X8 R/A DUCT @ RM 418 AND RM 420 | | | | | | SEPARATE PERMITS AND PLANS WILL BE | | | REQUIRED FOR WALK IN COOLERS/FREEZERS, | | | KITCHEN HOOD, FIRE SUPPRESSION SYSTEM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
17 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
16 |
Status |
N |
Date |
2001-06-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-08 |
Time |
15:57 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2001-06-08 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2001-06-08 00:00:00 | REVIEW NOTES: | | | | | | NO PLUMBING TO REVIEW ON THIS REVIEW | | | REFERED TO ENGINEERING. | | | | | | KSTEVENS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
15 |
Status |
P |
Date |
2001-06-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-06-02 |
Time |
08:32 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2001-06-02 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2001-06-02 00:00:00 | PROVISO; | | | | | | 1.SHT. P-4.3 AND P-4.4; SANITARY RISER | | | DIAGRAMS ARE NOT SIZED PROPERLY. | | | | | | REVIEW BY JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
14 |
Status |
P |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-05-07 |
Time |
16:31 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2001-05-07 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | REVISIONS; PAGE; P-1.1, P-2.1, P-2.2 | | | P-2.6, P-4.4, & P-4.5 OK | | | P-4.2 & P-4.3 UNSAT. | | | PIPE SIZES NOT CORRECT ON RISER DIAGRAMS | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
13 |
Status |
P |
Date |
2001-04-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-28 |
Time |
13:09 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-04-28 |
Time |
13:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
12 |
Status |
F |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-29 |
Time |
16:41 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2001-03-15 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2001-03-29 00:00:00 | DENIED; | | | | | | 1.NEED APPROVAL FROM HEALTH DEPARTMENT | | | BEFORE BATHROOM BY POOL CAN BE DELETED | | | POOL PLANS HAVE BEEN APPROVED BY THE | | | HEALTH DEPARTMENT WITH THE BATHROOM | | | ON THE PLAN. | | | | | | 2.WHAT IS THE BTU RATING OF THE FIRE- | | | PLACE? NOT ADDED TO TOTAL BTU'S. | | | | | | 3.PAGE P-4.2 SANITARY STACKS SHALL | | | COMPLY WITH 94 SPC 714.2. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
11 |
Status |
P |
Date |
2000-12-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-10 |
Time |
12:35 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION: COMPLY W/SPC 94 SEC 601.1 | | | PROVIDE A ANTI SYPHON DEVICE FOR SOAP | | | DISPENSING SYSTEM,WATTS 36-N. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
F |
Date |
2000-11-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-11-01 |
Time |
18:06 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-11-01 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)PLUMBING SYSTEM DESIGN APPEARS TO | | | BE BASED UPON THE 1997 PLUMBING CODE. | | | THE CODE IN EFFECT IS THE 1994 STANDARD | | | PLUMBING CODE.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.101. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-05 |
Time |
10:12 |
Rev Time |
3.50 |
