| Plan Review Stops For Permit 00021256 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-21 |
Time |
15:17 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-01-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-02 |
Time |
12:49 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW | | | 1). FLORIDA ENERGY CODE 400.ABCD.2 CODE | | | COMPLIANCE CERTIFICATION- THE BUILDING'S | | | OWNER, THE OWNER'S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY | | | THE OWNER SHALL CERTIFY TO THE BUILDING | | | OFFICIAL THAT THE BUILDING IS IN COMPLI- | | | ANCE WITH THE ENERGY EFFICIENCY CODE FOR | | | BUILDING CONSTRUCTION PRIOR TO RECEIVING | | | THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | 2). FL. ACCESSIBLITY CODE- 4.11 THE COR- | | | RECT ASME A17.1 IS GIVEN BUT THERE WAS | | | NO SHOP DRAWINGS OR CUT SHEETS ATTACHED. | | | 3).SBC 1606.4.1/ 1707.4.1- GLAZED OPEN- | | | INGS REQUIRE LARGE MISSLE IMPACT RESIS- | | | TANCE TESTING. THE DADE COUNTY PRODUCT | | | APPROVAL # 96-0119.07 DOESN'T HAVE A | | | EXPIRATION DATE, NOR DOES IT HAVE | | | DRAWINGS THAT ACCOMPANY THE REPORT. | | | THE ADDITIONAL SHEETS FOR APPROVED PRO- | | | DUCT APPROVAL SHOW THAT # 96-12.07 IS A | | | EXPIRED REPORT. | | | 4). BEFOR THE PERMIT TO CONSTRUCT CAN | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY, THE PERMIT PLANS | | | STAMED BY THAT OFFICE AND A COPY OF THE | | | RECEIPT ATTACHED TO THE PERMIT APPLICAT- | | | ION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-09-06 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTERS ATTACHED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-07-05 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-04-04 |
Time |
10:37 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-07 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-07 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-04-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-19 |
Time |
19:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-19 |
Time |
19:28 |
Sent To |
|
|
| Notes |
| 2001-04-19 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT TWO COPIES OF P | | | LANS NEED TO BE SUBMITTED. | | | | | | 2)NOTE: PLEASE NOTE THAT ALL PLANS THAT | | | ARESIGNED BY ARCH/ENGINEER NEED TO BE | | | ORIGINAL PER F.A.C 471.025/481.221 | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-30 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-08-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-08-23 |
Time |
15:21 |
Rev Time |
2.00 |
| Received By |
jleahy |
Date |
2000-08-23 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1-STILL NEED TO GIVE A LOAD CALCULATION | | | FOR ADDITIONAL LOADS ON AN EXISTING | | | SERVICE.SEE SECTION 220-35 OR ALL TH | | | INDIVIDUAL CALCULATIONS SHOWN IN 220!! | | | MOTOR CONTRIBUTION, CONTINUOUS LOAD | | | FACTORS ECT. ECT. ECT. | | | | | | 2-SEE ORIGINAL COMMENTS FROM LAST REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-22 |
Time |
20:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-08-23 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: LOAD CALCULATIONS AT THE BOTTOM | | | OF EACH PANEL ARE NOT COMPLETE? PLEASE | | | SHOW ALL CONTIUOUS LOADS AT 125%. | | | LARGEST MOTORS/LIGHTING ETC. | | | | | | 2)NOTE: PLEASE SUBMIT FINAL LOAD CALC | | | FOR MAIN SERVICE. NEW EQUIPMENT/LOADS | | | ARE BEING ADDED TO EXISTING SERVICE. | | | | | | | | | 3)NOTE: SEE PANELBOARD 'HPM'. THIS IS | | | LISTING A 14,000 AIC RATING? PLEASE | | | CLARIFY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-03-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-25 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-25 |
