Plan Review Details - Permit 00020850
Plan Review Stops For Permit 00020850
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-24 Cont ID  
Sent By bstaples Date 2000-02-28 Time 10:14 Rev Time 4.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. SHEET TS CORRECT THE FOLLOWING
 A.UNIT # IS NOT CORRECT ON PERMIT SHOULD
 BE #179.
 B. CONSTRUCTION IS TYPE II NOT 2C.
 C. OCCUPANCY TYPE IS SMALL ASSEMBLEY
 NOT A-3.
  
 2. PLANS LACK COMPLETE DEMINSIONS SEE
 SHEET A2-2 PLAN 10 AS AN EXAMPLE.
  
 3. SIGNS REQUIRE SEPERATE PERMITS.
  
 4. FLORIDA ENERGY SHEETS SEE 1997
 FLORIDA ENERGY CODE.
  
 5. EXTERIOR GLAZING: ALL EXTERIOR
 GLAZING SHALL MEET IMPACT RESISTANT
 REQUIREMENTS FOR LARGE MISSLE IMPACT.
 PROVIDE PRODUCT APPROVALS.
 ALL DOORS ON THE EXTERIOR SHALL MEET
 WIND LOAD REQUIREMENTS PROVIDE PRODUCT
 APPROVAL INFORMATION.
  
 4/24/00 REVISIONS REVIEWED FOR CODE
 COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-27 Cont ID  
Sent By dpalmer Date 2000-04-27 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2000-04-27 Time 18:59 Sent To  
Notes
2001-01-08 00:00:00**************NOTE *********************
  
 1)NOTE: NOTE ON PLANS FOR COLOR CODING
 OF FEEDERS PER LOCAL AMENDMENTS 215.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-25 Cont ID  
Sent By dpalmer Date 2000-02-25 Time 12:10 Rev Time 0.00
Received By dpalmer Date 2000-02-25 Time 12:10 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE:PLEASE SHOW THE COMPLETE LOAD
 CALCULATION. TO INCLUDE THE SQ.FT AND
 CONTINUOUS LOADS. ALL PER ART;220
  
 2)NOTE:PLEASE SHOW COMPLETE GROUNDING
 SYSTEM ON SERVICE.YOU SHOW GROUND WIRES,
 BUT PLEASE SHOW WHERE THEY ARE GOING.
 PER 250 AND 215-5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-05-15 Cont ID  
Sent By bstaples Date 2000-05-15 Time 12:01 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEENOTES ATTACHED TO PLANS M. CARSILLO
 5/11/00

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-02-28 Cont ID  
Sent By bstaples Date 2000-02-28 Time 10:27 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ATTACHED TO PLANS M. CARSILLO

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-04-24 Cont ID  
Sent By ndenmark Date 2000-04-24 Time 15:22 Rev Time 1.00
Received By ndenmark Date 2000-04-24 Time 15:21 Sent To  
Notes
2001-01-08 00:00:00PRIOR CONCERNS CORRECTED BY REVISION
 DATED3/10/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-04-24 Cont ID  
Sent By ndenmark Date 2000-02-23 Time 11:50 Rev Time 2.00
Received By ndenmark Date 2000-02-23 Time 11:50 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISION****************
  
 1) EQUIPMENT RACK TO HAVE MIN. 18" CLEAR
 ANCE BETWEEN ROOF SURFACE AND BOTTOM OF
 SUPPORT STRUCTURE OF STANDS (LOCAL CODE)
 2) EXHAUST TERMINATION FOR GREASE HOODS
 TO BE MIN. 40" ABOVE ROOF SURFACE 1997
 SMC 506.1
 3) SLOPE FOR GREASE DUCT TO BE MIN. 1"
 PER FOOT 1997 SMC 505.4
 4) OUTSIDE AIR INTAKE TO BE MIN. 10'
 FROM EXHAUST AIR OUTLET. PLAN SCALE SHOW
 LESS
 5) NEED SPECS ON CHILLED WATER PIPING
 MATERIAL. NOTE COPPER TO BE JOINED BY
 BRAZING 1997 SMC TABLE 1205
 6) SEPARATE PERMITS REQUIRED FOR HOODS,
 SUPPRESSION SYSTEMS, AND COOLER/FREEZERS

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-25 Time 11:09 Rev Time 2.75
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:001)SUBMIT COPY OF GAS TABLE UTILIZED IN
 DESIGN OF THE PIPING SYSTEM.COMPLY W/
 STANDARD GAS CODE SECS.1003.4.1,
 1003.4.2,1003.4.3
  
 2)SHT.P-1-UTILITIES DEMAND LEGEND NOTES
 250' RUN AND KITCHEN EQUIPMENT SCH.NOTES
 100'RUN FOR GAS PIPE.CLARIFY AND COMPLY
 W/SGC.
  
