Plan Review Details - Permit 00020512
| Plan Review Stops For Permit 00020512 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-03-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-20 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-20 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF THE | | | MAIN DISCONNECTS. MAINS MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. PER | | | 110-9/110-10 | | | | | | 2)NOTE: PLEASE DRAW MAIN DISCONNECTS | | | NEXT TO METER ON PLANS 215-5 | | | | | | 3)NOTE:PLEASE INDICATE ON RISER DIAGRAM | | | EQUIPMENT GROUNDING CONDUCTOR REQ`D | | | AFTER THE FIRST MEANS OF DISC. SIZE PER | | | 250-122 | | | | | | 4)NOTE:IF COLD WATER PIPE IN HOUSE IS | | | GOING TO BE METAL THEN IT MUST BE | | | INCLUDED AS PART OF THE GROUNDING ELEC- | | | -TRODE SYSTEM. PER 250-50 | | | | | | 5)NOTE: PLEASE LIST ON PANEL SCHEDULE | | | THE REQ`D BATH(S) CIRCUT(S). MUST BE | | | 20AMP AND #12 AWG REQ`D BY 210-11-C-3 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-02-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-02-26 |
Time |
13:29 |
Rev Time |
0.35 |
| Received By |
jleech |
Date |
2000-02-26 |
Time |
13:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-19 |
Time |
07:17 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-02-19 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT SIGNED AND SEALED SANITARY RISER | | | FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-04-17 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-04-17 |
Time |
14:26 |
Rev Time |
4.00 |
| Received By |
fknapp |
Date |
2000-04-17 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | ***************DENIED******************* | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE SOIL REPORT. | | | | | | 2)PROVIDE CURRENT DESIGN CERTIFICATION | | | FOR BUILDING CODE COMPLIANCE. | | | | | | 3)PROVIDE OWNER/AGENT SIGNATURE ON | | | ENERGY CALCULATIONS. | | | | | | 4)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR ALL | | | EXTERIOR DOOR ASSEMBLIES AND ALL ARCH | | | TRANSOMS. | | | | | | 5)BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO.,THE PERMIT PLANS STAMPED BY | | | THEM AND THE RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-02-16 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-02-16 |
Time |
10:42 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|