Time |
14:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-08-22 |
Time |
14:47 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED WITH PROVISO | | | PLANS REVIEWED SHOW NO MODIFICATION TO | | | EXISTING PARKING, WATER, SANITARY SEWER | | | SERVICE. | | | THE PLANS DO REFLECT AN ADDITION IN | | | BUILDING SQUARE FEET. | | | OUR DEPARTMENT WILL REQUIRE | | | TOTAL PERVIOUS AND IMPERVIOUS CALCULATIO | | | NS TO CALCULATE NEW STORM WATER CHARGES. | | | PLEASE LIST BUILDING S.F. , SIDEWALK AND | | | ROADWAYS S.F. AND GREEN AREAS. | | | THE TOTAL TO THESE SHALL CONPUTE TO 100% | | | OF THE SITE S.F. | | | PLEASE LIST THEM IN S.F. AND ACRES. | | | PLEASE LIST THE OWNER NAME, THE ADDRESS, | | | THE PROPERTY CONTROL NUMBER. THIS INFO | | | CAN BE SUBMITTED TO MANNY GONZALEZ | | | PROJECT SPECIALIST BY FAX OR MAIL. | | | PUBLIC UTILITIES ENGINEERING DEPT. | | | 1000 45TH ST, WPB FL 33407 SUITE 15 | | | 561 659 8040 OR FAX 561 659 8039 | | | HAVE A GREAT DAY!! |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-09 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-09 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | 1) ON MAY 9, 2001, THIS WRITER SPOKE | | | WITH MR. PAT FPERDUTO OF CHANCE | | | CONSTRUCTION. HE ANSWERED ALL PLAN | | | REVIEW COMMENTS THAT WERE MADE ON | | | 5/01/01 BY THIS OFFICE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2001-05-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-01 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-01 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2001-05-01 00:00:00 | 1) PLEASE DESCRIBE CONSTRUCTION OF | | | NEW CANOPY. | | | 2) PLEASE IDENTIFY ALL ILLUMINATED | | | EXIT SIGN LOCATIONS. | | | 3) PLEASE PROVIDE OCCUPANT CALCULATIONS | | | AND IDENTIFY ALL EXIT LOCATIONS. | | | 4) IF THERE ARE POWER OPERATED EXIT | | | DOORS, THEY MUST COMPLY WITH NFPA 101, | | | THE LIFE SAFETY CODE, 1985 EDITION, | | | SECTION 5-2.1.9. | | | 5) IS THE HOOD OVER THE ROTISSERIE NEW | | | OR EXISTING. IF THE HOOD IS NEW, | | | SEPARATE PLANS AND PERMITS ARE REQUIRED | | | FOR THE HOOD,DUCT,AND EXTINGUISHING | | | SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-01-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-08 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-08 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE SUBMIT SHOP DRAWINGS FOR ANY | | | FIRE ALARM SYSTEM MODIFICATIONS MADE TO | | | THE EXISTING SYSTEM. SEPARATE PLAN AND | | | PERMIT REQUIRED PRIOR TO INSTALLATION. | | | 2) PLEASE SUBMIT SHOP DRAWINGS FOR FIRE | | | SPRINKLER SYSTEM MODIFICATIONS MADE TO | | | THE EXISTING SYSTEM. SEPARATE PLAN AND | | | PERMIT REQUIRED PRIOR TO INSTALLATION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-21 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-06-19 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-06-19 |
Time |
13:54 |
Rev Time |
1.00 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE FIRE SPRINKLER DRAWINGS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-04-04 |
Time |
15:26 |
Rev Time |
