Plan Review Details - Permit 00020529
Plan Review Stops For Permit 00020529
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By lmartine Date 2000-02-24 Time 08:44 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-26 Cont ID  
Sent By dpalmer Date 2000-04-26 Time 09:01 Rev Time 0.00
Received By dpalmer Date 2000-04-26 Time 09:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-14 Cont ID  
Sent By dpalmer Date 2000-02-14 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2000-02-14 Time 16:36 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO **************
  
 NEED ALL THE INFORMATION BELOW BEFORE
 FIRST ROUGH ELECTICAL INSPECTION.
  
 1)NOTE:NEED TO SUBMIT PLANS SHOWING ALL
 BRANCH CIRCUT #`S WITH APNEL SCHEDULES
 AND LOAD CALCULATIONS.
  
 2)NOTE: SEE LABELED AREA FOR OUTLETS
 REQ`D BY LOCAL CODES.
  
 NEED TO SUBMIT FOR REVIEW AND APPROVAL
 BEFORE ROUGH!!! IF THERE ARE ANY
 QUESTIONS PLEASE CALL. 659-8096 EXT 8451
 OR 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-24 Time 09:18 Rev Time 0.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED W/PROVISO BY R.TURNQUIST ON
 2/17/OO.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By ndenmark Date 2000-02-24 Time 08:28 Rev Time 0.25
Received By ndenmark Date 2000-02-24 Time 08:28 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 EXISTING DUCT TO BE INSPECTED FOR CLEAN-
 LINESS AND CLEANED AND SANITIZED IF
 DEEMED NECESSARY
 PERMITS REQUIRED FOR HOOD AND SUPPRESSIO
 SYSTEM , SUBMIT PLANS WITH MECH PERMIT
 APPLICATION

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-05-02 Cont ID  
Sent By tlarge Date 2000-05-02 Time 13:42 Rev Time 0.25
Received By tlarge Date 2000-05-02 Time 13:42 Sent To  
Notes
2001-01-08 00:00:00GAS DRAWING.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-04-29 Cont ID  
Sent By tlarge Date 2000-04-29 Time 05:23 Rev Time 0.50
Received By tlarge Date 2000-04-29 Time 05:23 Sent To  
Notes
2001-01-08 00:00:00SIZING OF GAS SYSTEM SHALL COMPLY W/SGC
 TABLE 305.4(A).(SUPPLY LINE FROM METER
 SHALL BE 2 1/2".SHOW ALL CUT LENGTHS OF
 PIPE.)

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-24 Time 06:35 Rev Time 0.75
Received By tlarge Date 2000-02-24 Time 06:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-20 Time 10:08 Rev Time 0.50
Received By tlarge Date 2000-02-20 Time 10:08 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY,WATER,AND GAS ISOMETRICS
 SIGNED AND SEALED BY DESIGN PROFESSIONAL
 FOR ALL CHANGES MADE TO THESE SYSTEMS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT MANUF.SHEETS FOR ALL NEW GAS
 EQUIPMENT BEING INSTALLED.EQUIPMENT
 SHALL BE APPROVED PER NFPA 54 SEC.5.1.1
 AND EXISTING SYSTEM SHALL COMPLY W/NFPA
 54 SEC.5.1.2.(ADEQUACIES FOR COMBUSTION,
 VENTILATION,CLEARANCES,AND VENTING SHALL
 BE SUBMITTED.)