Plan Review Details - Permit 00021256
Plan Review Stops For Permit 00021256
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-02-21 Cont ID  
Sent By jwitmer Date 2001-02-21 Time 15:17 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-01-02 Cont ID  
Sent By jwitmer Date 2001-01-02 Time 12:49 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW
 1). FLORIDA ENERGY CODE 400.ABCD.2 CODE
 COMPLIANCE CERTIFICATION- THE BUILDING'S
 OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER SHALL CERTIFY TO THE BUILDING
 OFFICIAL THAT THE BUILDING IS IN COMPLI-
 ANCE WITH THE ENERGY EFFICIENCY CODE FOR
 BUILDING CONSTRUCTION PRIOR TO RECEIVING
 THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
 2). FL. ACCESSIBLITY CODE- 4.11 THE COR-
 RECT ASME A17.1 IS GIVEN BUT THERE WAS
 NO SHOP DRAWINGS OR CUT SHEETS ATTACHED.
 3).SBC 1606.4.1/ 1707.4.1- GLAZED OPEN-
 INGS REQUIRE LARGE MISSLE IMPACT RESIS-
 TANCE TESTING. THE DADE COUNTY PRODUCT
 APPROVAL # 96-0119.07 DOESN'T HAVE A
 EXPIRATION DATE, NOR DOES IT HAVE
 DRAWINGS THAT ACCOMPANY THE REPORT.
 THE ADDITIONAL SHEETS FOR APPROVED PRO-
 DUCT APPROVAL SHOW THAT # 96-12.07 IS A
 EXPIRED REPORT.
 4). BEFOR THE PERMIT TO CONSTRUCT CAN
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMED BY THAT OFFICE AND A COPY OF THE
 RECEIPT ATTACHED TO THE PERMIT APPLICAT-
 ION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-09-06 Cont ID  
Sent By hpiskura Date 2000-09-06 Time 10:42 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTERS ATTACHED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-05 Cont ID  
Sent By hpiskura Date 2000-07-05 Time 10:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By hpiskura Date 2000-04-04 Time 10:37 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-05-07 Cont ID  
Sent By dpalmer Date 2001-05-07 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2001-05-07 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-04-19 Cont ID  
Sent By dpalmer Date 2001-04-19 Time 19:28 Rev Time 0.00
Received By dpalmer Date 2001-04-19 Time 19:28 Sent To  
Notes
2001-04-19 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT TWO COPIES OF P
 LANS NEED TO BE SUBMITTED.
  
 2)NOTE: PLEASE NOTE THAT ALL PLANS THAT
 ARESIGNED BY ARCH/ENGINEER NEED TO BE
 ORIGINAL PER F.A.C 471.025/481.221
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 17:07 Rev Time 0.00
Received By dpalmer Date 2000-08-30 Time 17:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-08-23 Cont ID  
Sent By jleahy Date 2000-08-23 Time 15:21 Rev Time 2.00
Received By jleahy Date 2000-08-23 Time 15:16 Sent To  
Notes
2001-01-08 00:00:001-STILL NEED TO GIVE A LOAD CALCULATION
 FOR ADDITIONAL LOADS ON AN EXISTING
 SERVICE.SEE SECTION 220-35 OR ALL TH
 INDIVIDUAL CALCULATIONS SHOWN IN 220!!
 MOTOR CONTRIBUTION, CONTINUOUS LOAD
 FACTORS ECT. ECT. ECT.
  
 2-SEE ORIGINAL COMMENTS FROM LAST REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-06-22 Cont ID  
Sent By dpalmer Date 2000-06-22 Time 20:24 Rev Time 0.00
Received By jleahy Date 2000-08-23 Time 15:12 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: LOAD CALCULATIONS AT THE BOTTOM
 OF EACH PANEL ARE NOT COMPLETE? PLEASE
 SHOW ALL CONTIUOUS LOADS AT 125%.
 LARGEST MOTORS/LIGHTING ETC.
  
 2)NOTE: PLEASE SUBMIT FINAL LOAD CALC
 FOR MAIN SERVICE. NEW EQUIPMENT/LOADS
 ARE BEING ADDED TO EXISTING SERVICE.
  
