| Plan Review Stops For Permit 00020337 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-12-04 |
Time |
12:27 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-12-04 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | STOREFRONT SHOP DRAWINGS AND PRODUCT | | | APPROVALS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-12-04 |
Time |
11:35 |
Rev Time |
3.00 |
| Received By |
drunnels |
Date |
2000-12-04 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION #15 OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-10-31 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-31 |
Time |
08:39 |
Rev Time |
8.00 |
| Received By |
drunnels |
Date |
2000-10-31 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. SUBMIT DETAIL FOR WALL BETWEEN | | | CORRIDORS 322 & 322B |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-30 |
Time |
12:09 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-30 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.SHEET A1.3 INDICATES TWO(2) AUDITORUIM | | | 18 | | | 2.REVISE "EGRESS LOAD-LEVEL 3" TABLE TO | | | REFLECT OCCUPANT CHANGES TO AUDITORUIM | | | 15 TO 18 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-04-07 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-04-07 |
Time |
08:50 |
Rev Time |
20.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. NO MECHANICIAL PERMITS OR WORK IS | | | COVERED BY THIS PERMIT. | | | 2. SMOKE DETECTORS SHALL BE INSTALLED IN | | | ATRUM AS PER 1997 SBC, SECTION 414.6.1&2 | | | 3. INCREASE THE FIRE RATING FROM ROOM | | | 120 TO EXIT 113B FROM ONE TO TWO HOURS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-12-14 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-12-14 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-09-27 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-09-27 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | RISER DIAGRAM NOTES ON PAGE E-14 SHOW 7 | | | SETS OF 500 KCMIL WIRE FEEDING MSB AT 75 | | | DEGREES "C" WIRE DOES NOT MEET CODE, IF | | | YOU ARE USING THE 90 DEGREE COLUMN THEN | | | SHOW LISTING FOR 90 DEGREE "C" ON THE | | | TERMINATIONS PER 110-14C2 | | | | | | LOAD CALCULATION FOR MSB STILL SHOWS NO | | | LOAD FOR FIRE PUMP IT MAY NOT BE FED BY | | | MAB BUT THE CONDUCTORS THAT FEED MSB | | | ALSO FEED THE FIREPUMP!!!!!!!!!!!!!!!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-08-29 |
Time |
13:27 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2000-08-29 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION #14 ONLY A DISC. TO TRANSF, | | | SEE REVSION 6/1/2000 FOR REMAINING | | | COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-06-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-06-01 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
0200-06-01 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1-MSB CALC DOES NOT SHOW ANY LOAD FOR TH | | | FIRE PUMP! | | | 2-MSB LOAD CALC SHOWS LOADS FOR THE | | | INDIVIDUAL PANEL, BUT THE LOAD ON THE | | | PANELS DOES NOT MATCH WHAT IS SHOWN ON | | | MSB CALC.215-5 | | | 3-PLAN CALLS FOR 9 4"PIPES FOR THE SERVI | | | BUT RISER SCHEDULE SHOWS 6 PLEASE FIX! | | | 4-RISER DIAGRAM STILL SHOWS NO DISCONNEC | | | AT THE TRANSFER SWITCH FOR THE EMERG. | | | FEED FROM THE GENERATOR, MAIN AT GEN. | | | TO REMOTE FROM THE OTHER MAINS IN THE | | | GEAR ROOM. | | | 5-NO PANEL SCHEDULES SHOWN FOR CCA1 THRU | | | CCA4 PANELS AND ALSO CG PANEL.THERE | | | ARE NO LOADS SHOWN ON THE DRAWINGS FOR | | | PANEL