0.45 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE SHOP DRAWINGS FOR FIRE ALARM | | | SYSTEM REMODEL. FIRE ALARM SHALL REMAIN | | | OPERABLE DURING CONSTRUCTION PERIOD | | | | | | REQUIRED EXITING SHALL REMAIN DURING | | | CONSTRUCTION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-05 |
Time |
09:56 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-09-05 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION M-5 SHOWS DUCT SMOKE DETECTOR | | | CONNECTED AS REQUIRED BY CODE ADDED TO | | | SET |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-07-12 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-07-12 |
Time |
14:02 |
Rev Time |
0.10 |
| Received By |
ndenmark |
Date |
2000-07-12 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-22 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-03-22 |
Time |
13:44 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-03-22 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | | | | DUCT SMOKE DETECTORS TO BE TIED TO BUILD | | | ING FIRE ALARM SYSTEM PER NFPA 90A 4-4.4 | | | .3 FOR NOTIFICATION |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2001-01-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-05 |
Time |
11:09 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
2001-01-05 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2000-09-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-10 |
Time |
06:21 |
Rev Time |
1.25 |
| Received By |
pschmitz |
Date |
2000-09-10 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)THE TOILET ROOM IN THE TMA SHOW ROOM | | | AND THE RECEIVING TOILET ROOM SHALL BE | | | HANDICAP ACCESSIBLEPER FACBC SEC.4.1.3 | | | (11).CLEARLY SHOW COMPLIANCE ON THE | | | PLANS.SHOW GRAB BAR HEIGHT,HEIGHT OF | | | FIXTURES,CLEARANCES,ETC. | | | | | | 2)CONTACT R.COMPO W/CITY OF WEST PALM | | | BEACH WASTEWATER TREATMENT FACILITY | | | REGARDING EFFLUENT FROM FILM PROCESSOR. | | | SUBMIT APPROVAL FROM R.COMPO FOR | | | SYSTEM W/O NEUTRALIZATION TANK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-08-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-23 |
Time |
13:35 |
Rev Time |
6.00 |
| Received By |
pschmitz |
Date |
2000-08-23 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)THE TOILET ROOM IN THE TMA SHOW ROOM | | | AND THE RECEIVING TOILET ROOM SHALL BE | | | HANDICAP ACCESSIBLE PER FACBC SEC. | | | 4.1.3(11).CLEARLY SHOW COMPLIANCE ON THE | | | PLANS.SHOW GRAB BAR HEIGHT,LOCATION, | | | HEIGHT OF FIXTURES,CLEARANCES,ETC. | | | COMPLY W/FACBC OCT.1997 ED. | | | | | | 2)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC SEC610.4.2. | | | | | | 3)SIZE ALL WASTE,VENT AND WATER LINES ON | | | THE DIAGRAM.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 4)INDIRECT WASTES SHALL DISCHARGE INTO | | | A FLOOR SINK,NOT FLOOR DRAIN.SPC SEC. | | | 807.1. | | | | | | 5)A CHECK AND GATE VALVE ARE REQD.ON THE | | | SUMPS DISCHARGE PER SPC SEC.717.2.SUMPS | | | SHALL BE VENTED PER 717.6.CONNECTION TO | | | DRAINAGE SYSTEM SHALL COMPLY W/SPC SEC. | | | 717.11. | | | | | | 6)FLOOR DRAINS SHALL BE IN FULL VIEW AT | | | ALL TIMES PER SPC SEC.409.4.1.2. | | | | | | 7)CONTACT R.COMPO W/CITY OF WPB CENTRAL | | | WASTEWATER TREATMENT FACILITY REGARDING | | | EFFLUENT FROM FILM PROCESSOR.SUBMIT | | | APPROVAL OF SYSTEM W/O NEUTRALIZATION | | | TANK FROM R.COMPO. | | | | | | 8)PHOTOLAB RISER-FIXTURES SHALL BE | | | VENTED PER SPC 717.4. | | | | | | 9)AN AIR GAP IS REQD.ON THE RTU COND. | | | DRAIN PIPING PER SPC SEC.806. | | | | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-06 |