  
 3)NOTE: SEE PANELBOARD 'HPM'. THIS IS
 LISTING A 14,000 AIC RATING? PLEASE
 CLARIFY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 14:24 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 14:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-22 Cont ID  
Sent By mgonzale Date 2000-08-22 Time 14:47 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISO
 PLANS REVIEWED SHOW NO MODIFICATION TO
 EXISTING PARKING, WATER, SANITARY SEWER
 SERVICE.
 THE PLANS DO REFLECT AN ADDITION IN
 BUILDING SQUARE FEET.
 OUR DEPARTMENT WILL REQUIRE
 TOTAL PERVIOUS AND IMPERVIOUS CALCULATIO
 NS TO CALCULATE NEW STORM WATER CHARGES.
 PLEASE LIST BUILDING S.F. , SIDEWALK AND
 ROADWAYS S.F. AND GREEN AREAS.
 THE TOTAL TO THESE SHALL CONPUTE TO 100%
 OF THE SITE S.F.
 PLEASE LIST THEM IN S.F. AND ACRES.
 PLEASE LIST THE OWNER NAME, THE ADDRESS,
 THE PROPERTY CONTROL NUMBER. THIS INFO
 CAN BE SUBMITTED TO MANNY GONZALEZ
 PROJECT SPECIALIST BY FAX OR MAIL.
 PUBLIC UTILITIES ENGINEERING DEPT.
 1000 45TH ST, WPB FL 33407 SUITE 15
 561 659 8040 OR FAX 561 659 8039
 HAVE A GREAT DAY!!

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-05-09 Cont ID  
Sent By mcarsill Date 2001-05-09 Time 13:39 Rev Time 0.00
Received By mcarsill Date 2001-05-09 Time 13:39 Sent To  
Notes
2001-05-09 00:00:001) ON MAY 9, 2001, THIS WRITER SPOKE
 WITH MR. PAT FPERDUTO OF CHANCE
 CONSTRUCTION. HE ANSWERED ALL PLAN
 REVIEW COMMENTS THAT WERE MADE ON
 5/01/01 BY THIS OFFICE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2001-05-01 Cont ID  
Sent By mcarsill Date 2001-05-01 Time 09:34 Rev Time 0.00
Received By mcarsill Date 2001-05-01 Time 09:23 Sent To  
Notes
2001-05-01 00:00:001) PLEASE DESCRIBE CONSTRUCTION OF
 NEW CANOPY.
 2) PLEASE IDENTIFY ALL ILLUMINATED
 EXIT SIGN LOCATIONS.
 3) PLEASE PROVIDE OCCUPANT CALCULATIONS
 AND IDENTIFY ALL EXIT LOCATIONS.
 4) IF THERE ARE POWER OPERATED EXIT
 DOORS, THEY MUST COMPLY WITH NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION,
 SECTION 5-2.1.9.
 5) IS THE HOOD OVER THE ROTISSERIE NEW
 OR EXISTING. IF THE HOOD IS NEW,
 SEPARATE PLANS AND PERMITS ARE REQUIRED
 FOR THE HOOD,DUCT,AND EXTINGUISHING
 SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-01-08 Cont ID  
Sent By mcarsill Date 2001-01-08 Time 13:29 Rev Time 0.00
Received By mcarsill Date 2001-01-08 Time 13:22 Sent To  
Notes
2001-01-08 00:00:001) PLEASE SUBMIT SHOP DRAWINGS FOR ANY
 FIRE ALARM SYSTEM MODIFICATIONS MADE TO
 THE EXISTING SYSTEM. SEPARATE PLAN AND
 PERMIT REQUIRED PRIOR TO INSTALLATION.
 2) PLEASE SUBMIT SHOP DRAWINGS FOR FIRE
 SPRINKLER SYSTEM MODIFICATIONS MADE TO
 THE EXISTING SYSTEM. SEPARATE PLAN AND
 PERMIT REQUIRED PRIOR TO INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-08-21 Cont ID  
Sent By mcarsill Date 2000-08-21 Time 14:53 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-06-19 Cont ID  
Sent By rturnque Date 2000-06-19 Time 13:54 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-04 Cont ID  
Sent By rturnque Date 2000-04-04 Time 15:26 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE SHOP DRAWINGS FOR FIRE ALARM
 SYSTEM REMODEL. FIRE ALARM SHALL REMAIN
 OPERABLE DURING CONSTRUCTION PERIOD
  
 REQUIRED EXITING SHALL REMAIN DURING
 CONSTRUCTION

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-09-05 Cont ID  
Sent By ndenmark Date 2000-09-05 Time 09:56 Rev Time 0.50
Received By ndenmark Date 2000-09-05 Time 09:56 Sent To  
Notes
2001-01-08 00:00:00REVISION M-5 SHOWS DUCT SMOKE DETECTOR
 CONNECTED AS REQUIRED BY CODE ADDED TO
 SET