| Received By |
tlarge |
Date |
2000-09-05 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | H**************PROVISO****************** | | | 1)SHEET P-4.3 REFERS TO SHT.P-4.2 FOR | | | POOL HOUSE PLUMBING RISER.PLUMBING RISER | | | FOR POOL HOUSE IS NOT ON THIS SHEET. | | | SUBMIT SIGNED AND SEALED SANITARY AND | | | WATER RISERS FOR REVIEW.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 2)A WATER USE PERMIT FOR THE IRRIGATION | | | SYSTEM IS REQD.FROM SFWMD PER F.S. | | | 373.219.THE PERMIT SHALL BE OBTAINED | | | PRIOR TO THE ISSUANCE OF THE IRRIGATION | | | PERMIT. | | | | | | 3)A WELL DRILLING PERMIT MAY ALSO BE | | | REQD.FROM SFWMD AND THE PALM BEACH | | | COUNTY HEALTH DEPT.VERIFICATION SHALL | | | BE SUBMITTED FOR REVIEW. | | | | | | 4)DETAIL/MANUF.SHEETS FOR LINT INTER- | | | CEPTOR SHALL BE SUBMITTED FOR REVIEW | | | PRIOR TO INSTALLATION.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 5)ADDITIONAL PLUMBING FIXTURES MAY BE | | | REQD.IN THE POOL TOILET ROOM PENDING | | | REVIEW BY THEPALM BEACH COUNTY HEALTH | | | DEPT.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 101.4.7. | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-16 |
Time |
13:10 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
2000-08-16 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | | | | THE PLUMBING PLANS ARE REVIEWED FOR THE | | | INSTALLATION OF THE UNDERGROUND DRAIN- | | | AGE SYSTEM ONLY (INCLUDES SANITARY AND | | | STORM).UPON SUBMITTAL AND REVIEWOF | | | THE REVISED DRAWINGS THE PLUMBING WILL | | | BE RELEASED FOR THE COMPLETE SYSTEMS.NO | | | ABOVE SLAB WORK SHALL BE INSTALLED UNDER | | | THIS PROVISO. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2000-08-13 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-13 |
Time |
10:20 |
Rev Time |
6.00 |
| Received By |
tlarge |
Date |
2000-08-13 |
Time |
06:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)IRRIGATION PLANS SHAL BE SIGNED AND | | | SEALED IF VALUE IS OVER $50,000 PER F.S. | | | 553.79. | | | | | | 2)ARCHITECTURAL PLANS SHALL BE SIGNED | | | AND DATED.(PLANS ARE SEALED.)PER FLA. | | | STATUTE 481.221. | | | | | | 3)A WATER USE PERMIT IS REQD.FROM SFWMD | | | FOR THE IRRIGATION SYSTEM.FLA.STATUTE | | | 373.219. | | | | | | | | | 4)SIZE OF GREASE TRAP SHALL BE APPROVED | | | BY CITY OF WPB UTILITIES.CONTACT RODNEY | | | COMPO AT 561-835-7423.SUBMIT COPY OF | | | APPROVAL FORM. | | | | | | 5)SANITARY SYSTEM REQUIRES ONE MAIN VENT | | | THROUGH THE ROOF PER SPC SEC.904.3.1. | | | | | | 6)CALCULATIONS FOR COMBUSTION AIR SHALL | | | BE ON THE PLANS.PROVISIONS SHALL BE MADE | | | FOR FUTURE DRYER.SGC.SEC.402.4.4.4,NFPA | | | 54 SEC.5.3.5. | | | | | | 7)SUBMIT DETAIL OF LINT INTERCEPTOR. | | | COMPLY W/SPC 1004.10.1.1. | | | | | | 8)FLOOR DRAINS ARE REQD.IN THE LAUNDRY | | | ROOM PER SPC SEC.409.4.5. | | | | | | 9)SHT.P4.2-MIN.SIZE VENT SHALL BE 3"PER | | | SPC SEC.911.3,TABLE 911.3.SEE RISER "D". | | | | | | 10)APPROVAL FROM DEPT.OF BUSINESS REG. | | | REQD.PRIOR TO APPROVAL FROM THIS DEPT. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 | | | | | | 11)DESIGN OF WASTE FOR KITCHEN SHALL | | | COMPLY W/SPC SEC.921 FOR HORIZ.WASTE AND | | | VENT SYSTEM. | | | | | | 12)ALL RISERS ARE SHOWN WITH FLAT DRY | | | MAIN VENTS.COMPLY W/SPC SEC.906.2.1. | | | | | | 13)DELETED.8/13/00.TKL. | | | | | | 14)DRAINS AT TRENCH DRAIN SHALL BE | | | EQUIPPED W/AIR GAPS PER SPC SEC.806. | | | | | | 15)CONTACT R.COMPO AT 561-835-7423 FOR | | | APPROVAL OF OIL INTERCEPTOR. | | | | | | | | | 16)TWO WAY CLEANOUTS ARE REQD.ON THE | | | INLET AND OUTLET OF THE GREASE INTER- | | | CEPTOR.SPC 710.4.SEE ATTACHED. | | | | | | 17)THE MIN.NUMBER OF PLUMBING FIXTURES | | | FOR THE POOL SHALL COMPLY W/FLA.DEPT.OF | | | HEALTH CHAPTER 64E-9.IF POOL AND POOL | | | BUILDING WILL BE PERMITTED SEPARATELY, | | | NOTE SUCH ON THE PLANS.. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2000-07-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-12 |
Time |
12:48 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-07-12 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SAME COMMENTS DATED 7/5/00. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-07-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-05 |
Time |
09:53 |
Rev Time |
8.25 |
| Received By |
tlarge |
Date |
2000-07-03 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT A COMPLETE SET OF PLUMBING | | | DRAWINGS FOR REVIEW.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1.(INCLUDE CON- | | | DENSATE RISER AND WATER RISERS.) | | | | | | SUBMIT A COMPLETE GAS ISOMETRIC FOR | | | REVIEW. SHOW TYPE OF PIPING,ALL CUT | | | SECTIONS OF PIPE,DISTANCE TO MOST REMOTE | | | OUTLET,BTU LOAD OF EACH APPLIANCE,TOTAL | | | BTU LOAD ON THE SYSTEM.SUBMIT COPY OF/OR | | | REFERENCE APPLICABLE SIZING TABLE USED | | | IN SYSTEM DESIGN,SHOW LOCATION OF METER. | | | | | | OIL INTERCEPTOR DESIGN SHALL COMPLY W/ | | | CITY OF WEST PALM BEACH DEPT.OF | | | ENGINEERING STANDARDS. | | | | | | SANITARY SYSTEM REQUIRES ONE MAIN VENT | | | THROUGH ROOF.(THIS IS NOT CLEARLY SHOWN | | | ON THE PLANS.)SPC SEC.904.3.1. | | | | | | WASTE STACKS SHALL COMPLY W/SPC SEC. | | | 714.2.(SEE STACK"B" AND CHECK ALL OTHER | | | STACKS). | | | | | | DESIGN AND CAPACITY OF GREASE TRAP SHALL | | | BE APPROVED BY THE CITY OF WEST PALM | | | BEACH UTILITIES.CONTACT R.COMPO AT | | | 561-835-7423.SUBMIT COPY OF APPROVAL | | | FORM FROM UTILITIES. | | | | | | SUBMIT CALCULATIONS FOR COMBUSTION AIR | | | FOR ALL GAS EQUIPMENT.COMPLY W/SGC SEC. | | | 402.4.` | | | | | | A LINT INTERCEPTOR IS REQUIRED FOR THE | | | WASHING MACHINES LOCATED IN THE LAUNDRY | | | ROOMS.SUBMIT DETAIL OF INTERCEPTOR. | | | COMPLY W/SPC SEC.1004.10.1.1.AND FLOOR | | | DRAINS ARE REQD.IN THE LAUNDRY ROOMS PER | | | SPC SEC.409.4.5. | | | | | | TWO WAY CLEANOUTS ARE REQD.ON THE INLET | | | AND OUTLET LINES OF THE INTERCEPTORS PER | | | SPC 710.4. | | | | | | VACUUM RELIEF VALVES ARE REQUIRED ON THE | | | WATER HEATERS AND STORAGE TANK PER SPC | | | SEC.507.1.2. | | | | | | SHT.4.2-RISER "D"-MIN.SIZE VENT SHALL BE | | | 3"PER SPC SEC.911.3,TABLE 911.3. | | | | | | INDICATE SLOPE OF PIPE ON PLANS.COMPLY | | | W/TABLE 714.1,714.2. | | | | | | WHIRLPOOL TUBS IN ROOMS 105,107 NOT | | | PROPERLY VENTED.SPC SEC.901.2. | | | | | | SHT.P4.3-LAYOUT OF RISER DIAGRAM DOESN'T | | | CORRELATE W/SHT.P2.1.