Time |
14:25 |
Rev Time |
3.50 |
| Received By |
pschmitz |
Date |
2000-06-06 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COMPLY W/ALL PREVIOUS COMMENTS DATED | | | 3/5/00 & 5/1/00. | | | | | | SHT.CV-1-"BUILDING CODES"-INSERT CORRECT | | | EDITION OF THE APPLICABLE STANDARD | | | BUILDING CODES.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.101.1 AND FLA.STATUTE. | | | | | | CLEARLY SHOW TERMINATION POINT OF CON- | | | DENSATE DRAINS ON ROOF.DRAINS SHALL NOT | | | DISCHARGE WHERE THE EFFLUENT CAN DRAIN | | | INTO A STREET,ALLEY OR OTHER AREAS | | | THAT WOULD CREATE A NUISANCE /MENACE. | | | SMC SEC.304.8.3(3). | | | | | | SHT.P1-EYEWASH SHALL DRAIN TO SANITARY | | | NOT DISCHARGE ONTO GROUND.SPC SEC.301.4, | | | 301.11.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-05-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-01 |
Time |
11:03 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-05-01 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COMPLY W/ALL PREVIOUS COMMENTS DATED | | | 3/5/00. | | | | | | SHT.M-4-DETAIL #4-SUPPLY AIR GAP ON | | | CONDENSATE DRAIN PER SPC SEC.806. | | | | | | SUBMIT INFO ON PURITAN CHEMICAL STATIONS | | | AS NOTED ON PLANS.COUNTYWIDE AMENDMENTS | | | TO SPC.SEC.104.2.1. | | | | | | EYEWASH DRAIN CANNOT DISCHARGE INTO | | | FLOOR DRAIN IN TMA TOILET ROOM PER SPC | | | SEC.807.1.1. | | | | | | RELIEF LINES FROM WATER HEATERS SHALL | | | DISCHARGE TO EXTERIOR PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.507.6.1.SEE SHT. | | | P-3,DETAIL#3 ALSO. | | | | | | SUMP DISCHARGE PIPING SHALL CONNECT TO | | | SANITARY SYSTEM PER SPC SEC.717.11. | | | (SUMPS AND ASSOCIATED PIPING SHALL | | | COMPLY W/SPC SECS.717.1-717.11.) | | | | | | SUMP PIPING CONNECTION FROM VISION AND | | | PHOTO AREAS TO SNACK BAR PIPING NOT | | | SHOWN PLANS..COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1. | | | | | | SINKS AT VISION CENTER SHALL BE PROPERLY | | | VENTED PER SPC SEC.901.2. | | | | | | GREASE RECOVERY UNITS ARE NOT PERMITTED | | | PER CITY OF WPB ORDINANCE. | | | | | | SHT.P-4-DETAIL#8-DRAINS CANNOT BE | | | REDUCED IN SIZE PER SPC SEC.709.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-03-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-05 |
Time |
10:02 |
Rev Time |
5.50 |
| Received By |
tlarge |
Date |
2000-03-05 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *******CONTINUATION OF PLBG.COMMENTS**** | | | 24)POT/SCULLERY SINKS SHALL BE STACKED | | | AND VENTED PER SPC SEC.804.1. | | | | | | 25)HEATER P& T LINE SHALL DISCHARGE TO | | | AN OBSERVABLE POINT PER COUNTYWIDE AMEND | | | MENTS TO SPC SEC.507.8.4. | | | | | | 26)SUBMIT WATER PIPING/DRAINAGE DETAILS | | | FOR ROTISSERIE AREA AND SUMP PUMP AT | | | TRUCK DOCK. | | | | | | 27)SIZE ALL SECTIONS OF THE COMPRESSED | | | AIR SYSTEM. | | | | | | 28)WATER FILTRATION SYSTEM SHALL BE NSF | | | APPROVED PER SPC SEC.615.1,615.2.SUBMIT | | | DATA. | | | | | | 29)SHT.P-4-SIZE AND DESIGN OF GREASE | | | TRAP SHALL BE APPROVED BY CITY OF WEST | | | PALM BEACH UTILITIES.CONTACT R.COMPO AT | | | (561)835-7423. | | | | | | 30)SHT.P-3-DETAILS #8,11,ET.AL.-LOCATION | | | OF FLOOR DRAINS SHALL COMPLY W/SPC SEC. | | | 409.4.1.2. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-03-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-05 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-03-05 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | JOB SPEC.15050-SEC.3.02(I)-VERTICAL AND | | | HORIZONTAL SPACING OF PIPE SUPPORTS | | | SHALL COMPLY W/SPC SECS.310.2,310.3 | | | RESPECTIVELY. | | | | | | 2)JOB SPEC.15400-SEC.2.01(D)-PIPING | | | INSULATION SHALL COMPLY W/FLA.ENERGY | | | CODE TABLE 4-11. | | | | | | 3)JOB SPEC.15400-SEC.2.15-GREASE | | | RECOVERY UNITS NOT PERMITTTED PER CITY | | | ORDINANCE. | | | | | | 4)JOB SPEC.15400-SEC.3.01(A)-SLOPE OF | | | DRAINAGE PIPE SHALL COMPLY W/SPC SEC. | | | 705.2,705.3.9(SEE SHT.P1,NOTE #3 ALSO) | | | | | | 5)SHT.CV1-THE CURRENT ADOPTED PLUMBING | | | CODE IN THE CITY OF WEST PALM BEACH IS | | | THE 1994 EDITION OF THE STANDARD | | | PLUMBING,NOT 1997. | | | | | | 6)THE MINIMUM NUMBER OF SANITARY FACIL- | | | ITIES REQD.BY 1994 PLBG.CODE IS : | | | MALES]-WATERCLOSETS-5 | | | -LAVATORIES_____5 | | | FEMALES]-WATER CLOSETS-9 | | | -LAVATORIES____9 | | | -DRINKING FOUNTAINS-4 | | | SEE SPC CODE SEC.407.1.3 & TABLE 407. | | | | | | 7)ALL COMMON AND PUBLIC AREA TOILET | | | ROOMS SHALL COMPLY W/FACBC SEC.4.1.3(11) | | | | | | 8)SHT.A-4-TOP OF H.C.LAV.AFF SHALL BE | | | 34" PER FACBC SEC.4.19.2. | | | | | | 9)SHT.A-5-DRINKING FOUNTAIN IN TMA SHALL | | | BE H.C.ACCESSIBLE AND COMPLY W/FACBC | | | SEC.4.1.3.(10)(A). | | | | | | 10)TOILET ROOM IN TMA SHOWROOM SHALL BE | | | HANDICAP ACCESSIBLE PER FACBC SEC.4.1.3. | | | (11) | | | | | | 11)SUBMIT WATER PIPING AND DRAINAGE | | | DETAILS FOR RACK WASHER. | | | | | | 12)WATER HEATER SHALL BE READILY ACCESS- | | | IBLE.PROVIDE PERMANENT LADDER OR RE- | | | LOCATE TO FLOOR.SPC 501.7. | | | | | | 13)CLEARLY SHOW TYPE OF FINISH ON REST- | | | ROOM WALLS.COMPLY W/SBC SEC.1204.2(NON- | | | ABSORBENT TO A HEIGHT OF 4'.) | | | | | | 14)SUBMIT MANUF.SHEETS FOR FILM PROCESS- | | | OR AND SILVER RECOVERY UNIT.WASTE SHALL | | | BE NEUTRALIZED PER SPC SEC.801.4.DATA | | | SHOWING ESTIMATED PH OF EFFLUENT SHALL | | | BE SUBMITTED FOR REVIEW. | | | | | | 15)SINK IN EMPLOYEE LOUNGE SHALL BE H.C. | | | ACCESSIBLE AND COMPLY W/FACBC SEC.4.24.1 | | | THRU 4.24.7. | | | | | | 16)SUBMIT WASTE AND WATER RISER FOR SINK | | | IN EMPLOYEE LOUNGE ,RM.112.LINE SHALL | | | DRAIN TO SANITARY PER SPC 1004.3. | | | | | | 17)WATER SUPPLY CONTROL FOR ALL AREAS | | | SHALL COMPLY W/SPC SEC.610.4.1.,610.4.2. | | | | | | 18)SIZE ALL WASTE,VENT AND WATER LINES | | | ON THE RISER DIAGRAMS.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | 19)HAND SINKS,SERVICE SINKS,FLOOR DRAINS | | | AND SIMILAR FIXTURES IN THE FOOD/SNACK | | | BAR AREAS SHALL DISCHARGE THROUGH THE | | | GREASE INTERCEPTOR PER SPC SEC.1004.4. | | | | | | 20)INDIRECT WASTE LINES SHALL COMPLY W/ | | | SPC SEC.805.1.1,805.2. | | | | | | 21)FLOOR DRAINS NOT SUPPLIED W/INDIRECT | | | WASTES SHALL BE EQUIPPED W/TRAP PRIMERS | | | PER SPC SEC.409.4.1.1. | | | | | | 22)SUBMIT COMPLETE GAS DRAWING FOR | | | REVIEW.SHOW MOST REMOTE OUTLET,CUT | | | SECTIONS OF PIPE,BTU LOAD OF EACH PIECE | | | OF EQUIP.ALL EQUIPMENT SHALL BE LISTED/ | | | APPROVED PER SGC SEC.402.1 AND NFPA 54. | | | SUBMIT MANUF. SHEETS FOR ALL GAS EQUIP. | | | | | | 23)SUMPS SHALL COMPLY W/SPC SEC.717.SUB- | | | MIT DETAILS ON SUMP CONSTRUCTION,PUMPS | | | ETSC.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-02-21 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-21 00:00:00 | APPROVED BY ERIC SNYDER 2/20/01 |
|
|