Plan Review Details - Permit 00011297
Plan Review Stops For Permit 00011297
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-04-26 Cont ID  
Sent By bstaples Date 2000-04-26 Time 16:54 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-04-04 Cont ID  
Sent By bstaples Date 2000-04-04 Time 14:07 Rev Time 0.00
Received By bstaples Date 2000-04-10 Time 10:03 Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS REQUIRED.
  
 2. NOTES ADDED TO DRAWINGS MUST BE
 APPROVED BY THE DESIGNER OF RECORD.
 SEE SHEETS, A-0, A-0.1, A-1.2, A-4.0,
 A-6.1, A-6.2, A-6.3, A-6.4, 3-3.0 AND
 E-3.1.
  
 3. SHEET A-6.4 PLANS DO NOT INDICATE
 CODE COMPLIANCE FOR MISSLE IMPACT
 PROTECTION. SEE 1997 STANDARD BUILDING
 CODE AND CITY OF WEST PALM BEACH
 AMENDMENTS (SSTD 12-97).
  
 4. SHEET A-12 SECTION, N & N1 INDICATE
 CONSTRUCTION OF ONLY ONE SIDE OF FIRE
 SEPERATION. CITY POLICY REQUIRES
 CONSTRUCTION OF BOTH SIDES OF THE WALL
 REVISE NOTES AND SECTION.
  
 5. FIRE SPRINKLER CONTRACTOR MUST APPLY
 FOR A FIRE SPRINKLER PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-01-28 Cont ID  
Sent By bstaples Date 2000-01-28 Time 10:08 Rev Time 0.00
Received By bstaples Date 2000-03-21 Time 14:14 Sent To  
Notes
2001-01-08 00:00:001. CITYPLACE APPROVAL STAMP NOT ON PLANS
 2. SHEET A-0, CODE REFERENCES NOT
 CORRECT,
 MECHANICAL CODE IS 1997 NOT 1996 SBC
 PLUMBING CODE IS 1994 NOT 1997 SBC
  
 KEY PLAN IS NOT INDICATING PROPER
 LOCATION FOR UNIT.
 UNIT ADDRESS LISTED IS NOT APPROVED FOR
 USE BY CITY OR US POSTAL SERVICE.
 3. SHEET A-1.2 MEZZAINE NOT IN
 COMPLIANCE WITH 1997 SBC SECTIONS 7, 10,
 AND 11ALSO CHAPTER 16 FOR LOAD
 INFORMATION.
 4. ESCULATORS SHALL COMPLY WITH CHAPTER
 7, 10 AND 30, 1997 SBC.
 5. SIGNS AND FIGURES REQUIRE SEPERATE
 PERMITTING.
 6. SHEET A-6.4 PROVIDE PRODUCT APPROVALS
 FOR ALL EXTERIOR WINDOWS AND DOORS, SEE
 NOTE 24.
 7.ALL WOOD SHAL BE PRESSURE TREATED FIRE
 RETARDANT LUMBER SBC 1997 SECTION707.
 8. SHEET A-03(3)&(4) INDICATE CHANGE IN
 FLOOR ELEVATIONS, PROVIDE INFORMATION
 ON PLAN INDICATING COMPLIANCE WITH 1997
 FL. HANDICAPPED CODE.
 9. INDICATE THE TOTAL HEIGHT OF
 CONSTRUCTION ON PLANS.
 PLAN REVIEW NOTES 1/28/00
 10. DEMISING WALL SECOND FLOOR TO BE
 2 HOUR SEE TABLE 704.1 SEPERATION
 ASSEMBLY TO MERCANTILE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-09-18 Cont ID  
Sent By dpalmer Date 2000-09-18 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2000-09-18 Time 19:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-04-27 Cont ID  
Sent By dpalmer Date 2000-04-27 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2000-04-27 Time 09:20 Sent To  
Notes
2001-01-08 00:00:00NOTES STILL ON PLANS FOR COLOR CODING
 OF FEEDERS 215 OF LOCAL AMENDMENTS .

