Plan Review Details - Permit 00030111
Plan Review Stops For Permit 00030111
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-08 Cont ID  
Sent By lmartine Date 2000-03-08 Time 07:22 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-09 Cont ID  
Sent By dpalmer Date 2000-03-09 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2000-03-09 Time 11:32 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: NEED TO SHOW ALL BRANCH CIRCUT
 #`S ON PLANS FOR OUTLETS AND LIGHTING.
  
 2)NOTE:PANEL SCHEDULE REFLECT ONLY ONE
 CIRCUT FOR LIGHTING AND OUTLETS.
 PLEASE CORRECT FOR THE PROPER AMOUNT OF
 CIRCUTS REQ`D.
  
 3)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. PER 110-9/110-10
  
 PROVIDE THE ABOVE INFORMATION BEFORE
 ROUGH.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By lmartine Date 2000-03-03 Time 07:24 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-03-06 Cont ID  
Sent By tlarge Date 2000-03-06 Time 09:17 Rev Time 0.33
Received By tlarge Date 2000-03-06 Time 09:17 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A)-PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 LAVATORY IN WOMEN'S RESTROOM SHALL
 COMPLY W/FACBC SEC.4.19.2.(MIN.29" REQD.
 UNDER LAV.TO FINISH FLOOR).
  
 WATER CLOSETS NOT PERMITTED ON WET VENT.
 COUNTYWIDE AMENDMENT TO SPC SEC.104.2.1.
  
 DOOR TO WASHER/DRYER SHALL COMPLY W/
 FACBC SEC.4.13.5.
  
 SUBMIT WATER RISER DIAGRAM FOR REVIEW
 PRIOR TO TOP OUT INSP.

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-03-06 Cont ID  
Sent By tlarge Date 2000-03-05 Time 12:57 Rev Time 0.30
Received By tlarge Date 2000-03-05 Time 12:57 Sent To  
Notes
2001-01-08 00:00:00HANDICAP DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A).
  
 LAVATORY IN WOMEN'S H.C. TOILET ROOM
 SHALL COMPLY W/FACBC SEC.4.19.2.(MIN.29"
 REQD.UNDER LAV.SUBMIT DETAIL.)
  
 DOOR OPENING TO WASHER/DRYER SHALL
 COMPLY W/FACBC SEC.4.1.6(A)(B)
  
 ONE MAIN VENT THRU ROOF REQD.PER SPC
 904.3.
  
 WATER CLOSETS NOT PERMITTED ON HORIZ.
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1
  
 SUBMIT WATER RISER DIAGRAM FOR REVIEW.
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-03-06 Cont ID  
Sent By pschmitz Date 2000-03-03 Time 09:52 Rev Time 0.50
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE STEP#2 FOR COMMENTS.