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-12 Cont ID  
Sent By ndenmark Date 2000-07-12 Time 14:02 Rev Time 0.10
Received By ndenmark Date 2000-07-12 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-22 Cont ID  
Sent By ndenmark Date 2000-03-22 Time 13:44 Rev Time 1.00
Received By ndenmark Date 2000-03-22 Time 13:44 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
 DUCT SMOKE DETECTORS TO BE TIED TO BUILD
 ING FIRE ALARM SYSTEM PER NFPA 90A 4-4.4
 .3 FOR NOTIFICATION

Review Stop P PLUMBING
Rev No 7 Status P Date 2001-01-05 Cont ID  
Sent By jleech Date 2001-01-05 Time 11:09 Rev Time 2.50
Received By pschmitz Date 2001-01-05 Time 11:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status F Date 2000-09-10 Cont ID  
Sent By tlarge Date 2000-09-10 Time 06:21 Rev Time 1.25
Received By pschmitz Date 2000-09-10 Time 06:21 Sent To  
Notes
2001-01-08 00:00:001)THE TOILET ROOM IN THE TMA SHOW ROOM
 AND THE RECEIVING TOILET ROOM SHALL BE
 HANDICAP ACCESSIBLEPER FACBC SEC.4.1.3
 (11).CLEARLY SHOW COMPLIANCE ON THE
 PLANS.SHOW GRAB BAR HEIGHT,HEIGHT OF
 FIXTURES,CLEARANCES,ETC.
  
 2)CONTACT R.COMPO W/CITY OF WEST PALM
 BEACH WASTEWATER TREATMENT FACILITY
 REGARDING EFFLUENT FROM FILM PROCESSOR.
 SUBMIT APPROVAL FROM R.COMPO FOR
 SYSTEM W/O NEUTRALIZATION TANK.

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-08-23 Cont ID  
Sent By tlarge Date 2000-08-23 Time 13:35 Rev Time 6.00
Received By pschmitz Date 2000-08-23 Time 13:35 Sent To  
Notes
2001-01-08 00:00:001)THE TOILET ROOM IN THE TMA SHOW ROOM
 AND THE RECEIVING TOILET ROOM SHALL BE
 HANDICAP ACCESSIBLE PER FACBC SEC.
 4.1.3(11).CLEARLY SHOW COMPLIANCE ON THE
 PLANS.SHOW GRAB BAR HEIGHT,LOCATION,
 HEIGHT OF FIXTURES,CLEARANCES,ETC.
 COMPLY W/FACBC OCT.1997 ED.
  
 2)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC610.4.2.
  
 3)SIZE ALL WASTE,VENT AND WATER LINES ON
 THE DIAGRAM.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 4)INDIRECT WASTES SHALL DISCHARGE INTO
 A FLOOR SINK,NOT FLOOR DRAIN.SPC SEC.
 807.1.
  
 5)A CHECK AND GATE VALVE ARE REQD.ON THE
 SUMPS DISCHARGE PER SPC SEC.717.2.SUMPS
 SHALL BE VENTED PER 717.6.CONNECTION TO
 DRAINAGE SYSTEM SHALL COMPLY W/SPC SEC.
 717.11.
  
 6)FLOOR DRAINS SHALL BE IN FULL VIEW AT
 ALL TIMES PER SPC SEC.409.4.1.2.
  
 7)CONTACT R.COMPO W/CITY OF WPB CENTRAL
 WASTEWATER TREATMENT FACILITY REGARDING
 EFFLUENT FROM FILM PROCESSOR.SUBMIT
 APPROVAL OF SYSTEM W/O NEUTRALIZATION
 TANK FROM R.COMPO.
  
 8)PHOTOLAB RISER-FIXTURES SHALL BE
 VENTED PER SPC 717.4.
  
 9)AN AIR GAP IS REQD.ON THE RTU COND.
 DRAIN PIPING PER SPC SEC.806.
  
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-06-06 Cont ID  
Sent By tlarge Date 2000-06-06 Time 14:25 Rev Time 3.50
Received By pschmitz Date 2000-06-06 Time 14:25 Sent To  
Notes
2001-01-08 00:00:00COMPLY W/ALL PREVIOUS COMMENTS DATED
 3/5/00 & 5/1/00.
  
 SHT.CV-1-"BUILDING CODES"-INSERT CORRECT
 EDITION OF THE APPLICABLE STANDARD
 BUILDING CODES.COUNTYWIDE AMENDMENTS TO
 SPC SEC.101.1 AND FLA.STATUTE.
  