 3)SHT.P-4-GAS PIPING CANNOT PENETRATE
 STAIRWAY ENCLOSURE PER SBC SEC.1006.1.3,
 1006.1.3.1(SEE GAS REGULATOR ALSO.)
  
 4)COMPLY W/ATTACHED GAS REQS.
  
 5)SHOW PRESSURE DROP OF SYSTEM ON THE
 PLANS.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE.
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-05-19 Cont ID  
Sent By tlarge Date 2000-05-19 Time 16:57 Rev Time 2.50
Received By tlarge Date 2000-05-19 Time 16:57 Sent To  
Notes
2001-01-08 00:00:00PROVISO:WATER SUPPLY CONTROL SHALL
 COMPLY W/SPC SECS.610.4.1 & 610.4.2.
 (THERE ARE FIXTURES THAT CANNOT BE
 ISOLATED W/O SHUTTING DOWN THE ENTIRE
 SYSTEM.SEE SERVICE STATION,BAKERY,2ND.FL
 TOILET ROOMS,ETC.)
  
 SUBMIT DETAILS FOR VENT FOR WATER HEATER
 SHOW TYPE OF VENT(B,BW,ETC.)HEIGHT ABOVE
 HEATER,TERMINATION POINT,ETC.COMPLY W/
 SGC SECS.605.3,608.3,609,ETC.
  
 SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS FOR ALL GAS EQUIPMENT.EQUIPMENT
 SHALL BE LISTED/APPROVED BY A
 A NATIONALLY RECOGNIZED AGENCY.SGC SEC.
 402.1.
  
 ********NOTE:ALL PRECEEDING ITEMS SHALL
 BE CORRECTED PRIOR TO INSPECTION.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-04-30 Cont ID  
Sent By tlarge Date 2000-04-30 Time 09:01 Rev Time 5.50
Received By tlarge Date 2000-04-30 Time 09:01 Sent To  
Notes
2001-01-08 00:00:00PLANS SHALL BE REVIEWED AND APPROVED BY
 THE DEPT.OF BUSINESS AND PROFESSIONAL
 REGULATION PRIOR TO REVIEW BY THIS DEPT.
 PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 CLARIFY TYPE OF OCCUPANCY ON TITLE SHEET
 THERE IS NO "A-3"OCCUPANCY IN THE SBC.
 SBC 304.2.1.
  
 SUBMIT OCCUPANT LOAD BASED ON HABITABLE
 FLOOR SPACE PER SPC SEC.407.1.3.
 PLANS NOTE OCCUPANT LOAD AS 416 PERSONS-
 AND DO NOT COMPLY W/SPC TABLE 407 OR FLA
 STATUTE 553.141.FOR MIN.FIXTURE REQS.
  
 PLANS SHALL BEAR THE CITY PLACE LANDLORD
 APPROVAL STAMP PRIOR TO APPROVAL FROM
 THIS DEPT.
  
 SHOW INSIDE CLEAR DIMENSIONS (LXW) OF
 ACCESSIBLE TOILET ROOMS AND STALLS.
 COMPLY W/FACBC SECS.4.16,4.17,FIGURES#28
 & #30.TOILETS TO BE 18"FROM WALL,NOT 19"
  
 SHT.P-1-(INSULATION TABLE FOR WATER
 PIPING )-INSULATION THICKNESS FOR PIPING
 SHALL COMPLY W/FLA.ENERGY CODE TABLE
 4-11.(FOR PIPING 1" AND LESS MIN.THICK-
 NESS SHALL BE 1")
  
 WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC 610.4.1(THERE ARE FIXTURES THAT
 CANNOT BE ISOLATED W/O SHUTTING DOWN
 ENTIRE SYSTEM.REVIEW WATER RISER AND
 COMPLY.SEE SERVICE STATION ,BAKERY,2ND
 FLR.TOILET ROOMS,ETC.)
  
