Plan Review Details - Permit 00020036
Plan Review Stops For Permit 00020036
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-01 Cont ID  
Sent By ndenmark Date 2000-02-01 Time 15:31 Rev Time 0.25
Received By ndenmark Date 2000-02-01 Time 15:31 Sent To  
Notes
2001-01-08 00:00:00HOOD FAN SHUT DOWN TO BE TESTED TO SHOW
 EXFAN STAYS ON AND SUPPLY FAN SHUTS OFF
 WHEN HOOD SUPPRESSION SYSTEM TRIPS
 COORDINATE INSPECTION SO ANY NEEDED
 PERSONNEL ARE PRESENT