Plan Review Details - Permit 00020361
Plan Review Stops For Permit 00020361
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-15 Cont ID  
Sent By dpalmer Date 2000-03-15 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2000-03-15 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-08 Cont ID  
Sent By dpalmer Date 2000-03-08 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2000-03-08 Time 20:17 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 NOTES ON PLANS
 PLEASE CORRECT PANEL SCHEDULE.
 CORRECT WIRE SIZES, AND LOAD TO CORRELAT
 -E WITH BRKRS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-26 Cont ID  
Sent By jleech Date 2000-02-26 Time 12:08 Rev Time 0.25
Received By jleech Date 2000-02-26 Time 12:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-11 Cont ID  
Sent By tlarge Date 2000-02-11 Time 07:15 Rev Time 0.33
Received By tlarge Date 2000-02-11 Time 07:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-04-14 Cont ID  
Sent By rmcdouga Date 2000-04-14 Time 09:26 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 1)PROVIDE PRODUCT APPROVALS WITH
 SPECIFIC ANCHORS TO BE USED FOR STORM
 PANELS PRIOR TO INSTALLATION

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By jcaloger Date 2000-03-20 Time 17:20 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00DESIGN COMPLIANCE FORM SPECIFYS SBC 1997
 THE NOTES ON PLAN S-2.1 SPECIFYS ASCE 7/
 93.CLARIFY WHICH DESIGN CRITERIA WAS
 USED.NOTE THAT ASCE 7/93 IS INVALID
 EDITION & ASCE 7/95 IS THE VALID CRITERI
 ALSO NOTE THAT ASCE 7/95 CLASSIFYS OUR
 LOCATION AS A 145 MPH ZONE. PLAN C1 SPEC
 SBC FOR WIND, S2-1 SPECIFYS ASCE 7-95 ?
  
 THERE ARE NOTES ON THE PLAN THAT SPECIFY
 THAT RATIONAL ANALYSIS WAS USED IN THE
 DESIGN.CLARIFY HOW THE WIND PRESSURES
 WERE DETERMINED USING THIS METHOD OR HOW
 IS THIS USED FOR THE DESIGN CALCULATIONS
  
 DESIGN PARAMETERS SPECIFYS REQUIRING A
 2500 PSF SOIL BEARING PRESSURE AND ON
 PLAN S1 2000 PSF IS SPECIFIED.CLARIFY
  
  
 THE DESIGN COMPLIANCE FORM SPECIFYS A
 MEAN ROOF HEIGHT OF 15 FEET.I CALCULAT
 THE MEAN HT TO BE 16.5 FT. CLARIFY AND
 RECALCULATE ALL UPLIFTS.
  
  
 PLAN S-2.1 , ROOF TRUSS SUPERLOADS BOX
 SPECIFYS A BASIC WIND PRESSURE OF 26.3.
 THIS PRESSURE DOES NOT COINCIDE WITH THE
 PRESSURES IN TABLE 1606.2A SBC FOR A
 MEAN ROOF HEIGHT OF 15 FEET. THIS MAY
 BE FROM ASCE 7, BUT THE DESIGN COMPLIANC
 FORM SPECIFYS SBC.CLARIFY
  
 PROVIDE THE CALCULATIONS FOR ATTACHING
 THE ROOF TILES AS PER THE PRODUCT
 APPROVAL, SEE TABLE 2
  
 THE DESIGN COMPLIANCE FORM AND THE PLANS
 ARE REQUIRED TO HAVE THE EXACT ADDRESS
 ON BOTH.
  
 PROVIDE ENERGY CALCULATION FORM 600

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-10 Cont ID  
Sent By gjoyce Date 2000-02-10 Time 10:11 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***