Plan Review Details - Permit 00021007
Plan Review Stops For Permit 00021007
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-20 Cont ID  
Sent By fknapp Date 2000-04-20 Time 11:07 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER D.PALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 20:14 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING
 OF EQUIPMENT MAINS. MAINS MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110-9/215-5 PLEASE LIST ON PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE SHOW ON RISER DIAGRAM THE
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 BLDG.STEEL AS REQ`D BY 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEWAND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-04 Cont ID  
Sent By jleech Date 2000-03-04 Time 10:45 Rev Time 0.35
Received By jleech Date 2000-03-04 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 15:40 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 15:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-25 Cont ID  
Sent By tlarge Date 2000-02-25 Time 17:26 Rev Time 0.50
Received By tlarge Date 2000-02-25 Time 17:26 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF PLUMBING FIXTURES ON RISER
 SHALL CORRELATE W/FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SANITARY DOESN'T COMPLY W/ SPC.
 A)WATER CLOSETS AND SHOWERS NOT PROPERLY
 VENTED.SPC 901.2,913.2.
 B)FIXTURE BRANCHES AND WATER CLOSETS NOT
 PERMITTED ON WET VENTS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1
 C)LAV AND KIT.SINK NOT VENTED.SPC 901.2.
 D)MIN.SIZE DRAIN U/G SHALL BE 2" PER
 SPC SEC.714.4.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By fknapp Date 2000-04-18 Time 13:52 Rev Time 5.00
Received By fknapp Date 2000-04-18 Time 13:52 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************PROVISO****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 FRONT ENTRY DOOR ASSEMBLY
 CIRCLE WINDOWS
 MULLIONS
  
 2)PROVIDE SPECIFICATIONS FOR 1HR RATED
 GLASS BLOCK.
  
 3)PROVIDE ROOF SHEATHING NAILING ZONES
 COMPLYING WITH CITY AMENDMENTS 2306.1
 ZONE 3 EDGES 4"OC.
  
 4)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By gjoyce Date 2000-02-24 Time 11:39 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***