 CLEARLY SHOW TERMINATION POINT OF CON-
 DENSATE DRAINS ON ROOF.DRAINS SHALL NOT
 DISCHARGE WHERE THE EFFLUENT CAN DRAIN
 INTO A STREET,ALLEY OR OTHER AREAS
 THAT WOULD CREATE A NUISANCE /MENACE.
 SMC SEC.304.8.3(3).
  
 SHT.P1-EYEWASH SHALL DRAIN TO SANITARY
 NOT DISCHARGE ONTO GROUND.SPC SEC.301.4,
 301.11.1.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-05-01 Cont ID  
Sent By tlarge Date 2000-05-01 Time 11:03 Rev Time 2.50
Received By tlarge Date 2000-05-01 Time 11:00 Sent To  
Notes
2001-01-08 00:00:00COMPLY W/ALL PREVIOUS COMMENTS DATED
 3/5/00.
  
 SHT.M-4-DETAIL #4-SUPPLY AIR GAP ON
 CONDENSATE DRAIN PER SPC SEC.806.
  
 SUBMIT INFO ON PURITAN CHEMICAL STATIONS
 AS NOTED ON PLANS.COUNTYWIDE AMENDMENTS
 TO SPC.SEC.104.2.1.
  
 EYEWASH DRAIN CANNOT DISCHARGE INTO
 FLOOR DRAIN IN TMA TOILET ROOM PER SPC
 SEC.807.1.1.
  
 RELIEF LINES FROM WATER HEATERS SHALL
 DISCHARGE TO EXTERIOR PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.6.1.SEE SHT.
 P-3,DETAIL#3 ALSO.
  
 SUMP DISCHARGE PIPING SHALL CONNECT TO
 SANITARY SYSTEM PER SPC SEC.717.11.
 (SUMPS AND ASSOCIATED PIPING SHALL
 COMPLY W/SPC SECS.717.1-717.11.)
  
 SUMP PIPING CONNECTION FROM VISION AND
 PHOTO AREAS TO SNACK BAR PIPING NOT
 SHOWN PLANS..COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 SINKS AT VISION CENTER SHALL BE PROPERLY
 VENTED PER SPC SEC.901.2.
  
 GREASE RECOVERY UNITS ARE NOT PERMITTED
 PER CITY OF WPB ORDINANCE.
  
 SHT.P-4-DETAIL#8-DRAINS CANNOT BE
 REDUCED IN SIZE PER SPC SEC.709.1

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-03-05 Cont ID  
Sent By tlarge Date 2000-03-05 Time 10:02 Rev Time 5.50
Received By tlarge Date 2000-03-05 Time 10:02 Sent To  
Notes
2001-01-08 00:00:00*******CONTINUATION OF PLBG.COMMENTS****
 24)POT/SCULLERY SINKS SHALL BE STACKED
 AND VENTED PER SPC SEC.804.1.
  
 25)HEATER P& T LINE SHALL DISCHARGE TO
 AN OBSERVABLE POINT PER COUNTYWIDE AMEND
 MENTS TO SPC SEC.507.8.4.
  
 26)SUBMIT WATER PIPING/DRAINAGE DETAILS
 FOR ROTISSERIE AREA AND SUMP PUMP AT
 TRUCK DOCK.
  
 27)SIZE ALL SECTIONS OF THE COMPRESSED
 AIR SYSTEM.
  
 28)WATER FILTRATION SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1,615.2.SUBMIT
 DATA.
  
 29)SHT.P-4-SIZE AND DESIGN OF GREASE
 TRAP SHALL BE APPROVED BY CITY OF WEST
 PALM BEACH UTILITIES.CONTACT R.COMPO AT
 (561)835-7423.
  
 30)SHT.P-3-DETAILS #8,11,ET.AL.-LOCATION
 OF FLOOR DRAINS SHALL COMPLY W/SPC SEC.
 409.4.1.2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-05 Cont ID  
Sent By tlarge Date 2000-03-05 Time 09:05 Rev Time 0.00
Received By tlarge Date 2000-03-05 Time 09:05 Sent To  
Notes
2001-01-08 00:00:00JOB SPEC.15050-SEC.3.02(I)-VERTICAL AND
 HORIZONTAL SPACING OF PIPE SUPPORTS
 SHALL COMPLY W/SPC SECS.310.2,310.3
 RESPECTIVELY.
  
 2)JOB SPEC.15400-SEC.2.01(D)-PIPING
 INSULATION SHALL COMPLY W/FLA.ENERGY
 CODE TABLE 4-11.
  
 3)JOB SPEC.15400-SEC.2.15-GREASE
 RECOVERY UNITS NOT PERMITTTED PER CITY
 ORDINANCE.
  
