Plan Review Details - Permit 00021132
Plan Review Stops For Permit 00021132
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-04 Cont ID  
Sent By hpiskura Date 2000-04-04 Time 14:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-09 Cont ID  
Sent By dpalmer Date 2000-05-09 Time 17:56 Rev Time 0.00
Received By dpalmer Date 2000-05-09 Time 17:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 11:29 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 11:28 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE; NEED TO SUBMIT SHOWING COMPLETE
 LOAD CALCULATIONS SHOWING ALL COTINUOUS
 LOAD AT 125% (LIGHTING ETC )
  
 2)NOTE: MAIN PANEL SCHEDULE SHOWS 150
 GOING TO ROOF TOP A/C ? OR IS THAT THE
 MAIN FOR THE OTHER PANEL? PLEASE CLARIFY
  
 3)NOTE: PLEASE PROVIDE ALL AIC RATINGS
 OF EQUIPMENT MAINS/ BRANCH PANELS ALSO.
 MAINS MUST BE RATED FOR THE AVAILBALE
 FAULT CURRENT AS PER 110-9/110-10
  
 4)NOTE: ALL OUTLETS IN BATHS MUST BE
 GFI/GFI PROTECTED AS PER 210-8-B IN OTHR
 THAN DWELLING UNITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS CALL
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-03-15 Cont ID  
Sent By lsmith Date 2000-03-15 Time 09:03 Rev Time 0.10
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-07 Cont ID  
Sent By lmartine Date 2000-03-07 Time 16:07 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-05-10 Cont ID  
Sent By cthirben Date 2000-05-10 Time 14:59 Rev Time 1.00
Received By cthirben Date 2000-05-10 Time 14:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-03-21 Cont ID  
Sent By ndenmark Date 2000-03-21 Time 11:40 Rev Time 0.50
Received By ndenmark Date 2000-03-21 Time 11:40 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TIED TO HORN AND STROBE FOR
 NOTIFICATION PER NFPA 92A 4-4.4.3

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-04 Cont ID  
Sent By tlarge Date 2000-03-04 Time 13:16 Rev Time 0.65
Received By tlarge Date 2000-03-04 Time 13:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2000-03-15 Cont ID  
Sent By lsmith Date 2000-03-15 Time 09:03 Rev Time 0.10
Received By lsmith Date   Time   Sent To  
Notes
***NONE***