CG? | | | 6-FROM DP1 AND DP2 THE PLAN SHOWS EACH | | | FEEDING A SET OF PANEL THAT ARE LISTED | | | AS CCA1 THRU CCA4 PLEASE CHANGE ON SET | | | SO NOT CONFUSE THE INSTALLER OR INSP. | | | 7-ML"X" PANELS IN EACH SPACE SHOWS A #12 | | | WIRE ON A 60A BREAKER?ALSO SHOWS 3 | | | #6'S FEEDING A WIRE WAY, WHAT KIND OF | | | LOAD IS THIS? | | | 8-THE 300KVA TRANSF. SHALL COMPLY WITH | | | 450-21B EXP.1&2! | | | 9-PAGE E1 SHOWS THE FIRE PUMP TO BE 25HP | | | RISER SHOWS 100HP!GENERATOR AT 150KW | | | AND RISER SHOWS 230KW? | | | 10-EDP LOAD CENTER SHOWS LOADS FOR THE | | | INDIVIDUAL PANELS DIFFERENT THAN WHAT | | | IS SHOWN AT THE PANEL CALCS. SHOW HOW | | | THIS WAS DONE.SEE 215-5 FOR WHAT IS | | | NEEDED!!!!!!!! | | | 11-EMS SYSTEM ISTHIS BEEN DELETED NEW PG | | | 13 SHOWS NO LOADS!!!!!!!!!!!! | | | 12-800AMP MAIN FOR FIRE PUMP CAN NOT BE | | | MOUNTED ON THE MAIN SWITCH GEAR, IT HA | | | TO BE REMOTE!!!!!!!!!!!!!!!!!!!!!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-01 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-08-14 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE: PLEASE SEE ORIGINAL NOTES ATTACH | | | -ED. NOTE THAT A DISCONNECT IS REQ`D | | | INLINE FROM GENERATOR TO TRANSFER SWITCH | | | AS PER 230-70-A AND MUST BE GROUPED,230- | | | 72. PLEASE REVISE AND SUBMIT FOR REVIEW | | | BEFORE ROUGH ELECTRICAL INSPECTION. | | | NOTE THE REQ`MENTS OF 230-70-B | | | | | | 2)NOTE; ALSO PLEASE INDICATE ALL THE | | | RATINGS OF TRANSFORMERS OVER 112 1/2 KVA | | | SEE 450-21-B FOR INSTALLATION REQ`MENTS. | | | INDICATE THIS ON PLANS 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPEC- | | | -TION. IF THERE ARE ANY QUESTIONS PLEASE | | | CALL (561) 659-8096 EXT 8372/8451 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-02-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-02-23 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-02-23 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1- MAIN SWITCH GEAR ROOM NEEDS TO COMPLY | | | WITH 110-16 FOR WORKING CLEARANCES, | | | | | | 2- ROOM MEETS CODE BUT IF SOMETHING IS | | | ADDED OR MOVED IT COULD BECOME A | | | PROBLEM. | | | | | | 3- PAGE E-14 TRANSFER SWITCH HAS NO DISC | | | ON THE LINE SIDE IN THE GEAR ROOM. | | | MAINS ARE TO BE GROUPED ONE ON THE | | | 1ST AND THE REST ON THE SECOND IS TO | | | REMOTE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2000-11-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-29 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-29 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-27 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-27 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-29 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-29 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) CORRIDOR 301C TO BE FIRE RATED FOR | | | AT LEAST ONE HOUR FROM STORAGE ROOM 301A | | | 2) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS IN THE | | | PREMIER BAR. | | | 3) ENSURE THAT EMERGENCY LIGHTING IS | | | PROVIDED IN THE BAR AREA. | | | 4) NO COOKING THAT PRODUCES SMOKE OR | | | GREASE LADEN VAPORS WILL BE ALLOWED IN | | | PREMIER BAR WITHOUT THE PRESENCE OF | | | A HOOD, DUCT AND EXTINGUISHING SYSTEM. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-04-19 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-02-24 |
Time |
10:10 |
Rev Time |
5.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED MIKE CARSILLO 2/22/00 SEE NOTES | | | ON PLANS. | | | RELEASED WITH CONDITIONS SEE LETTER M. | | | CARSILLO ATTACHED TO PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
