Plan Review Details - Permit 00020597
Plan Review Stops For Permit 00020597
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-02 Cont ID  
Sent By dpalmer Date 2000-05-02 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2000-05-02 Time 18:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 17:21 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 17:21 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: NEED TO SHOW EQUIPMENT GROUNDING
 CONDUCTOR REQ`D FROM MAIN TO PANEL.
 PLEASE SIZE PER 250-122
  
 2)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUT REQ`D BY 210-11-C-3 MUST
 BE #12 AND 20AMP.
  
 3)NOTE: PLEASE SHOW A/C EQUIPMENT AND
 THE REQ`D DISCONNECT BY 440-11 AND RECEP
  
 NEED TO SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-26 Cont ID  
Sent By jleech Date 2000-02-26 Time 13:43 Rev Time 0.35
Received By jleech Date 2000-02-26 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-11-17 Cont ID  
Sent By jleech Date 2000-11-17 Time 11:32 Rev Time 0.25
Received By jleech Date 2000-11-17 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-06-29 Cont ID  
Sent By tlarge Date 2000-06-29 Time 15:47 Rev Time 0.25
Received By tlarge Date 2000-06-29 Time 15:47 Sent To  
Notes
2001-01-08 00:00:00SUBMIT CLEAR AND LEGIBLE DIAGRAMS FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-02 Cont ID  
Sent By tlarge Date 2000-05-02 Time 05:58 Rev Time 0.33
Received By tlarge Date 2000-05-02 Time 05:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-19 Cont ID  
Sent By tlarge Date 2000-02-19 Time 07:28 Rev Time 0.33
Received By tlarge Date 2000-02-19 Time 07:27 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF PLUMBING FIXTURES ON
 SANITARY RISER DOESN'T CORRELATE W/FLOOR
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WATER CLOSET IN 2ND.FLR.M.B. NOT VENTED.
 SPC SEC.901.2.
  
 MAX.OF 4 FIXTURE UNITS PERMITTED ON 2"
 WET VENT PER SPC 911.1(1).(SEE 1ST.FLR.
 MASTER BATH)
  
 ONLY FIXTURE DRAINS PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.(SEE 1ST.FLR.M.B.)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By fknapp Date 2000-04-05 Time 09:53 Rev Time 4.00
Received By fknapp Date 2000-04-05 Time 08:40 Sent To  
Notes
2001-01-08 00:00:00 
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 OUTSWING DOOR WITH SIDELITE
 ARCH TRANSOMS
 CIRCLE WINDOW
 12'FIX WINDOW
 12'SLIDING GLASS DOOR
  
 2)PROVIDE STORM PANEL DRAWINGS THAT ARE
 SIGN, DATED AND HAVE RAISED SEAL AND
 IDENTIFY MOUNTING AND ANCHORS TO BE USED
  
 3)PROVIDE SPECIFICATIONS FOR 1 HR GLASS
 BLOCK.
  
 4)PROVIDE PRODUCT APPROVAL FOR ROOF
 COVERING UNDER SEPERATE PERMIT.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-14 Cont ID  
Sent By gjoyce Date 2000-02-14 Time 11:39 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***