 FIXTURE UNIT LOAD FOR SANITARY AND
 GREASY WASTE SYSTEM SHALL COMPLY W/SPC
 TABLES 713.1,713.2.REVISE FIXTURE UNIT
 LOAD.
  
 SUBMIT DETAILS FOR GAS VENT ON WATER
 HEATER.INDICATE TYPE OF VENT,HEIGHT,ETC.
 COMPLY W/SGC SECS.605.3,608.3.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR GAS APPLIANCES.COMPLY W/SGC SEC.
 402.4.4.
  
 INSTALLATION OF WATER HEATER SHALL
 COMPLY W/SGC SEC.405.1.1.SUBMIT MANUF.
 SHEETS FOR WATER HEATER AND ALL OTHER
 GAS EQUIPMENT.SGC SEC.402.1.
  
 ALL GAS VALVES SHALL BE READILY ACCESS-
 IBLE PER SGC 403.1.2.PLANS SHOW VALVES
 BEHIND EQUIPMENT.
  
 SHT.K-2.1-NO WATER ABOVE 140 DEGREES
 SHALL DISCHARGE INTO THE DRAINAGE SYSTEM
 PER SPC SEC.807.3.(SEE WATER HEATER NOTE
  
 SHT.P-8-CLARIFY BTU LOAD OF GAS WATER
 HEATER.PLANS NOTE 1800 & 1852 CFH.
  
 ELEVATOR SUMP DRAIN IS NOT SHOWN ON
 WASTE PIPING RISER.DISCHARGE SHALL BE TO
 SANITARY SYSTEM NOT GREASY WASTE.IF
 ELEVATOR IS HYDRAULIC,DRAIN SHALL FIRST
 PASS THRU AN OIL INTERCEPTOR PRIOR TO
 DISCHARGE TO SANITARY SYSTEM PER SPC
 SEC.1004.1,1004.5,1004.8.
  
 A UNION IS REQD.DOWNSTREAM OF ELECTRONIC
 GAS VALVE TO ALLOW FOR REMOVAL/REPLACE-
 MENT.NFPA 54 SEC.5.5.4.
  
 GAS SYSTEM IS UNDERSIZED FOR THE TOTAL
 BTU LOAD AND DISTANCE FROM POINT OF
 DELIVERY PER SGC TABLE 305.4(A).
  
 PLEASE CALL 561-659-8096 EXT.8377 IF YOU
 HAVE ANY QUESTIONS.T.LARGE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-24 Time 17:15 Rev Time 5.00
Received By tlarge Date 2000-02-24 Time 17:15 Sent To  
Notes
2001-01-08 00:00:00******CONTINUATION OF PLUMBING COMMENTS
 SHT.P-8-CLARIFY CORRECT BTU LOAD OF
 WATER HEATER.(NOTED AS 1800 CFH AND ALSO
 1852 CFH.)
  
 MAX.TEMPERATURE OF HOT WATER TO REST-
 ROOMS SHALL BE 110 DEGREES PER FLA.
 ENERGY CODE SEC.412.1ABCD.2.3.2(2).
  
 SHT.P-9-WATER RISER SHALL CLEARLY SHOW
 ENTIRE SCOPE OF WORK(WATER RISER DOES
 NOT REFLECT ENTIRE 2ND FLR.)COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 THE MINIMUM PLUMBING FIXTURE REQS.SHALL
 COMPLY W/FLA.STATUTE 553.141.(3).
  
 PLANS SHALL BE SIGNED AND SEALED PER
 FLA.STATUTE 471 AND COUNTYWIDE AMENDMENT
 TO SPC SEC.104.2.3.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT (561)659-8026,EXT.8377.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-24 Time 12:44 Rev Time 6.50
Received By tlarge Date 2000-02-24 Time 12:44 Sent To  
Notes
2001-01-08 00:00:00PLANS SHALL BE REVIEWED AND APPROVED BY
 DEPT.OF BUSINESS AND PROFESSIONAL REG.
 PRIOR TO REVIEW BY THIS DEPT.PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 CLARIFY TYPE OF OCCUPANCY ON TITLE SHEET
 THERE IS NO "A-3" OCCUPANCY IN THE SBC.
 SBC 304.2.1.
  