P |
Date |
2000-12-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-07 |
Time |
09:44 |
Rev Time |
3.00 |
| Received By |
ndenmark |
Date |
2000-12-07 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION 15 AND 16 SHEETS M-1,2,4 AND 5 | | | AS STAMPED AND DATED 12-7-00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
F |
Date |
2000-10-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-28 |
Time |
12:39 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-10-28 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION (15) DATED 9/20/00 DENIED | | | | | | 1. 1997 SMC 501.3 THE AIR DISCHARGED BY | | | EVERY MECHANICAL EXHAUST SYSTEM SHALL BE | | | DISCHARGED OUTDOORS. EXHAUSTING AIR INTO | | | AN ATTIC OR CRAWL SPACE SHALL BE PROHIB- | | | ITTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2000-08-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-28 |
Time |
15:12 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-08-28 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | LIFESAFETY AND FLOOR PLAN A 1.3 DATED | | | 8/18/00 SHOW RATED WALL ADDITION TO | | | PREMIER ROOM. NEED MECHANICAL PLANS | | | SHOWING LOCATION AND SPEC OF FIRE DAMPER | | | REQ'D TO PROTECT OPENINGS FOR DUCTS THRU | | | WALL. | | | SUBMIT PRIOR TO INSPECTION OF THIS | | | SYSTEM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-07-31 |
Time |
13:58 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-07-31 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED FOR MECHANICAL RESPECTIVE OF THE | | | PLAN TO START UP BY STAGES OF THE AIR | | | CONDITIONING AND PERMANENT POWER FOR | | | MUVICO | | | | | | AFTER REVIEWING THE COMMENTS BY THE FIRE | | | PLAN REVIEW AND ELECTRICAL PLAN REVIEW | | | THE MECHANICAL ASPECTS OF THIS PROPOSED | | | STARTUP ARE DENIED. | | | THE PERMANENT POWER AND AIR CONDITIONING | | | SHOULD NOT BE ALLOWED UNTIL FIRE ALARM | | | AND FIRE SPRINKLER SYSTEMS ARE IN PLACE | | | ANDFUNCTIONAL. THIS WAS ADDRESSED AT | | | TIME OF THE ORIGINAL MEETING DISCUSSING | | | THIS DEPARTMENTS REQUIREMENTS PRIOR TO | | | PERMANENT POWER BEING RELEASED | | | GENERALLY THERE IS NO PROBLEM WITH THE | | | PROPOSED PHASING OF MECHANICAL SYSTEMS | | | ONCE THE ISSUES FROM FIRE AND ELECTRICAL | | | ARE ADDRESSED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2000-07-12 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-07-12 |
Time |
08:19 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-07-12 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ********DENIED************************* | | | | | | 1) REVISION 8 INDICATES UTILIZING GYP. | | | BD. ENCLOSURE AS AIR PLENUM ELIMINATING | | | DUCT AND SMOKE FIRE DAMPERS AS INDICATED | | | ON MECH REVISION 6. | | | 2)1997 SBC 705.2.2 REQUIRES SHAFT ENCLOS | | | URES AT ALL PENETRATIONS OF FLOOR OPEN- | | | INGS. PROVIDE SHAFT DETAIL INCLUDING | | | RATING FOR ABOVE ENCLOSURES | | | 3) BLDG REVISION 8 SAYS SEE MECH DRAWING | | | NO MECHANICAL DRAWINGS INCLUDED WITH | | | THIS REVISION. MECHANICAL REVISION REQ'D | | | TO PROVIDE COMPLETE REVIEW OF THIS | | | CHANGE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2000-06-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-06-05 |
Time |