 4)JOB SPEC.15400-SEC.3.01(A)-SLOPE OF
 DRAINAGE PIPE SHALL COMPLY W/SPC SEC.
 705.2,705.3.9(SEE SHT.P1,NOTE #3 ALSO)
  
 5)SHT.CV1-THE CURRENT ADOPTED PLUMBING
 CODE IN THE CITY OF WEST PALM BEACH IS
 THE 1994 EDITION OF THE STANDARD
 PLUMBING,NOT 1997.
  
 6)THE MINIMUM NUMBER OF SANITARY FACIL-
 ITIES REQD.BY 1994 PLBG.CODE IS :
 MALES]-WATERCLOSETS-5
 -LAVATORIES_____5
 FEMALES]-WATER CLOSETS-9
 -LAVATORIES____9
 -DRINKING FOUNTAINS-4
 SEE SPC CODE SEC.407.1.3 & TABLE 407.
  
 7)ALL COMMON AND PUBLIC AREA TOILET
 ROOMS SHALL COMPLY W/FACBC SEC.4.1.3(11)
  
 8)SHT.A-4-TOP OF H.C.LAV.AFF SHALL BE
 34" PER FACBC SEC.4.19.2.
  
 9)SHT.A-5-DRINKING FOUNTAIN IN TMA SHALL
 BE H.C.ACCESSIBLE AND COMPLY W/FACBC
 SEC.4.1.3.(10)(A).
  
 10)TOILET ROOM IN TMA SHOWROOM SHALL BE
 HANDICAP ACCESSIBLE PER FACBC SEC.4.1.3.
 (11)
  
 11)SUBMIT WATER PIPING AND DRAINAGE
 DETAILS FOR RACK WASHER.
  
 12)WATER HEATER SHALL BE READILY ACCESS-
 IBLE.PROVIDE PERMANENT LADDER OR RE-
 LOCATE TO FLOOR.SPC 501.7.
  
 13)CLEARLY SHOW TYPE OF FINISH ON REST-
 ROOM WALLS.COMPLY W/SBC SEC.1204.2(NON-
 ABSORBENT TO A HEIGHT OF 4'.)
  
 14)SUBMIT MANUF.SHEETS FOR FILM PROCESS-
 OR AND SILVER RECOVERY UNIT.WASTE SHALL
 BE NEUTRALIZED PER SPC SEC.801.4.DATA
 SHOWING ESTIMATED PH OF EFFLUENT SHALL
 BE SUBMITTED FOR REVIEW.
  
 15)SINK IN EMPLOYEE LOUNGE SHALL BE H.C.
 ACCESSIBLE AND COMPLY W/FACBC SEC.4.24.1
 THRU 4.24.7.
  
 16)SUBMIT WASTE AND WATER RISER FOR SINK
 IN EMPLOYEE LOUNGE ,RM.112.LINE SHALL
 DRAIN TO SANITARY PER SPC 1004.3.
  
 17)WATER SUPPLY CONTROL FOR ALL AREAS
 SHALL COMPLY W/SPC SEC.610.4.1.,610.4.2.
  
 18)SIZE ALL WASTE,VENT AND WATER LINES
 ON THE RISER DIAGRAMS.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 19)HAND SINKS,SERVICE SINKS,FLOOR DRAINS
 AND SIMILAR FIXTURES IN THE FOOD/SNACK
 BAR AREAS SHALL DISCHARGE THROUGH THE
 GREASE INTERCEPTOR PER SPC SEC.1004.4.
  
 20)INDIRECT WASTE LINES SHALL COMPLY W/
 SPC SEC.805.1.1,805.2.
  
 21)FLOOR DRAINS NOT SUPPLIED W/INDIRECT
 WASTES SHALL BE EQUIPPED W/TRAP PRIMERS
 PER SPC SEC.409.4.1.1.
  
 22)SUBMIT COMPLETE GAS DRAWING FOR
 REVIEW.SHOW MOST REMOTE OUTLET,CUT
 SECTIONS OF PIPE,BTU LOAD OF EACH PIECE
 OF EQUIP.ALL EQUIPMENT SHALL BE LISTED/
 APPROVED PER SGC SEC.402.1 AND NFPA 54.
 SUBMIT MANUF. SHEETS FOR ALL GAS EQUIP.
  
 23)SUMPS SHALL COMPLY W/SPC SEC.717.SUB-
 MIT DETAILS ON SUMP CONSTRUCTION,PUMPS
 ETSC.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By lmartine Date 2001-02-21 Time 11:27 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-02-21 00:00:00APPROVED BY ERIC SNYDER 2/20/01