Plan Review Details - Permit 00020596
Plan Review Stops For Permit 00020596
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-02 Cont ID  
Sent By dpalmer Date 2000-05-02 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2000-05-02 Time 18:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 17:05 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SHOW A/C EQUIPMENT AND
 DISCONNECT REQ`D BY 440-11. ALSO RECEPT.
  
  
 2)NOTE: PLEASE LIST ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUT(S)
 BY 210-11-C-3 MUST BE 20 AMP AND #12
  
 3)NOTE: NEED TO SHOW THE REQ`D EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-26 Cont ID  
Sent By jleech Date 2000-02-26 Time 12:46 Rev Time 0.25
Received By jleech Date 2000-02-26 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-06-29 Cont ID  
Sent By tlarge Date 2000-06-29 Time 15:45 Rev Time 0.25
Received By tlarge Date 2000-06-29 Time 15:45 Sent To  
Notes
2001-01-08 00:00:00SUBMIT CLEAR AND LEGIBLE DIAGRAMS FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-02 Cont ID  
Sent By tlarge Date 2000-05-02 Time 06:17 Rev Time 0.30
Received By tlarge Date 2000-05-02 Time 06:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-19 Cont ID  
Sent By tlarge Date 2000-02-19 Time 06:21 Rev Time 0.50
Received By tlarge Date 2000-02-19 Time 06:21 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF PLUMBING FIXTURES ON
 SANITARY RISER DOESN'T CORRELATE W/FLOOR
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WATER CLOSET IN 2ND.FLR.BATH NOT VENTED.
 SPC SEC.901.2.
  
 MAX.OF 4 FIXTURE UNITS PERMITED ON 2"WET
 VENT PER SPC SEC.911.1(1). (SEE 1ST.FLR.
 MASTER BATH)
  
 ONLY FIXTURE DRAINS PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.(SEE 1ST.FLR.M.B.)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-04-04 Cont ID  
Sent By fknapp Date 2000-04-04 Time 11:45 Rev Time 4.00
Received By fknapp Date 2000-04-04 Time 09:25 Sent To  
Notes
2001-01-08 00:00:00 
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 OUTSWING DOOR WITH SIDELITE
 ARCH WINDOWS
 CIRCLE WINDOW
 12'FIX WINDOW
 12'SLIDING GLASS DOOR
  
 2)PROVIDE STORM PANEL DRAWINGS THAT ARE
 SIGN,DATED AND HAVE RAISED SEAL AND
 IDENTIFY MOUNTING AND ANCHORS TO BE USED
  
 3)PROVIDE SPECIFICATIONS FOR 1 HR GLASS
 BLOCK.
  
 4)PROVIDE PRODUCT APPROVAL FOR ROOF
 COVERING UNDER SEPERATE PERMIT.
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-14 Cont ID  
Sent By gjoyce Date 2000-02-14 Time 11:36 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***