14:41 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-06-05 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FAILED | | | | | | 1) SLOPE FOR GREASE DUCT MIN. 1" PER 12" | | | PER 1997 SMC 505.4 | | | 2) PROVIDE SPECIFIC DETAIL FOR KITCHEN | | | DUCT AND HOODS AT TIME OF PERMIT APPLICA | | | TION FOR HOOD INSTALLATION PRIOR TO ANY | | | WORK ON HOOD OR DUCT SYSTEM | | | 3) EXHAUST DUCT TO BE RUN IN ENCLOSURE | | | DEDICATED TO SINGLE EXHAUST DUCT AND FOR | | | NO OTHER PURPOSE | | | 4) MIN CLEARANCE FROM DUCT TO INSIDE OF | | | ENCLOSURE IS 6" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2000-05-12 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-05-12 |
Time |
15:02 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-05-12 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FIRE REVIEW COMMENTS TO BE ADDRESSED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
A |
Date |
2000-05-12 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-05-01 |
Time |
14:29 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-05-01 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PREVIOUS COMMENTS ABOUT SHAFT DETAIL NOT | | | ADDRESSED | | | NEED SHAFT DETAILS SHOWN | | | ACCEPTED BY REVISION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2000-04-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-04-04 |
Time |
07:31 |
Rev Time |
2.00 |
| Received By |
ndenmark |
Date |
2000-04-04 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | MECHANICAL REMOVED FROM THIS PLAN REVIE | | | DENIED: | | | 1) STILL NEED SHAFT DETAIL FOR BATHROOM | | | EXHAUST AND AIR CONDITIONING DUCT SYSTEM | | | 2) SHAFT DETAIL FOR PROJECTORS DOES NOT | | | SHOW PROTECTION OF SHAFT AT BOTTOM OF | | | SHAFT AT LEVEL 3 FLOOR, PROVIDE DETAIL | | | OF SHAFT PROTECTION AT BOTTOM OF SHAFT | | | PER 1997 SMC 601.1.2.2 AND 610.4 | | | 3) PLEASE SPECIFY DUCT MATERIAL FOR | | | PROJECTION EXHAUST DUCT | | | 4) SUPPY AIR DUCT FOR ATRIUM EXHAUST | | | SYSTEM HAS FIRE DAMPERS. PROVIDE INFOR- | | | MATION ON FIRE DAMPERS,I.E CAN THESE BE | | | REMOTELY OPERATED TO OVERIDE POSITION? | | | IF THESE DAMPERS SHUT THE REQUIRED | | | AMOUT OF MAKE UP AIR WILL NOT BE PROVIDE | | | CREATING A NEGATIVE PRESSURE ON THE | | | ATRIUM. THIS ISSUE NEEDS TO BE ADDRESSED | | | AND RESOLVED AS PART OF THE ATRIUM | | | EXHAUST SEQUENCE OF OPERATION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2000-04-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-02-17 |
Time |
11:18 |
Rev Time |
16.00 |
| Received By |
ndenmark |
Date |
2000-02-17 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | MECH REMOVED FROM PRIMEDENIED******* | | | 1) PROVIDE SHAFT DETAIL FOR PROJECTOR | | | EXHAUST SYSTEMS | | | 2) PROVIDE INFORMATION ON CODE REQUIRED | | | BACKDRAFT DAMPERS FOR EXHAUST FANS | | | 3) PROJECTOR EXHAUST DUCT DETAIL SHOWS | | | FLEXABLE METAL DUCT. 1997 SBC 403.3.8.1 | | | DOES NOT ALLOW FLEX DUCT EXCEPT AT CONN- | | | ECTION TO PROJECTOR | | | 4) VARIABLE OCCUPANCY NOT ALLOWED FOR | | | THE THEATERS. 50% REDUCTION IS NOT A | | | REALISTIC EXPECTATION FOR OCCUPANCY FOR | | | THIS PROJECT | | | 5) LOCAL CODE REQUIRES 18" MIN. CLEARANC | | | BETWEEN ROOF SURFACE AND BOTTOM OF SUPP- | | | ORT STRUCTURE FOR CONDENSING UNITS | | | 6) PROVIDE DETAIL FOR SHAFT ENCLOSURES | | | TO SHOW COMPLIANCE WITH 1997 SMC AND | | | NFPA 96 | | | 7) PROVIDE SEQUENCE OF OPERATION FOR | | | ATRIUM EXHAUST SYSTEM | | | 8) PROVIDE LOCATION AND ACCESS TO DUCT | | | SMOKE DETECTORS TO SHOW COMPLIANCE WITH | | | 1997 SMC AND NFPA 90A | | | 9) PROVIDE AIR BALANCE SCHEDULE FOR | | | BUILDING TO SHOW COMPLIANCE WITH 1997 | | | SMC 501.2 | | | ABOVE INFORMATION REQUIRED TO PROVIDE | | | REVIEW OF THIS PROJECT. INSUFFICIENT | | | INFORMATION INCLUDED FOR REVIEW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
