Plan Review Details - Permit 00030042
Plan Review Stops For Permit 00030042
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-17 Cont ID  
Sent By lmartine Date 2000-04-17 Time 14:53 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-10 Cont ID  
Sent By dpalmer Date 2000-07-10 Time 10:59 Rev Time 0.00
Received By dpalmer Date 2000-07-10 Time 10:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-15 Cont ID  
Sent By dpalmer Date 2000-03-15 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2000-03-15 Time 07:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By lmartine Date 2000-03-03 Time 07:33 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-06-12 Cont ID  
Sent By cthirben Date 2000-06-12 Time 09:55 Rev Time 0.00
Received By cthirben Date 2000-06-12 Time 09:59 Sent To  
Notes
2001-01-08 00:00:00NOTES **********************************
 FAN SHUT DOWN TO BE TIED IN TO THE FIRE
 ALARM SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-23 Cont ID  
Sent By ndenmark Date 2000-03-23 Time 08:04 Rev Time 0.33
Received By ndenmark Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE CFM INFORMATION FOR DROP IN
 MRI ROOM AND FOR GE EQUIPMENT ROOM PRIOR
 TO 1ST INSPECTION
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR EQUIPMENT WITH THE CAPACITY
 GREATER THAN 2000 CFM WITH NOTIFICATION
 BY HORN AND STROBE OR TIED TO BLDG FIRE
 ALARM PER NFPA 90A 4-4.4.2 (OR.3)

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 09:41 Rev Time 0.33
Received By tlarge Date 2000-07-12 Time 09:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-07-11 Cont ID  
Sent By tlarge Date 2000-07-11 Time 16:20 Rev Time 0.50
Received By tlarge Date 2000-07-11 Time 16:20 Sent To  
Notes
2001-01-08 00:00:00SHOW LOCATION OF DRINKING FOUNTAIN ON
 PLANS.COMPLY W/FACBC SEC.4.1.3.(10)(A).
  
 FLOOR DRAIN W/TRAP PRIMER IS REQD.IN THE
 TOILET ROOM PER SPC SEC.409.4.1.1.
  
 SINK AND COUNTER IN BREAK ROOM SHALL
 COMPLY W/FACBC SEC.4.24.1-4.24.7.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-29 Cont ID  
Sent By tlarge Date 2000-04-29 Time 10:52 Rev Time 0.75
Received By tlarge Date 2000-04-29 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-09 Cont ID  
Sent By tlarge Date 2000-03-09 Time 10:53 Rev Time 0.00
Received By tlarge Date 2000-03-09 Time 10:53 Sent To  
Notes
2001-01-08 00:00:00SUBMIT WATER RISER FOR REVIEW.WATER
 SUPPLY CONTROL SHALL COMPLY W/SPC SEC.
 610.4.1,610.4.2.
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A)(PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING).
  
 A FLOOR DRAIN IS REQD.IN THE TOILET ROOM
 PER SPC SEC.409.4.1.1(SEE EXCEPTION).
  
 BREAK ROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.CLEAR FLOOR SPACE
 SHALL BE CENTERED ON THE SINK.
  
 WATER CLOSET SHALL BE 18" FROM WALL PER
 FACBC FIGURE 28.