Plan Review Details - Permit 00011376
Plan Review Stops For Permit 00011376
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 08:55 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. AIC RATING NEED TO BE
 ABLE TO HANDLE AVAILABLE FAULT CURRENT
 AT MAINS. AIC RATING CAN BE FIGURED FROM
 FAULT CURRENT CALCULATIONS. AS PER
 ARTS:110-9/110-10/215-5
  
 2)NOTE:PLEASE HAVE REQ`D BATH(S) CURCUT
 (S) LISTED ON PANEL SCHEDULE AS REQ`D BY
 ART:210-52D OF THE NEC. NEEDS TO BE
 20AMP AND #12 AWG. REMEMBER THAT THERE
 STILL MUST BE TWO SPARE SPACES IN THE
 PANEL. YOU SHOW RANGE AS BEING ONE
 SPACE.PLEASE CHE3CK FOR SIZE OF PANEL.
  
 3)NOTE:AS REQ`D BY 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS. PLEASE SHOW ON RESUBMITTED
 DRAWINGS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVEIW AND APPROVAL BEFORE
 FIRST ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-13 Cont ID  
Sent By cthirben Date 2000-03-13 Time 14:25 Rev Time 0.50
Received By cthirben Date 2000-03-13 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 09:29 Rev Time 0.35
Received By jleech Date 2000-02-05 Time 09:29 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 NO A/C PLAN.SUBMIT DRAWINGS SHOWING,
 SIZE OF DUCTS CFM'S FOR EACH DROP,
 EQUIPMENT STATS AND LOCATIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-25 Cont ID  
Sent By tlarge Date 2000-02-25 Time 17:01 Rev Time 0.53
Received By tlarge Date 2000-02-25 Time 17:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-23 Cont ID  
Sent By lsmith Date 2000-03-23 Time 07:18 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: NEED FRENCH DOOR PRODUCT
 APPROVALS BEFORE INSPECTION LS

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-08 Cont ID  
Sent By lsmith Date 2000-03-08 Time 08:08 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED FOLLOWING:
 1. PRODUCT APPROVALS FRENCH DOORS
 2. CLARIFY WORK TO BE DONE WITH THIS
 PERMIT(SHOW NEW AND EXISTING)
 3. SHOW WINDOWS REPLACING
 4. SHOW WINDOWS FOR SHUTTERS

Review Stop Z ZONING
Rev No 1 Status N Date 2000-03-23 Cont ID  
Sent By lsmith Date 2000-03-23 Time 07:21 Rev Time 0.10
Received By lsmith Date   Time   Sent To  
Notes
***NONE***