Review Stop P PLUMBING
Rev No 1 Status N Date 2000-03-08 Cont ID  
Sent By tlarge Date 2000-02-25 Time 05:20 Rev Time 0.50
Received By tlarge Date 2000-02-25 Time 05:20 Sent To  
Notes
2001-01-08 00:00:00SIZING OF GAS LINE TO WATER HEATER AND
 DRYER SHALL BE 3/4" PER SGC TABLE 305.4
 (A).
  
 SUBMIT EHD OF 3/4" CSST AND SIZING TABLE
 FROM MANUF.AND SUBMIT NAME OF MANUF.TO
 ENSURE PROPER SIZING OF GAS SYSTEM
 UTILIZING CSST PIPE.TABLE 305.4(F).