Plan Review Details - Permit 00020690
Plan Review Stops For Permit 00020690
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-21 Cont ID  
Sent By lsmith Date 2000-03-08 Time 16:47 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED FOLLOWING:
 1. WIND LOAD PER ASCE-7981997 SBCCI
 2. LOAD CALCULATIONS IMPOSED BY ANTENNA
 PER CHAPTER 16 SBCCI
 3. WILL NEED SEPARATE ROOF PERMIT PER
 NOTE ON S-4

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-05-09 Cont ID  
Sent By dpalmer Date 2000-05-09 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2000-05-09 Time 19:47 Sent To  
Notes
2001-01-08 00:00:00NOTES ON PLANS ABOUT ALL NEW MAINS TO
 BE GROUPED PER 230-72

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-04-13 Cont ID  
Sent By dpalmer Date 2000-04-13 Time 20:41 Rev Time 0.00
Received By dpalmer Date 2000-04-13 Time 20:41 Sent To  
Notes
2001-01-08 00:00:00************ UNSAT ********************
  
 1)NOTE: NEED TO PROVIDE DISCONNECT IN -
 LINE FROM GENERATOR TO TRANSFER SWITCH.
 AS PER 225-31
 ALSO MAINS MUST BE GROUPED PER 230-70/
 230-72 AND ALL MUST BE MARKED PER NEC.
 1 OF? 2 OF? ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-04-13 Cont ID  
Sent By dpalmer Date 2000-02-29 Time 06:41 Rev Time 0.00
Received By dpalmer Date 2000-02-29 Time 06:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By rturnque Date 2000-03-03 Time 08:51 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-02 Cont ID  
Sent By gjoyce Date 2000-03-02 Time 14:47 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***