Plan Review Details - Permit 00020469
Plan Review Stops For Permit 00020469
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-14 Cont ID  
Sent By dpalmer Date 2000-03-14 Time 15:26 Rev Time 0.00
Received By dpalmer Date 2000-03-14 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-21 Cont ID  
Sent By dpalmer Date 2000-02-21 Time 11:05 Rev Time 0.00
Received By dpalmer Date 2000-02-21 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00************ UNSAT ********************
  
 1)NOTE: NEED TO SHOW GROUNDING ELECTRODE
 SYSTEM. TO BLDG.STEEL OF NEW ADDITION.
 NEEDS TO GO TO COLD WATER PIPE AND
 GROUND ROD. PER 250-81
  
 2)NOTE: 1 3/4 CONDUIT IS NOT A STANDARD
 SIZE. PLEASE CORRECT.
  
 3)NOTE:NEED TO SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS. MAIN MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. AS REQ`D BY
 ART:110-9/110-10. 215-5
  
 4)NOTE: PLEASE CHECK LOAD CALCULATIONS,,
 YOU SHOW ONLY ONE SMALL APPLIANCE CIRCUT
 ???? TWO REQ`D BY CODE.
 WHAT IS BEING USED FOR A/C, HEAT???
 IF THERE IS CENTRAL AIR THEN IT IS TO BE
 CALCUALTED.
 ALSO 40% OF 6553 IS NOT 262. PLEASE
 CORRECT THIS FIGURE FOR LOAD.
 IF THERE ARE INDIVIDUAL WALL A/C UNITS,
 THEN FIGURE NAMEPLATE RATINGS.
  
 NEED TO HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-02-23 Cont ID  
Sent By ndenmark Date 2000-02-23 Time 12:26 Rev Time 0.33
Received By ndenmark Date 2000-02-23 Time 12:26 Sent To  
Notes
2001-01-08 00:00:00NO MECH INCLUDED FOR REVIEW SUBMIT INFO
 WITH MECH PERMIT APPLICATION PRIOR TO
 ANY WORK BEING DONE

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-22 Cont ID  
Sent By tlarge Date 2000-02-22 Time 06:44 Rev Time 0.50
Received By pschmitz Date 2000-02-22 Time 06:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-03-14 Cont ID  
Sent By lsmith Date 2000-03-14 Time 16:44 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-14 Cont ID  
Sent By gjoyce Date 2000-02-14 Time 11:25 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***