(SEE 4"SAN.BY | | | TOILET ROOMS.) | | | | | | WHERE IS APPROVAL FROM DEPT.OF BUSINESS | | | AND PROFESSIONAL REGULATION FOR | | | RESTAURANT? SUBMIT COPY OF APPROVAL. | | | COUNTYWIDE AMENDMENT TO SPC SEC.101.4.7. | | | | | | IF YOU HAVE ANY QUESTIONS I CAN BE | | | REACHED AT 561-659-8096,EXT.8377. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-06 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-06-06 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PERMIT NOT TO BE ISSUED UNTIL | | | ALL PLAN REVIEW ITEMS HAVE BEEN | | | CORRECTED.6/5/00. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-05-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-25 |
Time |
14:59 |
Rev Time |
6.75 |
| Received By |
tlarge |
Date |
2000-05-25 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)PLANS SHALL BE APPROVED BY CITY OF | | | WEST PALM BEACH ENGINEERING DEPT.FOR THE | | | WATER SEWER,AND STORM DRAINAGE.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 2)SUBMIT COPIESOF APPROVALS FROM P.B. | | | COUNTY HEALTH DEPT.AND DEP,(NOT INCLUDED | | | W/RESPONSE SHEET.)COUNTYWIDE AMENDMENTS | | | TO SPC SEC.101.4.7 | | | | | | 3)FLOOR DRAINS SHALL BE INSTALLED SO | | | INLET IS AT ALL TIMES IN FULL VIEW.SEE | | | F.D.IN 1ST.FLR.VENDING AREA.SPC SEC. | | | 409.4.1.2. | | | | | | 4)SUBMIT COMPLETE GAS ISOMETRIC FOR | | | REVIEW.SHOW TYPE OF PIPING,ALL CUT | | | SECTIONS OF PIPE,DISTANCE TO MOST REMOTE | | | OUTLET,BTU LOAD OF EACH APPLIANCE,TOTAL | | | LOAD ON SYSTEM.SUBMITAPPLICABLE | | | SIZING TABLE USED T0 DESIGN THE SYSTEM. | | | | | | 5)SUBMIT DETAIL OF OIL INTERCEPTOR FOR | | | ELEVATOR SUMP AND PUMP.VENTS SHALL | | | COMPLY W/SPC SEC.906.2.1. | | | | | | 6)SANITARY SYSTEM REQUIRES ONE MAIN VENT | | | THROUGH THE ROOF.(DOES NOT APPEAR TO BE | | | ON THE PLANS.) | | | | | | 7)SHT.P-4-VENTS FOR TUBS SHALL COMPLY W/ | | | SPC SEC.906.2.1.(THEY SHALL BE A MIN.OF | | | 6"ABOVE THE FLOOD LEVEL RIM OF THE | | | FIXTURE BEFORE OFFSETTING HORIZONTALLY.) | | | | | | 8)VENT STACKS FOR WASTE AND SOIL STACKS | | | SHALL COMPLY W/SPC 906.2.2, 918. | | | | | | 9)KITCHEN STACK DIAGRAM-FIXTURES SHALL | | | DISCHARGE TO GREASY WASTE,NOT TO | | | SANITARY PER SPC SEC.1004.1, 1004.4. | | | DRY VENTS NOT PERMITTED. | | | | | | 10)SHT.P-4.3-TUBS,W.C.'S AND SHOWERS | | | SHALL COMPLY W/SPC SEC.906.2.2.(VENTS) | | | | | | 11)DESIGNAND CAPACITY OF GREASE TRAP | | | SHALL BE APPROVED BY CITY OF WEST PALM | | | UTILITIES.CALL R.COMPO AT (561)835-7423 | | | SUBMIT COPY OF APPROVAL FORM FROM | | | UTILITIES. | | | | | | 12)DESIGN OF CONDENSATE SYSTEM SHALL | | | COMPLY W/SPC 304.8.3,304.8.4. OF SMC. | | | | | | 13)SUBMIT DETAILS ON GAS VENTS.SHOW | | | TERMINATION POINTS.COMPLY W/SGC SEC. | | | 608. | | | | | | 14)SIZING OF BRANCH VENT FOR 1ST.FLR. | | | TOILET ROOM SHALL COMPLY W/SPC TABLE | | | 920.4. | | | | | | 15)ALL ADDENDUMS SHALL BE DRAWN ON FULL | | | SHEETS AND SIGNED AND SEALED PER FLA. | | | STATUTE. | | | | | | 16)A LINT INTERCEPTOR IS REQUIRED FOR | | | THE DISCHARGE FROM THE LAUNDRY ROOMS.SPC | | | SEC.1004.11 | | | | | | 17)THE GREASE TRAP SHALL COMPLY W/ | | | CITY OF WEST PALM BEACH UTILITIES. | | | TWO WAY CLEANOUTS ARE REQD.ON THE INLET | | | AND OUTLET DRAIN LINES,AND MANHOLES ARE | | | REQD.ON THE INLET AND OUTLET. | | | | | | 18)WATER SUPPLY BRANCHES TO THE ROOMS | | | SHALL BE VALVED PER SPC SEC.610.4.1. | | | | | | 19)A WELL DRILLING PERMIT IS REQD.FROM | | | DEP FOR THE WELL AND A WATER USE PERMIT | | | IS REQD. FROM SFWMD FOR THE IRRIGATION | | | SYSTEM PER FLA.STATUTE 373.219. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-03-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-16 |
