Plan Review Details - Permit 00021175
Plan Review Stops For Permit 00021175
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-10 Cont ID  
Sent By dpalmer Date 2000-04-10 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2000-04-10 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-14 Cont ID  
Sent By dpalmer Date 2000-03-14 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2000-03-14 Time 18:53 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 AS REEQ`D BY NFPA-72 2-2.1.1.1 INCLUDING
 ROOMS THAT MAY BE CONVERTED TO SLEEPING
 ROOMS.
  
 2)NOTE:PLEASE SHOW RECEPT REQ`D BY ART;
 210-63
  
 3)NOTE:NO EQUIPMENT GROUND IS TO BE
 INSTALLED FROM METER TO FIRST MEANS OF
 DISCONNECT.
  
 4)NOTE:PLEASE INCLUDE BATH(S) CIRCUT(S)
 ON PANEL SCHEDULE.AS REQ`D BY 210-11-C-3
  
 5)NOTE: NEED TO IN AIC RATING OF MAIN
 AS REQ`D BY 110-9/215-5 MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 6)NOTE:SMALL APPLIANCE CIRCUTS REQ`D BY
 210-11-C-1 #12 AND 20AMP X TWO,1500VA
  
 7)NOTE: PLEASE INCLUDE COLD WATER PIPE
 AS PART OF GROUNDING ELEC. SYSTEM AS
 PER 250-81
  
 8)NOTE:PLEASE CHECK THE HEAT STRIP BEING
 INSTALLED?? THIS 5KW SEEMS LIKE IT WILL
 BE TOO SMALL FOR 1200 SQ FT.
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-03-15 Cont ID  
Sent By cthirben Date 2000-03-15 Time 09:21 Rev Time 1.00
Received By cthirben Date 2000-03-15 Time 09:20 Sent To  
Notes
2001-01-08 00:00:00*********** NO MECHANICAL PLANS ********

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-03-20 Cont ID  
Sent By lsmith Date 2000-03-20 Time 09:51 Rev Time 0.10
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-04-11 Cont ID  
Sent By lsmith Date 2000-04-11 Time 10:32 Rev Time 1.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-23 Cont ID  
Sent By lsmith Date 2000-03-23 Time 07:51 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED PRODUCT APPROVALS FOR FOLLOWING:
 1. WINDOWS
 2. DOORS
 3. ROOFING MATERIALS
 NEED SIGNED & SEALED TRUSS DRAWINGS
 NEED PLAN HIGHLIGHTED IN AREAS TO BE
 REPLACED OR REPAIRED.
 BOB COMPTON TO DO PREINSPECTION 3/23/00