Plan Review Details - Permit 00020683
Plan Review Stops For Permit 00020683
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-18 Cont ID  
Sent By dpalmer Date 2000-05-18 Time 18:34 Rev Time 0.00
Received By dpalmer Date 2000-05-18 Time 18:16 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: LOAD CALCULATION DOES NOT MEET
 ART 220 OF THE NEC . PLEASE CORRECT.
  
 2)NOTE: EQUIPMENT GROUNDING CONDUCTOR
 IS REQ`D FROM MAIN HOUSE IN CONDUIT WITH
 FEEDERS FOR PANEL. SIZE PER 250-122
  
 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BLDG. STEEL AS PER 250-50 AND
 ANY METAL COLD WATER PIPE AT DETACHED
 BLDG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-05 Cont ID  
Sent By dpalmer Date 2000-04-05 Time 11:51 Rev Time 0.00
Received By dpalmer Date 2000-04-05 Time 11:51 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: NEED TO HAVE MEANS OF DISCONNECT
 OF DETACHED STRUCTURE.ANY MORE THAN ONE
 CIRCUT.
 2)NOTE:NEED TO SHOW MORE DETAIL FOR
 FOUNTAIN. EXISTING ELEC?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-04-28 Cont ID  
Sent By lmartine Date 2000-04-28 Time 07:46 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-19 Cont ID  
Sent By tlarge Date 2000-05-19 Time 06:05 Rev Time 0.33
Received By tlarge Date 2000-05-19 Time 06:05 Sent To  
Notes
2001-01-08 00:00:00PROVISO:FILL LINE TO FOUNTAIN SHALL BE
 PROTECTED AGAINST BACKFLOW PER SPC SECS.
 601.5,606.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-04-04 Cont ID  
Sent By tlarge Date 2000-04-04 Time 14:16 Rev Time 0.30
Received By tlarge Date 2000-04-04 Time 14:16 Sent To  
Notes
2001-01-08 00:00:00SUBMIT INFO ON FOUNTAIN-TYPE OF PIPING,
 BACKFLOW PREVENTOR,ETC.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-05-19 Cont ID  
Sent By lmartine Date 2000-05-19 Time 13:17 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-04-28 Cont ID  
Sent By lmartine Date 2000-04-28 Time 07:47 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
 1]MINIMUM F.F.ELEVATION 7.5',FLOOD ZONE
 CERTIFICATE IS PROVIDED AND REQUIRED.
 2]SUBMIT DETAILS FOR FOUNTAIN FEATURE.
 3]PROVIDE INFORMATION FOR INTERIOR
 FINISHES.
 4]SUBMIT ROOF COVER TEST REPORT.
 5]COUNTY IMPACT FEES ARE REQUIRED.
 6]MUST PROVIDE MECHANICAL VENTILATION
 SYSTEM TO COMPLY WITH SECTION 411.4.2
 1997SBC.

Review Stop Z ZONING
Rev No 2 Status P Date 2000-03-31 Cont ID  
Sent By lmartine Date 2000-03-31 Time 16:14 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY DENNIS CAMBELL,3/31/00

Review Stop Z ZONING
Rev No 1 Status N Date 2000-04-27 Cont ID  
Sent By lmartine Date 2000-04-27 Time 16:14 Rev Time 0.00
Received By lmartine Date 2000-03-09 Time 11:30 Sent To  
Notes
2001-01-08 00:00:00DOES NOT MEET LANDSCAPEREQUIRMENTS
 ANEIL WAS CHECKING THE NOTES FOR CUSTOME