Time |
15:29 |
Rev Time |
7.50 |
| Received By |
tlarge |
Date |
2000-03-16 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CONTINUATION OF PLUMBING PLAN REVIEW: | | | SHT.P-1.1.-MIN.SIZE OF WASHING MACHINE | | | DRAIN AND STANDPIPE SHALL BE 2" PER SPC | | | TABLE 713.1. | | | | | | SHT.P-2.1-FLOOR DRAIN IN LAUNDRY ROOM | | | #112 SHALL BE IN FULL VIEW PER SPC | | | 409.4.1.2. | | | | | | DISCHARGE OF SUMP PUMP SHALL BE TO | | | SANITARY SYSTEM,NOT TO STORM AND SHALL | | | DISCHARGE THROUGH AN INTERCEPTOR PER | | | SPC SEC.1004.1. | | | | | | RELIEF LINES FROM WATER HEATERS SHALL | | | DISCHARGE TO EXTERIOR PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.507.6(3).SEE JOB | | | SPEC.15486-3.02(F). | | | | | | SHT.P-3.3.-SHOWS SANITARY TO GREASE INT. | | | COMPLY W/SPC SEC.1004.3. | | | | | | SHT.P-4.1-WATER RISER #4 DOESN'T MATCH | | | FLOOR PLAN ON P-2.2. | | | | | | WATER SUPPLY CONTROL FOR RISERS AND | | | BRANCHES SHALL COMPLY W/SPC SEC.610.4.1, | | | 610.4.2. | | | | | | SUBMIT WATER RISER DIAGRAMS FOR ALL | | | AREAS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | SANITARY SYSTEM REQS.ONE MAIN VENT THRU | | | ROOF PER SPC SEC.904.3.1.SHOW TERM- | | | INATION POINT OF ALL VENTS. | | | | | | SHT.P-4.2-VENTS FOR TUBS SHALL COMPLY W/ | | | SPC SEC.906.2.1.(SEE RISER "C"-DOESN'T | | | MATCH FLOOR PLAN.) | | | | | | VENT STACKS FOR WASTE AND SOIL STACKS | | | SHALL COMPLY W/SPC SEC.906.2.2,918. | | | DRY VENTS NOT PERMITTED. | | | | | | SHT.P-4.2-KIT.STACK DIAGRAM-FIXTURES | | | SHALL DISCHARGE TO GREASY WASTE,NOT TO | | | SANITARY PER SPC SEC.1004.1,1004.4. | | | DRY VENTS NOT PERMITTED. | | | | | | VENTS FOR FLOOR DRAINS SHALL COMPLY W/ | | | SPC SEC.904.2.1. | | | | | | SHT.P-4.3-VENTS FOR TUBS,W.C.'S,SHOWERS | | | SHALL COMPLY W/SPC SEC.906.2.2. | | | | | | ANTI-SCALD VALVES ARE REQD.IN SHOWERS | | | PER SPC SEC.613.1. | | | | | | DESIGN AND CAPACITY OF GREASE TRAP SHALL | | | COMPLY W/CITY OF WPB UTILITIES REQS. | | | CONTACT RODNEY COMPO AT (561)835-7423. | | | SUBMIT APPROVAL FORM FROM UTILITIES DEPT | | | | | | SIZING OF CONDENSATE DRAINS FROM PTAC | | | UNITS SHALL COMPLY W/SMC SEC.304.8.4. | | | (SEE SHT.M-3.1.) | | | | | | SUBMIT DETAILS ON VENTS FOR GAS EQUIP. | | | TERMINATION OF GAS VENTS SHALL COMPLY W/ | | | SGC SEC.608,609 | | | | | | END OF COMMENTS. | | | TIMOTHY LARGE-PLUMBING PLANS EXAMINER | | | (561)659-8096,EXT.8377. | | | | | | SIZING OF BRANCH VENT FOR 1ST.FLR.TOILET | | | ROOMS SHALL COMPLY W/SPC TABLE 920.4. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-03-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-14 |
Time |
19:39 |
Rev Time |
4.50 |
| Received By |
tlarge |
Date |
2000-03-14 |
Time |
19:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHOW WATER SOURCE FOR IRRIGATION SYSTEM. | | | IF FROM A WELL OR ARTIFICIAL BODY OF | | | WATER A WATER USE PERMIT WILL BE REQD. | | | FROM SO.FLA.WATER MNGMT.DISTRICT PER | | | FLA.STATUTE 373.219. | | | | | | A RAIN SENSOR AND CONTROLLER SHALL BE | | | INSTALLED ON THE IRRIGATION SYSTEM PER | | | FLA.STATUTE SEC.373.62. | | | | | | CIVIL PLANS SHALL BE APPROVED BY CITY OF | | | WEST PALM BEACH ENGINEERING DEPT.FOR THE | | | WATER,SEWER AND STORM DRAINAGE.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.101.4.7. | | | | | | SUBMIT COPIES OF APPROVALS FROM DEP AND | | | HEALTH DEPT.FOR INSTALLATION OF WATER | | | MAIN.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 101.4.7. | | | | | | PLANS SHALL BE ROUTED TO THE DEPT.OF | | | BUSINESS REGULATION FOR REVIEW AND | | | APPROVAL.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | SPEC.15140-PART 3.09(E).-HORIZONTAL | | | COPPER PIPING SHALL BE SUPPORTED PER | | | SPC SEC.310.3.4. | | | | | | SPEC.15430-3.01(G)-SPACING AND SIZE OF | | | CLEANOUTS IN THE DRAINAGE SYSTEM SHALL | | | COMPLY W/ SPC SEC.710.2.4.(1)(2),711. | | | | | | SPEC.15430-3.01(T)-TWOWAY CLEANOUTS | | | ARE REQD.ON THE INLET AND OUTLET OF THE | | | GREASE TRAP PER SPC 710.4. | | | | | | SHOW WIDTH AND LENGTH OF STANDARD SHOWER | | | AND HANDICAP SHOWER STALLS.COMPLY W/ | | | COUNTYWIDE AMENDMENTS TO SPC SEC, | | | 409.8.2.1.,FACBC SEC.4.21.2 - 4.21.8. | | | FIG.57,(A) OR (B). | | | | | | SHT.A-3.6-SHOW FIXTURE CLEARANCE OF | | | WATER CLOSETS IN ACCESSIBLE BATHROOMS. | | | | | | GRAB BARS IN SLEEPING UNITS SHALL COMPLY | | | W/FACBC SEC.4.26 & FIGS.33 & 34.VERTICAL | | | BARS NOT ACCEPTABLE.SEE SHT.A-3.9. | | | | | | EQUIVALENT FACILITATION SHALL BE | | | PROVIDED PER FACBC SEC.9.1.4. | | | ACCESSIBLE ROOMS SHALL BE EVENLY DIS- | | | PERSED. | | | | | | TOILETS IN ALL ACCESSIBLE ROOMS SHALL BE | | | PROVIDED W/A PORTABLE OR ATTACHED SEAT | | | PER FACBC SEC.9.2.3. | | | | | | KITCHENS,KITCHENETTES,OR WET BARS IN | | | SLEEPING UNITS SHALL COMPLY W/FACBC SEC. | | | 9.2.2.(7) | | | | | | SHT.A-4.1-FLOOR DRAIN SHOWN UNDER ICE | | | MACHINE-INLET SHALL BE IN FULL VIEW PER | | | SPC SEC.409.4.1.2. | | | | | | SHT.A-8.4-DETAIL #6-CLEAR FLOOR SPACE | | | SHALL BE PROVIDED FOR SINK AND SHALL BE | | | CENTERED ON THE FIXTURE AND COMPLY W/ | | | FACBC SEC.4.24.1-4.24.7. | | | | | | GUEST LAUNDRY SHALL COMPLY W/FACBC SEC. | | | 9.1.1. | | | | | | WALLS AND FLOOR IN EMPLOYEE TOILET SHALL | | | BE NONABSORBENT TO A HEIGHT OF 4' PER | | | SBC SEC.1204.2. | | | | | | SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT. | | | EQUIPMENT SHALL BE LISTED PER SGC SEC. | | | 402.1 | | | | | | SUBMIT COMPLETE GAS DRAWING FOR REVIEW. | | | SHOW TYPE OF PIPING,SIZES,BTU RATING OF | | | EACH APPLIANCE,ETC.COMPLY W/SGC CHAPTS. | | | 3-6 & NFPA 54,58.INCLUDE CALCULATIONS | | | FOR COMBUSTION AIR. | | | | | | MAX.TEMP.TO PUBLIC RESTROOMS SHALL NOT | | | EXCEED 110 DEG.PER FLA.ENERGY CODE SEC. | | | 412.1.ABCD.2.3.2. | | | | | | SHT.P-1.1.-REMOVE VACUUM BREAKERS FROM | | | WASHING MACHINE. | | | | | | SEE PLUMBING PLAN REVIEW STEP #2 FOR | | | CONTINUATION OF PLUMBING COMMENTS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-19 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE APPROVAL ON NEW SITE PLAN |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-05-26 |
Time |
15:12 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|