Plan Review Details - Permit 00021248
Plan Review Stops For Permit 00021248
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-08 Cont ID  
Sent By tlarge Date 2000-03-08 Time 09:53 Rev Time 0.30
Received By tlarge Date 2000-03-08 Time 09:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-03-08 Cont ID  
Sent By tlarge Date 2000-02-25 Time 07:21 Rev Time 0.50
Received By tlarge Date 2000-02-25 Time 07:21 Sent To  
Notes
2001-01-08 00:00:00INDICATE TYPE OF PIPE BEING INSTALLED.
 COMPLY W.SGC SEC.306.
  
 SHOW DIMENSIONS OF ALL CUT LENGTHS OF
 PIPE TO ENSURE COMPLIANCE W/SGC TABLES
 305.4(A),305.4(F).
  
 IF CSST WILL BE USED INDICATE MANUF.OF
 CSST,THE PROPER EHD OF THE TUBING AND
 SUBMIT SIZING TABLE FROM THE MANUF.TO
 ENSURE PROPER SIZING.