| 2001-01-08 00:00:00 | PLANS SHALL BE REVIEWED AND APPROVED BY |
| | DEPT.OF BUSINESS AND PROFESSIONAL REG. |
| | PRIOR TO REVIEW BY THIS DEPT.PER COUNTY- |
| | WIDE AMENDMENTS TO SPC SEC.101.4.7. |
| | |
| | CLARIFY TYPE OF OCCUPANCY ON TITLE SHEET |
| | THERE IS NO "A-3" OCCUPANCY IN THE SBC. |
| | SBC 304.2.1. |
| | |
| | SUBMIT OCCUPANT LOAD BASED ON HABITABLE |
| | FLOOR SPACE PER SPC SEC.407.1.3.THE MIN. |
| | REQUIRED NUMBER AND TYPE OF PLUMBING |
| | FIXTURES SHALL COMPLY W/SPC. TABLE 407. |
| | |
| | CLEARLY SHOW THE REQD.WHEELCHAIR TURN- |
| | ING SPACE IN THE TOILET STALLS PER |
| | FACBC SEC.4.2.3. |
| | |
| | GREASE TRAP SHALL COMPLY W/CITY OF WPB |
| | UTILITIES REQS.CONTACT ROD COMPO AT(561) |
| | 835-7423. |
| | |
| | CLEARLY SHOW SIZES OF ACCESSIBLE TOILET |
| | ROOMS AND HANDICAPSTALLS.COMPLY W/ |
| | FACBC 4.16,4.17,FIGURE 28, FIG,30.(LXW) |
| | |
| | SHT.P-1(INSULATION TABLE FOR WTR.PIPING) |
| | INSULATION THICKNESS FOR PIPING SHALL |
| | COMPLY W/FLA.ENERGY CODE TABLE 4-11. |
| | |
| | SHT.P-2-DRAIN FROM BAKERY,BAR & SERVICE |
| | AREAS SHALL DRAIN TO THE GREASY WASTE |
| | SYSTEM,NOT THE SANITARY.SPC SEC.1004.1, |
| | 1004.4. |
| | |
| | SUBMIT DETAIL OF DETERGENT PUMPS AND |
| | WATER CONNECTION THERETO.A BACKFLOW |
| | PREVENTION DEVICE SHALL BE INSTALLED ON |
| | THE WATER CONNECTION PER SPC SEC.606.1. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | SECS.610.4.1,610.4.2. |
| | |
| | SHT.P-7-THE DISTANCE OF A WATER CLOSET |
| | TRAP FROM ITS VENT SHALL NOT EXCEED |
| | 5 FT.PER COUNTYWIDE AMENDMENTS TO SPC |
| | TABLE 908.1,FOOTNOTE #2. |
| | |
| | SHT.P-7-FIXTURE BRANCHES AND WATER |
| | CLOSETS ARE NOT PERMITTED ON HORIZ.WET |
| | VENTS PER COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.911.1.1,911.1.3.(SEE MEN'S AND |
| | WOMEN'S RESTROOM.) |
| | |
| | THE SANITARY RISER DOES NOT SHOW ALL |
| | PLUMBING FIXTURES.SUBMIT REVISED |
| | SANITARY RISER THAT CLEARLY REFLECTS |
| | ENTIRE SCOPE OF WORK TO BE PERFORMED. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | (SEE WOMEN'S R.R., 3" SAN.TO 2ND.FLR., |
| | 2ND FLR. PLBG.,ETC.) |
| | |
| | FIXTURE UNIT LOAD SHALL COMPLY W/TABLE |
| | 713.1,713.2.REVISE FIXTURE UNIT LOAD. |
| | |
| | WATER FILTRATION/TREATMENT SYSTEMS SHALL |
| | COMPLY W/SPC SEC.615.1,615.2.,NSF 42,53, |
| | 58.SUBMIT MANUF.SHEETS. |
| | |
| | SUBMIT DETAILS ON GAS VENT FOR WATER |
| | HEATER.INDICATE TYPE OF VENT,HEIGHT |
| | ABOVE ROOF,ETC.COMPLY W/SGC SECS.605.3, |
| | 608.3. |
| | |
| | SUBMIT CALCULATIONS FOR COMBUSTION AIR. |
| | COMPLY W/SGC SECS.402.4.4 |
| | |
| | INSTALLATION OF WATER HEATER ON ROOF |
| | SHALL COMPLY W/SGC SEC.405. |
| | |
| | |
| | |
| | |
| | |
| | CLEARLY SHOW EMERGENCY SHUT-OFF VALVE/ |
| | ELECTRONIC GAS VALVE ON GAS RISER. |
| | COMPLY W/NFPA 54 SEC.5.5.4. |
| | |
| | |
| | SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP. |
| | EQUIPMENT SHALL BE APPROVED PER SGC |
| | 402.1. |
| | |
| | ALL GAS VALVES SHALL BE ACCESSIBLE AND |
| | LOCATED PER SGC SEC.403.1.2.,INCLUDING |
| | ELECTRONIC GAS VALVE.(SEE SHT.K-3.1) |
| | |
| | SHT.K-2.1-NO WATER ABOVE 140 DEGREES |
| | SHALL DISCHARGE INTO THE DRAINAGE |
| | SYSTEM PER SPC SEC.807.3. |