Plan Review Details - Permit 00020273
Plan Review Stops For Permit 00020273
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-11-20 Cont ID  
Sent By lmartine Date 2000-11-20 Time 06:52 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-27 Cont ID  
Sent By lmartine Date 2000-04-27 Time 13:10 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00*************PROVISO**************
 OK FOR PHASE ONE WORK [BUILDING]
  
 SUBMIT FLORIDA ENERGY CALCULATIONS,
 PROVIDE PLUMBING INFORMATION,
 REDESIGN CORRIDORS[434 AND 500]INCLUDE
 DOORS[433 AND 509]FOR COMPLIANCE WITH
 FL.ACC.CODE SECT. 4.13.6,MANUVERING
 CLEARENCES
  
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 659-8096 #8456

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2001-03-07 Cont ID  
Sent By dpalmer Date 2001-03-07 Time 08:37 Rev Time 0.00
Received By dpalmer Date 2001-03-07 Time 08:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 19:49 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 19:49 Sent To  
Notes
2001-03-01 00:00:00HOLD UNTIL 2/5/01

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-10-10 Cont ID  
Sent By dpalmer Date 2000-10-10 Time 08:32 Rev Time 0.00
Received By dpalmer Date 2000-10-10 Time 07:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-07-27 Cont ID  
Sent By dpalmer Date 2000-07-27 Time 20:55 Rev Time 0.00
Received By dpalmer Date 2000-07-27 Time 20:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-06-27 Cont ID  
Sent By dpalmer Date 2000-06-27 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2000-06-27 Time 19:15 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PREVIOUS NOTES WERE NOT ADDRESS-
 -ED. PLEASE NOTE THAT ALL REVISED PANEL
 SCHEDULES AND LOAD CALCUALTIONS ARE TO
 BE SIGNED AND SEALED BY ENGINEER OF
 RECORD.REVISED LOAD CALCS AND PANELS
 WERE FAXED. THIS IS WILL NOT BE ACCEPTED
 THIS IS A STATE STATUE.
  
 2)NOTE:PLEASE SUBMIT ELECTRICAL ROOM
 DIMENSIONS. SHOW FOR ELECTRICAL CLEAR-
 -ENCES FOR TRANFORMER AS PER 450-21
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. PLANS THAT ARE SUBMITTED
 ARE TO BE ATTACHED BY CONTRACTOR.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-06-22 Cont ID  
Sent By dpalmer Date 2000-06-22 Time 20:46 Rev Time 0.00
Received By dpalmer Date 2000-06-22 Time 20:46 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: AS PER OUR CONVERSATION. SHOWING
 THE PANEL WITH FEED-THRU LUGS WAS FINE.
 STILL NEED TO SHOW THE LOAD CALCULATIONS
 COMPLETED AT THE BOTTOM OF EACH PANEL.
 LIGHTING TO BE SHOWN AT 125 %
  
 2)NOTE: FILL IN OUTLETS PER LOCAL CODE.
  
 3)NOTE: PLEASE SEE ART 450-21-B FOR
 TRANSFORMER REQ`MENTS. PLEASE GIVE EXACT
 DIMENSIONS OF ELETRICAL ROOM WITH VERT.
 AND HORIZONTALCLEARENCES. OO
  
 4)NOTE: PLEASE COMPLETE THE LOAD CALCU-
 LATION FOR LOAD ON MAIN "H".
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 09:57 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 09:57 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE:SHOW LOAD CALCULATIONS;PLEASE
 INCLUDE ALL CONTIUOUS LOADS(LIGHTING)ETC
 NEED TO SHOW!
  
  
  
  
  
  
 3)NOTE; PLEASE CHECK ALL OUTLET SPACING
 TO MEET LOCAL CODE. FOR OFFICE AND
 STORAGE SPACE. 210-50 OF THE PALM BEACH
 COUNTY /CITY AMENDMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-04-26 Cont ID  
Sent By lmartine Date 2000-04-26 Time 10:30 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-18 Cont ID  
Sent By mcarsill Date 2000-10-18 Time 16:02 Rev Time 0.00
Received By mcarsill Date 2000-10-18 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By rturnque Date 2000-03-03 Time 08:41 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-10-17 Cont ID  
Sent By ndenmark Date 2000-10-17 Time 17:57 Rev Time 0.50
Received By ndenmark Date 2000-10-17 Time 17:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-08-23 Cont ID  
Sent By ndenmark Date 2000-08-23 Time 11:46 Rev Time 0.33
Received By ndenmark Date 2000-08-23 Time 11:46 Sent To  
Notes
2001-01-08 00:00:00OUTSIDE AIR AND AIR BALANCE CALCS ARE
 ATTACHED TO SHELL FOR THIS ADDRESS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2000-07-25 Cont ID  
Sent By cthirben Date 2000-07-25 Time 12:05 Rev Time 1.00
Received By cthirben Date 2000-07-25 Time 11:37 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 AS PER REVIEW DONE ON 07.13.00 NO CHANGE
 ON PLANS TO REVIEW ON 07.25.00.
 PROVIDE OUTSIDE AIR CAL..
 PROVIDE AIR BALANCE SCHEDULE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-13 Cont ID  
Sent By ndenmark Date 2000-07-13 Time 10:15 Rev Time 1.00
Received By ndenmark Date 2000-07-13 Time 10:15 Sent To  
Notes
2001-01-08 00:00:00*************DENIED********************
 1) PROVIDE OUTSIDE AIR CALCULATIONS
 PER ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-03-10 Cont ID  
Sent By ndenmark Date 2000-03-10 Time 14:15 Rev Time 1.00
Received By ndenmark Date 2000-03-10 Time 14:15 Sent To  
Notes
2001-01-08 00:00:00MECH NOT REVIEWED********************8
 BUILDING CORE MECHANICAL SYSTEMS ARE
 APPROVED FOR CODE COMPLIANCE
 SYSTEM SHOWN AS EXISTING HAS TO BE APPR-
 OVED PRIOR TO REVIEW OF ADDITIONAL
 SYSTEMS

