| Plan Review Stops For Permit 00011426 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-04-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-04-18 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-04-18 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-19 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-19 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT MAINS/PANEL. AS REQ`D BY | | | ARTS 110-9/110-10. /215-5 OF THE NEC. | | | | | | 2)NOTE: SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS. | | | | | | 3)NOTEL PLEASE LIST THE DEDICATED BATH(S | | | CIRCUT REQ`D BY 210-52D.SHALL BE #12 AND | | | 20 AMP. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-02-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-02-12 |
Time |
09:58 |
Rev Time |
0.35 |
| Received By |
jleech |
Date |
2000-02-12 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-06-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-01 |
Time |
06:32 |
Rev Time |
0.25 |
| Received By |
tlarge |
Date |
2000-06-01 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISED SANITARY RISER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-04-24 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-24 |
Time |
07:00 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-04-24 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-02-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-08 |
Time |
06:50 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-02-08 |
Time |
06:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2000-06-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-06-14 |
Time |
19:34 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2000-06-14 |
Time |
19:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-TRUSS DRAWINGS SUBMITTED ARE FOR | | | ANOTHER MODEL. | | | -THERE IS ANOTHER SET OF TRUSS DRAWINGS | | | ON FILE, SIGNED AND SEALED BY ANOTHER | | | ENGINEER. CLARIFY. | | | 2-SEE ITEMS REQUESTED ON PREVIOUS | | | PROVISO. | | | 3-GARAGE DOOR DESIGN PRESSURES: | | | -LETTER BY ARCHITECT IS NOT CLEAR. | | | THERE ARE TWO DIFFERENT SIZES OF DOORS | | | THEREFORE, DESIGN PRESSURES SHOULD BE | | | DIFFERENT. PROVIDE CALCULATIONS FOR | | | EACH OPENING. | | | -SUBMIT PRODUCT APPROVAL FOR EACH TYPE | | | OF DOOR. THERE IS NONE WITH THE SET. | | | 4-SLIDING GLASS DOORS WITH TRANSOM ABOVE | | | SITE SPECIFIC PRODUCT APPROVAL NEEDS | | | THE PROFESSIONAL OF RECORD (KUNIK) TO | | | SIGN, SEAL AND DATE THE SEPARATE | | | PRODUCT APPROVAL FORM. PLEASE INCLUDE | | | ALL REQUIRED INFORMATION FOR THE | | | SPECIFIC JOB AND ALL INFORMATION | | | REQUIRED BY THE PROFESSIONALS OF | | | RECORD TO AVOID UNNECESSARY RETURNS | | | AND DELAYS. | | | 5-ENTRY DOORS PRODUCT APPROVAL: | | | -ENGINEER WHO SIGNED AND SEALED THE | | | DOCUMENT IS NOT THE PROFESSIONAL OF | | | RECORD (IS KUNIK). | | | 6-ROYAL PALM ALUMINUM LETTER FROM | | | MANAGER OF ENGINEERING TO BE SIGNED, | | | SEALED AND DATED. | | | | | | | | | | | | NOTE: | | | ENGINEERS TO PROVIDE ALL INFORMATION | | | REQUIRED BY PROFESSIONAL ENGINEERS WHEN | | | SEALING A DOCUMENT FOR PUBLIC RECORD. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-04-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-20 |
Time |
17:03 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2000-04-20 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS APPROVED WITH PROVISO: | | | 1-CLARIFY WHO IS THE ENGINEER OF RECORD | | | FOR THIS HOUSE. THERE ARE TOO MANY | | | ENGINEERS INVOLVED IN THIS PROJECT. | | | -THE STRUCTURAL ENGINEER WHO SIGNED THE | | | ORIGINAL PACKAGE SUBMITTED WAS DR. | | | ERNEST A. KUONEN P.E.. NOW HE DIDN'T | | | SIGNED AND SEALED THESE DWGS. WHY? | | | -THE DESIGN CERTIFICATION FOR BUILDING | | | CODE COMPLIANCE FORM IS SIGNED AND | | | SEALED BY ROBERT E. AGSTEN III. P.E. | | | -AND, THE PRODUCT APPROVAL IS SIGNED | | | BY WHO? | | | 2-PRODUCT APPROVAL FOR ENTRY DOORS NEED: | | | -ITEM #8: A)ADDRESS OF ENGINEER. B)DATE | | | THAT DOCUMENT WAS SIGNED AND SEALED. | | | C) NEED A WET SIGNATURE NO A COPY. | | | -ITEM #9: A)CLEARLY PROVIDE NAME AND | | | ADDRESS OF ENGINEER OF RECORD FOR THIS | | | PROJECT. | | | 3-PROVIDE PRODUCT APPROVAL FOR ARCHED | | | WINDOWS. | | | 4-IF ENGINEER OF RECORD IS DR. KUONEN | | | P.E. THEN HE NEEDS TO SIGN SEAL AND | | | DATE ALL STRUCTURAL DRAWINGS AND | | | THE DESIGN CERTIFICATION CERTIFICATION | | | FOR BUILDING CODE COMPLIANCE FORM AS | | | WELL. | | | NOTE: CLEARLY INDICATE NAME, ADDRESS | | | AND LICENSE # IN EVERY DOCUMENT | | | PREPARED BY THE ENGINEER. | | | 5-GARAGE DOORS: | | | -DESIGN PRESSURES ARE LOWER THAN THE | | | DESIGN PRESSURES CALCULATED BY THE | | | ARCHITECT OR ENGINEER OF RECORD. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2000-03-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-03-30 |
Time |
17:24 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2000-03-30 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-UPDATE/REVISE ALL DRAWINGS AS REQUIRED | | | SEE COMMENTS ON PLANS. | | | 2-DRAWING A2: WHERE IS COLUMN C6. | | | 3-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR | | | OPENING. TABLE 1004 SBC 1997. | | | 4-PROVIDE THE DESIGN PRESSURES AT ALL | | | EXTERIOR OPENINGS. SEC. 1606 SBC 1997. | | | 5-SPECIFY CEILING INSTALLATION AT ENTRY | | | AND REAR PORCHES. SPECIFY FASTENERS | | | AND SPACING. SEC. 2504.2 SBC 1997. | | | 6-PRODUCT APPROVAL FOR ENTRY DOORS IS | | | FOR OUTSWING DOORS. ARCHITECT'S PLANS | | | SHOWS INSWING DOORS. PROVIDE PRODUCT | | | APPROVAL FOR INSWING DOORS OR REVISE | | | ARCHITECT'S DRAWINGS. | | | 7-REVISE ENGINEERED ROOF TRUSSES. THERE | | | IS ONLY ONE MEAN ROOF HEIGHT FOR | | | ENTIRE BUILDING. MEAN ROOF HEIGHT IS | | | TAKEN FROM GRADE, NOT FROM FINISH | | | FLOOR, TO THE AVERAGE POINT OF HIGHEST | | | ROOF. IN THIS CASE IS PLUS OR MINUS | | | 20'-0". SEE EXTERIOR ELEVATIONS. | | | 8-REVISE THE DESIGN CERTIFICATION FOR | | | BUILDING CODE COMPLIANCE FORM. MEAN | | | ROOF HEIGHT IS PLUS OR MINUS 20'-0". | | | SEE EXTERIOR ELEVATIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-03-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-03-31 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2000-03-31 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED BY ANGELA JONES. 3-31-00 | | | SEE APPLICATION AND SURVEY. |
|
|