Plan Review Details - Permit 00021185
Plan Review Stops For Permit 00021185
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-08-31 Cont ID  
Sent By dpalmer Date 2000-08-31 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2000-08-31 Time 10:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 18:29 Sent To  
Notes
2001-01-08 00:00:00PLANS STILL DON`T SHOW CLARIFICATION
 FOR AHU/WH????
  
 CALLED AND LEFT MESSAGE 8/21/00

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-08-02 Cont ID  
Sent By dpalmer Date 2000-08-02 Time 17:09 Rev Time 0.00
Received By dpalmer Date 2000-08-02 Time 17:09 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *****************
  
 1)NOTE: PLANS NEED TO BE SIGNED AND
 SEALED LIKE ORIGINAL PLANS/ARCH. OF REC-
 -ORD.
  
 2)NOTE: PLEASE CLARIFY WHEATHER YOU ARE
 HAVING A SPLIT A/C SYSTEM OR PKG UNIT.
 PLANS SHOW BOTH????
  
 PLEASE RESUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW.
  
 659-8096 EXT8372
  
 STILL NEED TO SHOW DETAIL ON GROUNDING
 AT GARAGE AS ASKED FOR ON PREVIOUS
 NOTES.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-03 Cont ID  
Sent By dpalmer Date 2000-04-03 Time 07:44 Rev Time 0.00
Received By dpalmer Date 2000-04-03 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-14 Cont ID  
Sent By gjoyce Date 2000-02-29 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2000-03-14 Time 17:15 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW INDETAIL THE GROUND-
 -ING ELECTRODE SYSTEM AT GARAGE. TO GRND
 ROD AND COLD WATER PIPE. 250-81
  
 2)NOTE: PLEASE NOTE THAT YOU HAVE TO
 GROUP MAINS AS PER 230-72 AT HOUSE.
 YOU SHOW FEED FOR GARAGE COMING OUT OF
 METER CAN. THIS CANNOT BE DONE. ALSO
 SUBMIT LOAD CALCULATION ON MAIN HOUSE
 ELECTRIC IF YOU ARE FEEDING ON EXISTING
 RISER/OR PANEL.
  
 3)NOTE:ALSO 3-2/0`S TO GARAGE???
  
 4)NOTE:ALSO 5KW A/C UNIT DOES NOT REQ`
 50AMP BRKR OR 3-#6 CONDUCTORS. #10 EQUIP
 MENT GROUND.NEED TO SHOW COMPLETE DETAIL
 ON A/C SYSTEM BEING INSTALLED IN WALL
 OF THE SMALL ROOM.THIS WIRING CAN NOT
 BE INSTALLED. MUST BE WIRING FOR RATED
 A/C UNIT. 3-#10`S. NO ELEC.MAY BE
 INSTALLED THAT MAY BE CHANGED FOR FUTURE
 COOKING.ALSO, 2 POLE 50 IS TOO LARGE FOR
 UNIT.
  
 5)NOTE:PLEASE INCLUDE BATH ON PANEL
 SCHEDULE. AS REQ`D BY 210-52D AND 210-11
 -C-3.
  
 NOTE THAT ZONING AS NOTED , NO KITCHEN
 WILL BE PERMITTED IN THIS STRUCTURE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-29 Cont ID  
Sent By ndenmark Date 2000-08-29 Time 15:03 Rev Time 0.25
Received By ndenmark Date 2000-08-29 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-08-10 Cont ID  
Sent By cthirben Date 2000-08-10 Time 08:53 Rev Time 1.00
Received By cthirben Date 2000-08-10 Time 08:51 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 *INDICATE THE TYPE A/C UNIT. WHAT IS
 STATED ON PLANS IS CONFLICTING.
 *PROVIDE SEALED AND SIGNED PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-16 Cont ID  
Sent By cthirben Date 2000-03-16 Time 13:38 Rev Time 1.00
Received By cthirben Date 2000-03-16 Time 13:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-09-08 Cont ID  
Sent By tlarge Date 2000-09-08 Time 10:08 Rev Time 0.25
Received By tlarge Date 2000-09-08 Time 10:08 Sent To  
Notes
2001-01-08 00:00:00MIN.VENT SIZE SHALL BE 3" PER SPC SEC.
 904.3.1.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-09 Cont ID  
Sent By tlarge Date 2000-08-09 Time 06:42 Rev Time 0.30
Received By tlarge Date 2000-08-09 Time 06:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-15 Cont ID  
Sent By tlarge Date 2000-03-15 Time 06:31 Rev Time 0.33
Received By tlarge Date 2000-03-15 Time 06:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-08-31 Cont ID  
Sent By rmcdouga Date 2000-08-31 Time 09:26 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-08-10 Cont ID  
Sent By rmcdouga Date 2000-08-10 Time 16:22 Rev Time 1.00
Received By rmcdouga Date 2000-08-10 Time 16:21 Sent To  
Notes
2001-01-08 00:00:00DENIED
 REVISION SUBMITTED 8-2-00
 1)PROVIDE 2 SETS OF PLANS WET SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-04-10 Cont ID  
Sent By lsmith Date 2000-04-10 Time 10:41 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED PRODUCT APPROVAL FOR FRENCH DOOR

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-29 Cont ID  
Sent By dpalmer Date 2000-03-14 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2000-02-29 Time 17:31 Sent To  
Notes
2001-01-08 00:00:00ZONING WAS PASSED BY GRACE JOYCE BUT HER
 STOP WAS ENTERED IN ELEC. STOP.
 GRACE`S NOTES WERE; NO KITCHEN MAY BE
 INSTALLED.