P |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-11 |
Time |
17:25 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
F |
Date |
2000-09-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-25 |
Time |
16:16 |
Rev Time |
2.75 |
| Received By |
pschmitz |
Date |
2000-09-25 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)REVISIONS THAT INCLUDE THE BAR AREA | | | CANNOT BE REVIEWED UNTIL 2 SETS OF PLANS | | | FOR THE ENTIRE BAR AREA ARE ROUTED TO | | | THE DEPT.OF BUSINESS REGULATION.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.101.4.7. | | | | | | 2)THE WATER RISER DIAGRAM IS LACKING | | | PIPE SIZES IN AREAS.PLEASE REVIEW THE | | | RISER DIAGRAM AND MAKE ALL NECESSARY | | | ADJUSTMENTS.COUNTYWIDE AMENDMENTS TO SPC | | | 104.2.1. | | | | | | 3)SHUT-OFF VALVES ARE REQD.ON THE WATER | | | DISTRIBUTION BRANCH MAINS PER SPC SEC. | | | 610.4.2. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-30 |
Time |
16:51 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-08-29 |
Time |
19:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)PLANS SHALL BE REVIEWED AND APPROVED | | | BY THE DEPT.OF BUSINESS REGULATION | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 101.4.7. | | | | | | 2)SHT.P7.1-PREMIER BAR AREA-PLAN VIEW | | | SHOWS A FLOOR SINK AND THE SANITARY | | | RISER SHOWS A HAND SINK.CLARIFY. | | | | | | 3)SHT.P8-SEE REVISION DELTA 14-SHOW | | | LOCATION OF THIS PIPING ON THE PLAN | | | VIEW.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | 4)SHT.P8-PREMIER BAR AREA-SIZE ALL | | | SECTIONS OF THE DWV SYSTEM.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 5)CONTACT R.COMPO W/CITY OF WPB | | | UTILITIES FOR APPROVAL OF WASTE FROM | | | ELEVATORS TO SANITARY SYSTEM.CALL | | | 561-835-7423. | | | | | | 6)SHT.P8-SHOW LOCATION OF TERMINATION | | | POINT OF 3"DRAIN FROM OIL INTERCEPTOR. | | | | | | 7)TWO WAY CLEANOUTS ARE REQD.ENTERING | | | AND LEAVING INTERCEPTORS.SPC SEC.710.4. | | | | | | 8)WATER HEATERS SHALL BE READILY | | | ACCESSIBLE.SPC 507.1. | | | | | | 9)SHT.P9.1-WATER SUPPLY CONTROL SHALL | | | COMPLY W/SPC SEC.610.4.2.(VALVES ARE | | | REQD.ON THE BRANCH LINES.) | | | | | | 10)CLEARLY SHOW THE LOCATIONS OF THE | | | INTERCEPTORS ON THE PLANS.SPC 104.2.1. | | | | | | 11)CLEARLY LABEL RISERS,STACKS ,ETC.FOR | | | IDENTIFICATION AND LOCATION.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2000-06-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-28 |
Time |
16:25 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-06-28 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT MANUF.SHEETS/DETAIL OF OIL | | | INTERCEPTOR.SPC SEC.1004.2. | | | | | | CLEARLY IDENTIFY SPACE/LOCATION OF OIL | | | INTERCEPTOR.INTERCEPTOR SHALL BE | | | ACCESSIBLE.SPC SEC.1004.8. | | | | | | SUBMIT SANITARY AND WATER ISOMETRICS FOR | | | THE CHANGES TO THE SYSTEMS.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | SHT.P-7-INDICATE THE FLOOR LEVEL OF | | | THE STRUCTURE FOR THESE CHANGES.SPC SEC. | | | 104.2.1. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.PROVIDE FIXED LADDER | | | OR RELOCATE WATER HEATER TO FLOOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-05-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-16 |
Time |
16:43 |
Rev Time |
2.75 |
| Received By |
