| Plan Review Stops For Permit 00020799 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-30 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-02-18 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
bstaples |
Date |
2000-03-30 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. OWNER NEEDS TO SIGN FLORIDA ENERGY | | | SHEETS, ALL COPIES.OK 3/30/00 WRS | | | 2. PROVIDE PRODUCT APPROVAL INFORMATION | | | ON ALL EXTERIOR WINDOWS AND DOORS. ALL | | | GLAZING SHALL BE IMPACT RESISTANT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
20:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
20:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHEETS E2.01 FOR GFI BRKR CIRCUIT ONLY | | | AND SHEET E9.01 FOR PANEL SCHEDULE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-26 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-26 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-29 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-29 |
Time |
12:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-08 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-08 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE:NEED TO LABEL ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. AS REQ`D BY 210-8-A-6 | | | | | | 2)NOTE:PLEASE CORRECT WIRE SIZE GOING TO | | | ALL PANELS. YOU SHOW #3 BEING PROTECTED | | | BY A 125 AMP BRKR. TABLE 310-16 75C | | | COLUMN,,,WIRE IS ONLY RATED FOR 100AMPS. | | | | | | 3)NOTE; YOU ARE SHOWING A/C LOAD AT 100% | | | THIS SEEMS TO BE THE DERATED LOAD??? | | | PLEASE SHOW SIZE OF THE ORIGINAL HEAT | | | STRIP.SEE AP-E8.01 | | | | | | 4)NOTE: PLEASE SHOW THE LOAD ON "HP" | | | AS BEING CONTINUOUS. | | | | | | PLEASE SUBMIT THE ABOVE INFORAMTION | | | FOR REVIEW AND APPROVAL.IF THERE ARE ANY | | | QEUSTIONS PLEASE CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-02-25 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-02-25 |
Time |
10:47 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE COMMENTS ATTACHED TO PLANS CARSILLO |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2000-07-29 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-29 |
Time |
07:56 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-29 |
Time |
07:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-06-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-06-24 |
Time |
10:37 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-06-24 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1.REVISION DETAIL 2 REFERS TO M307, NOT | | | INCLUDED IN THIS REVISION.THIS DETAIL | | | DOES NOT SHOW CHASE FOR DUCTS PASSING | | | THROUGH SLAB. TO BE PROTECTED PER SKETCH | | | ASK-2 FOR APPROVAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-06-16 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-16 |
Time |
08:48 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-06-16 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-03-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-03-08 |
Time |
07:46 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-03-08 |
Time |
07:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-10 |
Time |
22:17 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-08-10 |
Time |
21:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-06-26 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-26 |
Time |
15:07 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-06-26 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-06-15 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-15 |
Time |
06:23 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-06-15 |
Time |
06:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-03-30 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-30 |
Time |
14:17 |
Rev Time |
1.75 |
| Received By |
tlarge |
Date |
2000-03-30 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-26 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-26 |
Time |
14:37 |
Rev Time |
2.75 |
| Received By |
tlarge |
Date |
2000-02-26 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | ALL BATHROOMS IN THE COVERED DWELLING | | | UNIT SHALL COMPLY W/THE PROVISIONS OF | | | THE FAIR HOUSING ACT 24 CFR 100.205(C) | | | (3)(IV)REQ.#7(2) PARAGRAPH (A) OR (B). | | | CLEAR FLOOR SPACE SHALL BE PROVIDED AT | | | FIXTURES TO ALLOW A PERSON IN A WHEEL- | | | CHAIR OR OTHER MOBILITY AID USE OF THE | | | FIXTURES.CLEAR FLOOR SPACE SHALL BE | | | SHOWN ON THE PLANS AND DESIGNATE WHICH | | | OPTION OF REQUIREMENT #7(A OR B)IS BEING | | | USED. | | | | | | SHT.AP-A7.04-WOOD BACKING FOR GRAB BARS | | | ON LONG WALL OF TUB SHALL BE A MAX.OF 6" | | | ABOVE TUB.SEE FED.FAIR HOUSING ACT 24 | | | CFR 100.205. | | | | | | RELIEF LINES FROM EWH SHALL NOT BE | | | TRAPPED PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.507.8.4. | | | | | | HEATER PANS SHALL COMPLY W/SPC SEC. | | | 507.8.2. | | | | | | SUBMIT ENERGY CALCS.AND EF RATING OF EWH | | | PER FLA.ENERGY CODE SEC.103.2. | | | | | | SHOW FIXTURE UNIT LOAD ON SANITARY RISER | | | (STACKS AND HORIZONTAL DRAINS.)COMPLY W/ | | | SPC TABLES 714.1,714.2. | | | | | | SIZE ALL PORTIONS OF THE DWVSYSTEM. | | | (CHECK ALL RISERS-SIZES MISSING FROM | | | BUILDING DRAINS,BRANCHES,AND VENTS) | | | | | | THE CLEAR FLOOR SPACE PROVIDED AT SINKS | | | SHALL BE CENTERED ON THE BOWL PER FED. | | | FAIR HOUSING ACT 24 CFR 100.205 (C)(3) | | | (IV) REQ.#7(1). |
|
|