Plan Review Details - Permit 00021287
Plan Review Stops For Permit 00021287
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-11 Cont ID  
Sent By dpalmer Date 2000-09-11 Time 12:51 Rev Time 0.00
Received By dpalmer Date 2000-09-11 Time 12:51 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SEE THAT NOT ALL OF THE
 NOTES WERE ADDRESSED FROM THE FIRST
 REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THER ARE ANY QUESTIONS
 PLEASE CALL!!
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-14 Cont ID  
Sent By dpalmer Date 2000-03-14 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2000-03-14 Time 17:52 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PERMIT APPLICATION SHOWS YOU
 CHANGING THE SERVICE??? NEED TO SEE
 ELECTRICAL RISER DIAGRAM, SHOWING SIZE
 OF EQUIPMENT, WIRES, CONDUITS, AND
 SUBMIT AIC RATING OF EQUIPMENT MAINS.
 ALL REQ`D BY 215-5/110-9
  
 2)NOTE: PLEASE NOTE SMOKE DETECTORS REQ`
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 OF YOUR NEW CONSTRUCTION.
  
 3)NOTE; PLEASE SHOW ON PANEL SCHEDULE
 THE REQ`D CIRCUTS FOR BATH(S)210-11-C-3
  
 4)NOTE:IF THERE ARE GOOING TO BE MORE
 THAN ONE CITCUT IN SHED, THEN YOU NEED
 DISCONNECT AT THAT STRUCTURE. IF ONLY
 ONE CIRCUT THEN IT MUST BE GFI. PER
 225-30-B-2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-03-30 Cont ID  
Sent By rmcdouga Date 2001-03-30 Time 12:38 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-30 00:00:00PERMIT VOIDED OWNER INSTALLING WINDOW
 UNITS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-09-14 Cont ID  
Sent By ndenmark Date 2000-09-14 Time 09:59 Rev Time 0.25
Received By ndenmark Date 2000-09-14 Time 09:59 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 NO MECHANICAL INFORMATION PROVIDED FOR
 REVIEW. PROVIDE PLANS AND INFORMATION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-03-15 Cont ID  
Sent By cthirben Date 2000-03-15 Time 16:09 Rev Time 1.00
Received By cthirben Date 2000-03-15 Time 16:05 Sent To  
Notes
2001-01-08 00:00:00 
 *****************DENIED*****************
 1. EXHAUST FAN OR 3'SQ. WINDOW NEEDS TO
 BE INSTALLED IN BATHROOM SMC 503.3.1
  
 2. NO A/C PLANS WAS SUBMITTED FOR REVIEW

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-30 Cont ID  
Sent By rmcdouga Date 2001-03-30 Time 12:35 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-15 Cont ID  
Sent By tlarge Date 2000-03-15 Time 06:07 Rev Time 0.00
Received By pschmitz Date 2000-09-16 Time 13:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-03-30 Cont ID  
Sent By rmcdouga Date 2001-03-30 Time 12:05 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-09-20 Cont ID  
Sent By rmcdouga Date 2000-09-20 Time 07:29 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR EACH
 SPECIFIC TYPE OF EXTRIOR WINDOW OR DOOR
 TO BE USED. INCLUDING ARCHED WINDOWS
 SHOWN ON PLANS.
  
 2)PROVIDE EGRESS WINDOW IN BEDROOM.
 97 SBC 1005.4
  
 3)PROVIDE WINDOW SIZES AND TYPES (SINGLE
 HUNG,AWNING,ETC.)FOR ALL NEW WINDOWS.
  
 4)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS, KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS.
 MISSLE IMPACT PROTECTION IS REQUIRED FOR
 ALL EXTERIOR GLAZING. CITY OF WPB
 AMENDMENTS TO 97 SBC.
  
 5)PROVIDE ATTIC ACCESS PER 97 SBC 2309.6
  
 6)PROVIDE ATTIC VENTIATION.97 SBC 2309.7
  
 7)PROVIDE WALL SECTION AND CONSTRUCTION
 DETAILS FOR EXISTING CARPORT THAT IS
 BEING ENCLOSED.
  
 8)PROVIDE ENERGY CALCULATIONS INCLUDING
 MANUAL "J" CALCS. PER 79 FL. ENERGY
 EFFICIENCY CODE.
  
 9)CONNECTOR LSTA 18 SHOWN ON PLANS
 ATTACHING TRUSSES TO WALL IS AN IMPROPER
 APPLICATION. USE SIMPSON MTS-12,H6 OR
 EQUAL.
  
 10)PROVIDE SOIL COMPACTION TEST AT TIME
 OF FIRST INSPECTION.
  
 11)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY,PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY BLDG.
 DEPT. BEFORE A PERMIT TO CONSTRUCT WILL
 BE ISSUED.
  
 12)PROVIDE POSITIVE AND NEGATIVE WIND-
 LOAD PRESSURES FOR EXTERIOR WINDOW AND
 DOOR OPENINGS.
  
 13)PROVIDE FRAMING DETAILS FOR ARCHED
 WINDOWS SHOWN ON PLANS.
  
 14)PLEASE RECHECK DISTANCE BETWEEN SHED
 AND BED ROOM. FOUNDATION PLAN HAS 4'-0"
 AND DIMENSION ON SURVEY IS 2.9'
 (18.9'-16.0'=2.9')

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-24 Cont ID  
Sent By lsmith Date 2000-03-24 Time 11:34 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED PRODUCT APPROVALS WINDOWS, DOORS
 AND ROOF.
 NEED SEALED ENGINEERED DRAWINGS TRUSSES
 CURRENT SBCCI CODE IS 1997 PLANS SHOW
 1994

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-29 Cont ID  
Sent By gjoyce Date 2000-02-29 Time 10:46 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***