tlarge |
Date |
2000-05-16 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *******************PROVISO************** | | | | | | THE LAYOUT OF THE GREASY WASTE SYSTEM ON | | | THE PLAN VIEW ON SHT.P-1 DOESN'T CORR- | | | ELATE W/THE SANITARY RISER ON SHT.P-8. | | | | | | THE SIZE OF THE GREASE TRAP SHALL BE | | | APPROVED BY THE CITY OF WEST PALM BEACH | | | UTILITIES.CONTACT ROD COMPO AT | | | (561)835-7423.SUBMIT APPROVAL FORM FROM | | | UTILITIES. | | | | | | DISCHARGE FROM ELEVATOR SUMPS SHALL | | | CONNECT TO THE SANITARY SYSTEM. | | | | | | WATER RISER-OVER 4 FIXTURE CONNECTED TO | | | 1/2"H.W.LINE.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.607.7. | | | | | | LINE SIZES ARE LACKING ON THE WATER | | | RISER AND STORM RISER. | | | | | | SHT.8.1-10"STORM DRAIN DRAINING INTO 8" | | | LINE.SEE RISER ST-5.SPC 709.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-04-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-20 |
Time |
11:37 |
Rev Time |
6.50 |
| Received By |
tlarge |
Date |
2000-04-20 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | REVISED DRAWINGS SHOWING THE FOLLOWING | | | CORRECTIONS SHALL BE SUBMITTED PRIOR TO | | | ROUGH PLUMBING INSPECTION. | | | | | | 1.)FLOORS AND WALLS IN TOILET ROOMS AND | | | RESTROOMS SHALL BE NONABSORBENT MATERIAL | | | TO A HEIGHT OF 4'PER SBC SEC.1204.2. | | | (PLANS NOTE PAINT BUT NOT THE TYPE.) | | | | | | 2.)PLUMBING PLANS REFER TO DRAWING | | | MUV-CIT2.SUBMIT DRAWING FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 3.)THE LAYOUT OF THE GREASY WASTE SYSTEM | | | ON SHT.P1 DOESN'T CORRELATE W/SHT.P8. | | | | | | 4.)SHT.P1-THE 6"SANITARY LINE IS DRAIN- | | | ING INTO A 4" LINE.COMPLY W/SPC SEC. | | | 709.1 | | | | | | 5.)SHOW SQ.FOOT AREA DRAINED BY EACH | | | DD,RD,& GD ON THE STORM WATER RISER. | | | COMPLY W/SPC TABLES 1108.1,1108.2. | | | | | | 6)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC SEC.610.4.1,610.4.2. | | | | | | 7)WATER RISER LACKS PIPE SIZES.COMPLY W/ | | | W/SPC TABLE 607.1. | | | | | | 8)CLEARLY SHOW CONTINUATION POINTS OF | | | SANITARY SYSTEM TO UPPER LEVELS.THE | | | EXTENSIONOF THE SOIL,WASTE AND VENT | | | SYSTEMTO THE UPPER FLOORS IS VAGUE. | | | COMPLY W/SPC 104.2.1. | | | | | | 9)THE SIZE OF THE GREASE TRAP SHALL BE | | | APPROVED BY THE CITY OF WEST PALM BEACH | | | UTILITIES.CONTACT ROD COMPO AT | | | (561)835-7423. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-04 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-04-04 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLANS SHALL BE REVIEWED AND APPROVED BY | | | THE PALM BEACH COUNTY HEALTH DEPT.PRIOR | | | TO REVIEW BY THIS DEPT.PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.101.4.7. | | | | | | FLOORS AND WALLS TO A HEIGHT OF 4'SHALL | | | BE NONABSORBENT MATERIAL.SHT.ID-5.1. | | | NOTES PAINT,BUT NOT THE TYPE.COMPLY W/ | | | SBC 1204.2.(SEE RMS.113,113A.) | | | | | | PLANS SHALL BEAR THE CITY PLACE LANDLORD | | | STAMP PRIOR TO REVIEW BY THIS DEPT. | | | | | | PLBG.SHEETS REFER TO CIVIL DRAWINGS FOR | | | CONTINUATION OF WATER,SEWER,& STORM. | | | SUBMIT THESE PLANS FOR REFERENCE.COUNTY- | | | WIDE AMENDMENTS TO SPC 104.2.1. | | | | | | SHOW REQD.BACKFLOW PREVENTION DEVICE ON | | | WATER RISER AND ON PLAN VIEW.SPC 104.2.1 | | | | | | SUBMIT ISOMETRIC DRAWINGS FOR SUMP | | | DISCHARGE LINES FROM ELEVATORS AND | | | ESCALATORS.DRAINS MAY BE REQD.TO DIS- | | | CHARGE THRU AN INTERCEPTOR PER SPC SEC. | | | 1004.1,1004.5. | | | | | | PLUMBING PLANS REFER TO DRWG.MUV-CIT2. | | | CLARIFY AND SUBMIT THESE SHEETS IF | | | APPLICABLE.