Plan Review Details - Permit 00020965
Plan Review Stops For Permit 00020965
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-08 Cont ID  
Sent By lmartine Date 2000-03-08 Time 13:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-04-24 Cont ID  
Sent By dpalmer Date 2000-04-24 Time 09:05 Rev Time 0.00
Received By dpalmer Date 2000-04-24 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-28 Cont ID  
Sent By dpalmer Date 2000-03-28 Time 06:51 Rev Time 0.00
Received By dpalmer Date 2000-03-28 Time 06:51 Sent To  
Notes
2001-01-08 00:00:00*************** OK *********************
  
 NOTES ON PLANS FOR GROUNDING ELECTRODE
 SYSTEM PER ART 250

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By dpalmer Date 2000-03-03 Time 07:33 Rev Time 0.00
Received By dpalmer Date 2000-03-03 Time 07:33 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE:NEED TO SUBMIT AIC RATINGS OF ALL
 EQUIPMENT MAINS. MAINS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT AS REQ`D BY
 110-9/110-10 OF THE NEC. SHOW ON EACH
 PANEL.
  
 2)NOTE:MISSING LIGHTING IN FIRST FLOOR
 BATHROOMS. AS REQ`D BY 210-70
  
 3)NOTE:PLEASE INDICATE THE SWITCHES AS
 3-WAY IF THIS IS THE CASE.
  
 4)NOTE:PLEASE INDICATE ALL BRANCH CIRCUT
 #`S ON PLANS FOR LIGHTING AND OUTLETS.
  
 5)NOTE:PLEASE NOTE THAT OUTLETS ARE REQ`
 -D FOR SHOW WINDOWS AS PER 210-62.
 THEY MUST BE DIRECTLY ABOVE WINDOW.
  
 6)NOTE:PLEASE SHOW LOAD CALCULATIONS
 SHOWING THE SEPARATE LOAD REQ`D FOR
 TRACK LIGHTING AND SHOW WINDOWS. AS PER
 220-12 A&B
 ALSO PLEASE SHOW LIGHTING LOADS AT 125%
 FOR CONTINUOUS DUTY. 3 OR MORE HOURS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 ANY INSPECTIONS ARE CALLED IN. IF THERE
 ARE ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-02 Cont ID  
Sent By rturnque Date 2000-03-02 Time 08:14 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-03-08 Cont ID  
Sent By lmartine Date 2000-03-08 Time 13:19 Rev Time 0.00
Received By lmartine Date 2000-03-08 Time 13:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-26 Cont ID  
Sent By tlarge Date 2000-02-26 Time 09:36 Rev Time 0.50
Received By tlarge Date 2000-02-26 Time 09:35 Sent To  
Notes
***NONE***