Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-01 Cont ID  
Sent By dpalmer Date 2000-05-01 Time 07:44 Rev Time 0.00
Received By dpalmer Date 2000-05-01 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 19:56 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS. MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
 215-5
  
 2)NOTE: YOU SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO CWP OR BLDG.STEEL.
 BOTH MUST BE A PART OF THE GROUNDING
 ELECTRODE SYSTEM AS PER 250-50 PLEASE
 SHOW ON RISER DIAGRAM.215-5
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUT(S) AS PER 210-11-C-3
  
 4)NOTE: SHOW LIGHT AS REQ`D BY 210-70-
 A-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE
 ARE ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-04 Cont ID  
Sent By jleech Date 2000-03-04 Time 11:14 Rev Time 0.35
Received By jleech Date 2000-03-04 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-29 Cont ID  
Sent By tlarge Date 2000-04-29 Time 07:00 Rev Time 0.30
Received By tlarge Date 2000-04-29 Time 07:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-25 Cont ID  
Sent By tlarge Date 2000-02-25 Time 17:09 Rev Time 0.33
Received By tlarge Date 2000-02-25 Time 17:09 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF PLUMBING FIXTURES ON
 SANITARY RISER SHALL CORRELATE W/FLOOR
 PLAN AND RISER SHALL COMPLY W/STANDARD
 PLBG.CODE.
 A)MIN.SIZE OF PIPING U/G SHALL BE 2" PER
 SPC SEC.714.4.
 B)WATER CLOSETS AND TUBS IN BATHS 2 & 3
 NOT PROPERLY VENTED.SPC SEC.901.2.
 C)REVISE KIT. SINK DRAIN AND VENT TO
 COMPLY W/SPC SEC.901.2,905.7,908.2.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-05-22 Cont ID  
Sent By rmcdouga Date 2000-05-22 Time 11:09 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER JOHN CALOGERO 5-11-00 RM

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-04-18 Cont ID  
Sent By jcaloger Date 2000-04-18 Time 12:35 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00THE SOIL REPORT NEEDS THE ENGINEER
 ORIGINAL SIGNATURE AND DATE
  
  
 PLANS NEEDS PALM BEACH COUNTY IMPACT FEE
 PAID
  
 THE PROPOSED WINDOWS DO NOT HAVE A VALID
 PRODUCT APPROVAL THERFORE ARE DENIED FOR
 USE.
  
  
 OWES RADON AND ADDITIONAL PERMIT FEES.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By gjoyce Date 2000-02-24 Time 14:54 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***