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 17:10 Rev Time 1.00
Received By tlarge Date 2000-08-29 Time 17:06 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
  
 1)THE CORE RESTROOMS ARE NON-COMPLIANT
 PER SPC TABLE 407.CERTIFICATE OF
 OCCUPANCY SHALL NOT BE ISSUED UNTIL THIS
 MATTER IS RESOLVED.SEE PERMIT NUMBER
 99101414.TLARGE.8/29/00.

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 08:46 Rev Time 0.75
Received By tlarge Date 2000-08-29 Time 08:46 Sent To  
Notes
2001-01-08 00:00:001)THE MINIMUM NUMBER OF WATER CLOSETS
 REQD.FOR THE MALES BASED ON THE SQUARE
 FEET OF HABITABLE FLOOR SPACE,OCCUPANT
 LOAD AND TABLE 407 IS 4.(3 FOR THE FIRST
 150 PERSONS AND 1 FOR EACH ADDITIONAL
 100 PERSONS OR FRACTION THEREOF.)
  
 2)FOR THE FEMALES-BASED ON THE SAME
 DATA AND CRITERIA NOTED ABOVE,4 WATER
 CLOSETS ARE REQD.FOR THE FIRST 150
 PERSONS,AND 1.5 FOR EACH ADDITIONAL 100
 PERSONS OR FRACTION THEREOF WHICH BRINGS
 THE TOTAL NUMBER OF WATER CLOSETS REQD.
 FOR THE FEMALES TO 6.
  
 3)THE TOTAL NUMBER OF LAVATORIES REQD.
 FOR THE FEMALES IS 3 FOR THE FIRST 125
 PERESONS AND 1.5 FOR EACH ADDITIONAL
 120 PERSONS OVER 125 WHICH BRINGS THE
 TOTAL TO 5 LAVATORIES.
  
 ***NOTE:THESE REQS.ARE BASED UPON THE
 THE FLOOR AREA CALCULATIONS SUBMITTED BY
 COOPER CARRY DATED AUGUST 23,2000.
 CALCULATIONS SHALL BE SUBMITTED FOR THE
 DEDUCTED AREAS USED TO ARRIVE AT THE
 PRESENT FIGURES.SEE SPC SEC.407.1.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 16:41 Rev Time 0.65
Received By tlarge Date 2000-08-21 Time 16:41 Sent To  
Notes
2001-01-08 00:00:00THE APPLICATION STILL NOTES 20,000 SQ.
 FT.OF FLOOR SPACE.SUBMIT THE NUMBER OF
 OCCUPANTS BASED ON THE SQUARE FEET OF
 HABITABLE FLOOR SPACE.SEE SPC SEC.
 407.1.3.FOR ALLOWED DEDUCTIBLE AREAS.
 COMPLY W/SPC TABLE 407 FOR MIN.PLUMBING
 FIXTURE REQS.
  
 2)SUBMIT DETAIL OF THE HANDICAP STALLS.
 THERE IS AN ISSUE WITH THE STALLS BEING
 NON-COMPLIANT THAT STEMS FROM MY REVIEW
 OF REVISIONS FOR THE SHELL BUILDING.
 STALLS SHALL COMPLY W/FACBC SEC.4.17.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-05 Cont ID  
Sent By pschmitz Date 2000-08-05 Time 10:01 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW, UNSAT
 (1) SHT A-1 IS NOT THE MOST CURRENT COPY
 OF THE COMMON AREA REST RM'S.
 (2) PERMIT APPLICATION SHOWS 20,000 SQ.
 FT.TAB 407 MIN FACILITIES, BUSSINESS
 OCC.REQ'S 5-W/C'S & 5-LAV'S FOR WOMENS
 REST RM, SPC 94.
 (3) SHT A-8 ELEVATION DETAIL FOR RM 492
 FRONT APPROACH TO SINK, COMPLY W/FACBC
 4.24.5 S SHOW CLEAR FLR SPACE & KNEE
 CLEARANCE.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-26 Cont ID  
Sent By tlarge Date 2000-06-26 Time 16:14 Rev Time 1.50
Received By pschmitz Date 2000-06-26 Time 16:14 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SQUARE FOOT AREA OF OCCUPIED
 SPACE.MINIMUM REQUIRED SANITARY
 FACILITIES SHALL COMPLY W/SPC TABLE 407.
  
 CLEAR FLOOR SPACE FOR SINK IN ROOM 492
 SHALL BE CENTERED ON THE FIXTURE PER
 FACBC SEC.4.24.5.

Review Stop Z ZONING
Rev No 1 Status N Date 2000-04-26 Cont ID  
Sent By lmartine Date 2000-04-26 Time 10:35 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***