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | WATER HEATERS LOCATED ABOVE THE GROUND | | | FLOOR SPACE SHALL HAVE A PAN WITH A | | | DRAIN PER COUNTYWIDE AMENDMENTS SEC. | | | 507.8.1 | | | | | | ALL FLOOR SINKS,FLOOR DRAINS,HAND SINKS | | | ETC.LOCATED IN THE FOOD PREP AREA SHALL | | | DRAIN TO THE GREASY WASTE SYSTEM.SPC SEC | | | 1004.1,1004.4. | | | | | | THE FIXTURE UNIT LOAD ON THE 4"BUILDING | | | DRAIN EXCEEDS THE TOTAL ALLOWABLE LIMIT | | | BY TABLE 714.1 OF SPC. | | | | | | LAYOUT OF U/G SANITARY ON SHT.P1 DOESN'T | | | CORRELATE W/SHT.P8.COUNTY AMENDMENTS TO | | | SPC SEC.104.2.1,AND THERE ARE FIXTURES | | | MISSING ON THE RISER.(SEE RMS.130,131, | | | MOP SINK.CHECK ALL RESTROOMS.) | | | | | | ISOMETRICS FOR MAIN CONCESSION AREAS DO | | | NOT CORRELATE W/ FLOOR PLAN.CLARIFY. | | | COUNTYWIDE AMENDMENT TO SPC SEC.104.2.1. | | | | | | | | | REMOVE TRAP ON OSD LINE PER SPC SEC. | | | 1106.4.(SEE SHT.8.1) | | | | | | SHOW SQ.FT.AREA DRAINED BY EACH DD. | | | COMPLY W/SPC TABLES 1108.1,1108.2. | | | | | | INDICATE TYPICAL DROP SIZE ON AIR RISER | | | AND PIPE MATERIAL,SHOW VALVES. | | | | | | COMPRESSED AIR DRAWING ON P-5 AND P-9 DO | | | NOT CORRELATE.CLARIFY. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | 610.4.1,610.4.2. | | | | | | WATER RISER LACKS PIPE SIZES.CLEARLY | | | SIZE RISER DIAGRAM & COMPLY W/SPC TABLE | | | 607.1. | | | | | | SHT.P9 SHOWS WATER SUPPLY EXTENDING | | | BEYOND 4TH FLR.LEVEL.CLARIFY. | | | | | | SHTP9.1-WATER HEATERS INSTALLED ABOVE | | | FIRST FLOOR SPACE SHALL BE EQUIPPED W/ | | | PANS AND PAN DRAINS PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.507.8.1 | | | | | | WATER HEATERS SHALL BE VALVED PER SPC. | | | SEC.501.6,506.1. | | | | | | HOT WATER SHALL BE INSTALLED ON LEFT | | | SIDE PER SPC SEC.601.10. | | | | | | A TWO WAY CLEANOUT SHALL BE INSTALLED | | | ENTERING AND LEAVING EACH GREASE TRAP. | | | SPC SEC.1004.2,710.4 | | | | | | CLEARLY SHOW MATCH POINTS ON SANITARY | | | RISERS TO FOUNDATION PLAN TO ENSURE | | | DESIGN COMPLIES W/SPC.SEE PAGE P8. | | | | | | LABEL WATER RISERS ON P9.1 AS TO AREA. | | | COUNTYWIDE AMENDMENTSTO SPC SEC.104.2.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-02-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-27 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-02-27 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****CONTINUATION OF PLUMBING COMMENTS** | | | | | | SHT.P-2 SHOWS FIRE LINE CONNECTED TO | | | DOMESTIC WATER LINE.LINES SHALL BE | | | SEPARATE PER SPC SEC.601.2,601.5. | | | | | | PLUMBING PLANS REFER TO SHEETS MUV-CIT2. | | | CLARIFY AND SUBMIT THESE SHEETS IF | | | APPLICABLE.COUNTYWIDE AMENDMENTS SEC. | | | 104.2.1. | | | | | | WATER HEATERS LOCATED ABOVE 1ST.FLR. | | | CEILING SHALL HAVE A PAN WITH A DRAIN | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 507.8.1.PAN SHALL COMPLY W/SPC SEC. | | | 507.8.2. | | | | | | | | | *******************NOTE***************** | | | THE FOUNDATION PLANS WERE APPROVED BY | | | PLUMBING PLAN REVIEW ON 10/1/99 WITH A | | | PROVISO THAT CORRECT SANITARY,WATER, | | | STORM AND CONDENSATE ISOMETRICS MUST BE | | | SUBMITTED WITHIN 30 DAYS.TO DATE THESE | | | ISOMETRICS HAVE NOT BEEN SUBMITTED FOR | | | REVIEW. | | | | | | CALL (561)659-8096 IF YOU HAVE ANY | | | QUESTIONS.TIMOTHY K.LARGE,PLANS EXAMINER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-27 |