 SUBMIT OCCUPANT LOAD BASED ON HABITABLE
 FLOOR SPACE PER SPC SEC.407.1.3.THE MIN.
 REQUIRED NUMBER AND TYPE OF PLUMBING
 FIXTURES SHALL COMPLY W/SPC. TABLE 407.
  
 CLEARLY SHOW THE REQD.WHEELCHAIR TURN-
 ING SPACE IN THE TOILET STALLS PER
 FACBC SEC.4.2.3.
  
 GREASE TRAP SHALL COMPLY W/CITY OF WPB
 UTILITIES REQS.CONTACT ROD COMPO AT(561)
 835-7423.
  
 CLEARLY SHOW SIZES OF ACCESSIBLE TOILET
 ROOMS AND HANDICAPSTALLS.COMPLY W/
 FACBC 4.16,4.17,FIGURE 28, FIG,30.(LXW)
  
 SHT.P-1(INSULATION TABLE FOR WTR.PIPING)
 INSULATION THICKNESS FOR PIPING SHALL
 COMPLY W/FLA.ENERGY CODE TABLE 4-11.
  
 SHT.P-2-DRAIN FROM BAKERY,BAR & SERVICE
 AREAS SHALL DRAIN TO THE GREASY WASTE
 SYSTEM,NOT THE SANITARY.SPC SEC.1004.1,
 1004.4.
  
 SUBMIT DETAIL OF DETERGENT PUMPS AND
 WATER CONNECTION THERETO.A BACKFLOW
 PREVENTION DEVICE SHALL BE INSTALLED ON
 THE WATER CONNECTION PER SPC SEC.606.1.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SECS.610.4.1,610.4.2.
  
 SHT.P-7-THE DISTANCE OF A WATER CLOSET
 TRAP FROM ITS VENT SHALL NOT EXCEED
 5 FT.PER COUNTYWIDE AMENDMENTS TO SPC
 TABLE 908.1,FOOTNOTE #2.
  
 SHT.P-7-FIXTURE BRANCHES AND WATER
 CLOSETS ARE NOT PERMITTED ON HORIZ.WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1,911.1.3.(SEE MEN'S AND
 WOMEN'S RESTROOM.)
  
 THE SANITARY RISER DOES NOT SHOW ALL
 PLUMBING FIXTURES.SUBMIT REVISED
 SANITARY RISER THAT CLEARLY REFLECTS
 ENTIRE SCOPE OF WORK TO BE PERFORMED.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
 (SEE WOMEN'S R.R., 3" SAN.TO 2ND.FLR.,
 2ND FLR. PLBG.,ETC.)
  
 FIXTURE UNIT LOAD SHALL COMPLY W/TABLE
 713.1,713.2.REVISE FIXTURE UNIT LOAD.
  
 WATER FILTRATION/TREATMENT SYSTEMS SHALL
 COMPLY W/SPC SEC.615.1,615.2.,NSF 42,53,
 58.SUBMIT MANUF.SHEETS.
  
 SUBMIT DETAILS ON GAS VENT FOR WATER
 HEATER.INDICATE TYPE OF VENT,HEIGHT
 ABOVE ROOF,ETC.COMPLY W/SGC SECS.605.3,
 608.3.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 COMPLY W/SGC SECS.402.4.4
  
 INSTALLATION OF WATER HEATER ON ROOF
 SHALL COMPLY W/SGC SEC.405.
  
  
  
  
  
 CLEARLY SHOW EMERGENCY SHUT-OFF VALVE/
 ELECTRONIC GAS VALVE ON GAS RISER.
 COMPLY W/NFPA 54 SEC.5.5.4.
  
  
 SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 EQUIPMENT SHALL BE APPROVED PER SGC
 402.1.
  
 ALL GAS VALVES SHALL BE ACCESSIBLE AND
 LOCATED PER SGC SEC.403.1.2.,INCLUDING
 ELECTRONIC GAS VALVE.(SEE SHT.K-3.1)
  
 SHT.K-2.1-NO WATER ABOVE 140 DEGREES
 SHALL DISCHARGE INTO THE DRAINAGE
 SYSTEM PER SPC SEC.807.3.