Plan Review Details - Permit 00021007
| Plan Review Stops For Permit 00021007 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-04-20 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-04-20 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK PER D.PALMER |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-20 |
Time |
20:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-20 |
Time |
20:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING | | | OF EQUIPMENT MAINS. MAINS MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110-9/215-5 PLEASE LIST ON PANEL | | | SCHEDULE. | | | | | | 2)NOTE: PLEASE SHOW ON RISER DIAGRAM THE | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | BLDG.STEEL AS REQ`D BY 250-50 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEWAND APPROVAL. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-04 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-03-04 |
Time |
10:45 |
Rev Time |
0.35 |
| Received By |
jleech |
Date |
2000-03-04 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-04-18 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-18 |
Time |
15:40 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-04-18 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-25 |
Time |
17:26 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-02-25 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LOCATION OF PLUMBING FIXTURES ON RISER | | | SHALL CORRELATE W/FLOOR PLAN.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | SANITARY DOESN'T COMPLY W/ SPC. | | | A)WATER CLOSETS AND SHOWERS NOT PROPERLY | | | VENTED.SPC 901.2,913.2. | | | B)FIXTURE BRANCHES AND WATER CLOSETS NOT | | | PERMITTED ON WET VENTS.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1 | | | C)LAV AND KIT.SINK NOT VENTED.SPC 901.2. | | | D)MIN.SIZE DRAIN U/G SHALL BE 2" PER | | | SPC SEC.714.4. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2000-04-18 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-04-18 |
Time |
13:52 |
Rev Time |
5.00 |
| Received By |
fknapp |
Date |
2000-04-18 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | *****************PROVISO**************** | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR: | | | FRONT ENTRY DOOR ASSEMBLY | | | CIRCLE WINDOWS | | | MULLIONS | | | | | | 2)PROVIDE SPECIFICATIONS FOR 1HR RATED | | | GLASS BLOCK. | | | | | | 3)PROVIDE ROOF SHEATHING NAILING ZONES | | | COMPLYING WITH CITY AMENDMENTS 2306.1 | | | ZONE 3 EDGES 4"OC. | | | | | | 4)BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED,IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO., THE PERMIT PLANS STAMPED BY | | | THEM AND THE RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-02-24 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-02-24 |
Time |
11:39 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|