Time |
09:32 |
Rev Time |
6.25 |
| Received By |
tlarge |
Date |
2000-02-27 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THE TOTAL NUMBER OF DRINKING FOUNTAINS | | | REQD.IS 7 PER SPC TABLE 407 AND A MIN.OF | | | 1 SHALL BE LOCATED ON EACH FLOOR SUBJECT | | | TO ACCESS.FOUNTAINS SHALL ALSO COMPLY W/ | | | FACBC SEC.4.1.3(10)(A)(B) AND 4.15. | | | SUBMIT DETAIL OF H.C.DRINKING FOUNTAIN. | | | | | | THE TOTAL NUMBER OF WATER CLOSETS REQD. | | | FOR THE MALES IS 9 AND A TOTAL OF 8 IS | | | SUPPLIED.COMPLY W/SPC TABLE 407 FOR MIN. | | | FIXTURE REQS. | | | | | | PLANS SHALL BE REVIEWED AND APPROVED | | | BY THE PALM BEACH COUNTY HEALTH DEPT. | | | PRIOR TO REVIEW BY THIS DEPT.PER COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.101.4.7. | | | CALL (561)355-3018. | | | | | | SHT.A6.2-CLEARLY SHOW DEPTH OF HANDICAP | | | STALL IN ROOM #131(WOMEN'S R.R.) AND | | | SHOW HANDICAP STALL DOOR IN MEN'S R.R. | | | (#130). | | | | | | MIN.CLEAR FLOOR SPACE UNDER H.C.LAVS | | | FROM BOTTOM OF APRON TO F.F.IS 29"PER | | | FACBC SEC.4.19.2.SHOW ON ELEVATION | | | DETAILS. | | | | | | SHT.A6.2-HANDICAP URINAL SHALL BE IN- | | | STALLED W/THE RIM NO HIGHER THAN 17"PER | | | FACBC SEC.4.18.2 AND SHOW REQD.30"X48" | | | CLEAR FLOOR ACCESS TO FIXTURE. | | | | | | CLEARLY SHOW LOCATION OF ALL DRINKING | | | FOUNTAINS ON THE PLANS.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | | | | | | | | | | SHT.ID 3.13-HT. OF H.C. TOILET IN TOILET | | | ROOMS 113,113A SHALL BE AT 17-19"PER | | | FACBC SEC.4.16.3. | | | | | | SHT.A6.2-CLEARLY SHOW WIDTH OF H.C. | | | TOILET ROOM.COMPLY W/FACBC SEC.4.16.2, | | | 4.19.3. | | | | | | INDICATE TYPE OF FINISH ON TOILET ROOM | | | WALLS.COMPLY W/SBC 1204.2.(FINISH | | | SCHEDULE NOTES PAINT BUT NOT TYPE.WALLS | | | MUST BE NONABSORBENT TO A HEIGHT OF 4'. | | | | | | PLANS MUST BEAR CITY PLACE APPROVAL | | | STAMPS FOR PERMITTING. | | | | | | UNISEX TOILET ROOMS CANNOT BE CONSIDERED | | | IN COUNT FOR THE MIN.FIXTURE REQS. | | | SEPARATE FACILITIES ARE REQD.PER SPC | | | TABLE 407,FOOTNOTES #6 & #8. | | | | | | FLOOR DRAINS ARE REQD.IN ALL TOILET | | | ROOMS PER SPC 409.4.4.1. | | | | | | PLUMBING SHEETS REFER TO CIVIL DWGS.FOR | | | CONTINUATION OF PLUMBING LINES.SUBMIT | | | CIVIL DWGS.FOR REVIEW OR PERMIT NUMBER | | | OF CIVIL WORK. | | | | | | SUBMIT DETAIL OF GREASE INTERCEPTOR | | | WITH ALL REQD.INFORMATION.THE SUBMITTED | | | DETAIL DOESN'T CONTAIN ENOUGH INFO FOR | | | PROPER REVIEW.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1.CONTACT R.COMPO AT (561) | | | 835-7423 FOR INFORMATION REGARDING SIZE, | | | DESIGN,ETC. | | | | | | SUBMIT A SANITARY,STORM,WATER AND CON- | | | DENSATE ISOMETRIC THAT CLEARLY REFLECTS | | | THE ENTIRE SCOPE OF WORK BEING DONE.THE | | | ISOMETRICS SHALL MATCH THE PLAN VIEW | | | DRAWINGS.THE SUBMITTED RISER DIAGRAMS | | | ARE THE SAME FROM SEPT.1999 W/THE | | | FOUNDATION ONLY PLANS.THEY WERE NOT | | | ACCEPTABLE THEN AND ARE NOT ACCEPTABLE | | | NOW.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | A BACKFLOW PREVENTION DEVICE IS REQD.ON | | | THE DOMESTIC WATER SERVICE PER SPC SEC. | | | 606. | | | | | | SUBMIT ISOMETRICS FOR SUMP DISCHARGE | | | LINES FROM ELEVATORS AND ESCALATORS,AND | | | ALL COMPRESSED AIR PIPING.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | PLAN VIEW AND RISER DIAGRAMS SHOW | | | SANITARY SYSTEM AND GREASY WASTE INTER- | | | CONNECTED.COMPLY W/SPC SEC.1004.3 |
|
|