Plan Review Details - Permit 00021153
Plan Review Stops For Permit 00021153
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-16 Cont ID  
Sent By dpalmer Date 2001-02-16 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2001-02-16 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-31 Cont ID  
Sent By dpalmer Date 2000-03-31 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2000-03-31 Time 12:27 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE:NEED TO SUBMIT ALL AIC RATINGS OF
 MAINS.110-9/215-5 MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE:YOU SHOW EQUIPMENT GROUNDING
 CONDUCTORS FROM METER TO MAIN DISC? ONLY
 AFTER FIRST MEANS OF DISCONNECT.
  
 3)NOTE:YOU NEED TO SUBMIT NEW LOAD
 CALCUALTIONS FOR EXISTING HOUSE SERVICE
 PER 220-3-C-1
  
 4)NOTE:PLEASE CHECK PANEL SCHEDULES. ALL
 BATH CIRCUTS PER 210-11-C-3 20AMP #12
  
 5)NOTE:PLEASE SHOW COMPLETE GROUNDING
 ELECTRODE SYSTEM FOR THE NEW MAIN HOUSE
 SERVICE.
  
 6)NOTE:PLEASE NOTE ALL THE REQ`MENTS FOR
 SMOKE DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS!! THIS NEEDSTOINCLUDE
 ALL SD`S IN COMMON AREAS FOR TWO STORY.
 NFPA-72 2-2.1.1.1
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-04 Cont ID  
Sent By jleech Date 2000-03-04 Time 09:56 Rev Time 0.50
Received By jleech Date 2000-03-04 Time 09:56 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 1. BATHROOMS VENTILATION TO COMPLY TO
 SMC-503.3.1.
 2.RELOCATE R/A DOORS COULD SHUT OFF AIR
 SUPPLY.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 15:16 Rev Time 0.00
Received By jleech Date 2000-11-14 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 07:20 Rev Time 0.00
Received By tlarge Date 2000-08-21 Time 07:20 Sent To  
Notes
2001-01-08 00:00:001)FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED.SPC SEC.913.2.
  
 2)WASHING MACHINES SHALL BE TRAPPED AND
 VENTED.SPC SEC.401.4,901.2.
  
 3)FIXTURE BRANCHES NOT PERMITTED ON
 WET VENTS.(1ST.FLR.WATER CLOSET IN
 GUEST HOUSE SHALL BE SEPARATELY VENTED.)
 COUNTYWIDE AMENDMENTS 911.1.1.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-04 Cont ID  
Sent By tlarge Date 2000-03-04 Time 06:19 Rev Time 0.65
Received By tlarge Date 2000-03-04 Time 06:19 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 SUBMIT REVISED SANITARY RISER PRIOR TO
 RGH.PLBG.INSP.-CABANA BATH NOT ON RISER.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-05-05 Cont ID  
Sent By hpiskura Date 2000-05-05 Time 07:38 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-04-20 Cont ID  
Sent By hpiskura Date 2000-04-20 Time 10:46 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER ATTACHED TO APPLICATION

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-02 Cont ID  
Sent By gjoyce Date 2000-02-24 Time 11:01 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***