Plan Review Details - Permit 00021020
| Plan Review Stops For Permit 00021020 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-05-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-05-01 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-05-01 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-20 |
Time |
19:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-20 |
Time |
19:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING OF | | | EQUIPMENT MAINS. MAINS ARE TO BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. 110-9 | | | 215-5 | | | | | | 2)NOTE: YOU SHOW GROUNDING ELECTRODE | | | CONDUCTOR GOING TO CWP OR BLDG.STEEL. | | | BOTH MUST BE A PART OF THE GROUNDING | | | ELECTRODE SYSTEM AS PER 250-50 PLEASE | | | SHOW ON RISER DIAGRAM.215-5 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH(S) CIRCUT(S) AS PER 210-11-C-3 | | | | | | 4)NOTE: SHOW LIGHT AS REQ`D BY 210-70- | | | A-3 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE | | | ARE ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-04 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-03-04 |
Time |
11:14 |
Rev Time |
0.35 |
| Received By |
jleech |
Date |
2000-03-04 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-04-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-29 |
Time |
07:00 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-04-29 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-25 |
Time |
17:09 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-02-25 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LOCATION OF PLUMBING FIXTURES ON | | | SANITARY RISER SHALL CORRELATE W/FLOOR | | | PLAN AND RISER SHALL COMPLY W/STANDARD | | | PLBG.CODE. | | | A)MIN.SIZE OF PIPING U/G SHALL BE 2" PER | | | SPC SEC.714.4. | | | B)WATER CLOSETS AND TUBS IN BATHS 2 & 3 | | | NOT PROPERLY VENTED.SPC SEC.901.2. | | | C)REVISE KIT. SINK DRAIN AND VENT TO | | | COMPLY W/SPC SEC.901.2,905.7,908.2. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-05-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-05-22 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK PER JOHN CALOGERO 5-11-00 RM |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-04-18 |
|
|
Cont ID |
|
| Sent By |
jcaloger |
Date |
2000-04-18 |
Time |
12:35 |
Rev Time |
1.00 |
| Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THE SOIL REPORT NEEDS THE ENGINEER | | | ORIGINAL SIGNATURE AND DATE | | | | | | | | | PLANS NEEDS PALM BEACH COUNTY IMPACT FEE | | | PAID | | | | | | THE PROPOSED WINDOWS DO NOT HAVE A VALID | | | PRODUCT APPROVAL THERFORE ARE DENIED FOR | | | USE. | | | | | | | | | OWES RADON AND ADDITIONAL PERMIT FEES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-02-24 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-02-24 |
Time |
14:54 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|