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-04-10 Cont ID  
Sent By dpalmer Date 2000-04-10 Time 18:00 Rev Time 0.00
Received By dpalmer Date 2000-04-10 Time 17:57 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: STILL NEED TO SHOW GROUNDING
 SYSTEM ON THE LINESIDE OF TRANSFORMER.
 215-5
 2)NOTE:PLEASE MAKE NOTES ON PLANS THAT
 COLOR CODING FOR FEEDERS ARE TO BE TO
 LOCAL CODE.215
  
 3)NOTE:PLEASE INDICATE ON PLANS ALL LOAD
 -S THAT ARE CONTINUOUS AT 125%.
 SHOW IN LOAD CALCULATION FOR ALL
 LIGHTING.ALSO MOTOR LOAD FOR THE TWO
 CLOCK MOTORS.AND ANY OTHER LOADS.
 215-5/220-12/210-19A
  
 4)NOTE: ALSO FOR 210-62 REQ`MENTS FOR
 OUTLETS IN SHOW WINDOWS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By dpalmer Date 2000-02-01 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2000-02-01 Time 11:22 Sent To  
Notes
2001-01-08 00:00:00************ NOTE**********************
  
 1)NOTE: NEED TO SHOW GROUNDING ON THE
 LINE SIDE OF TRANSFORMER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-27 Cont ID  
Sent By mcarsill Date 2000-09-27 Time 11:02 Rev Time 0.00
Received By mcarsill Date 2000-09-27 Time 11:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-04-26 Cont ID  
Sent By bstaples Date 2000-04-24 Time 11:39 Rev Time 0.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 REVISED PLANS TO FIRE 4/24/00

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By bstaples Date 2000-02-01 Time 11:19 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ON PLANS M. CARSILLO LT.2/1/00
 ENGINEER DRAWINGS FOR FIRE SPRINKLER
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-09-09 Cont ID  
Sent By ndenmark Date 2000-09-09 Time 07:59 Rev Time 0.33
Received By ndenmark Date 2000-09-09 Time 07:59 Sent To  
Notes
2001-01-08 00:00:00AS BUILT DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-05-03 Cont ID  
Sent By ndenmark Date 2000-05-03 Time 10:30 Rev Time 0.50
Received By ndenmark Date 2000-05-03 Time 10:30 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS CORRECTED BY REVISIONS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-04-11 Cont ID  
Sent By ndenmark Date 2000-04-11 Time 07:05 Rev Time 1.00
Received By ndenmark Date 2000-04-11 Time 07:05 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 1) AIR BALANCE REQUESTED NOT PROVIDED:
 OUTSIDE AIR PROVIDED ON PLAN EQUALS
 4955 CFM
 LESS BATH EXHAUST OF 200 CFM = 4755 CFM
 LESS 4952 CFM RELIEF VENTILATOR=-197CFM
 WHICH WOULD PUT BUILDING IN A NEGATIVE
 PRESSURE.
 PROVIDE CORRECTED AIR BALANCE SHOWING
 OUTSIDE AIR AND EXHAUST AIR BALANCE,
 INCLUDING EXFILTRATION, RELIEF AND
 EXHAUST AIR FIGURES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-31 Cont ID  
Sent By ndenmark Date 2000-01-31 Time 15:04 Rev Time 1.00
Received By ndenmark Date 2000-01-31 Time 15:04 Sent To  
Notes
2001-01-08 00:00:00*************DENIED********************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) PROVIDE AIR BALANCE CALCULATIONS PER
 1997 SMC 501.2
 3) NOTE: NO COMBUSTIBLE MATERIALS ALLOW-
 ED IN PLENUM AREAS PER 1997 SMC 609.1.2

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-10-07 Cont ID  
Sent By tlarge Date 2000-10-07 Time 07:40 Rev Time 1.00
Received By tlarge Date 2000-10-07 Time 07:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status N Date 2000-09-22 Cont ID  
Sent By tlarge Date 2000-09-22 Time 14:24 Rev Time 0.33
Received By tlarge Date 2000-09-22 Time 14:24 Sent To  
Notes
2001-01-08 00:00:00PLUMBING NOT AFFECTED THIS REVISION.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-05-09 Cont ID  
Sent By tlarge Date 2000-05-09 Time 10:15 Rev Time 1.50
Received By tlarge Date 2000-05-09 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-05-02 Cont ID  
Sent By tlarge Date 2000-05-02 Time 20:02 Rev Time 1.25
Received By tlarge Date 2000-05-02 Time 20:02 Sent To  
Notes
2001-01-08 00:00:00PLANS SHALL BE SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO USE WHEELCHAIRS AND
 FOR THOSE WHO HAVE TROUBLE BENDING OR
 STOOPING.INDICATE MEANS OF COMPLIANCE ON
 PLANS.
  
 INDICATE OCCUPANT LOAD ON PLANS FOR
 DETERMINATION OF MINIMUM SANITARY REQS.
 SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT-
 IBLE AREAS AND COMPLY W/SPC TABLE 407.
 (PLUMBING FIXTURES ARE NOT ADEQUATE FOR
 SPECIFIED OCCUPANT LOAD.)
  
 URINAL SHALL BE LOCATED TO ENSURE USER
 PRIVACY PER SPC SEC.404.3.(FIXTURE IS
 LOCATED IN LINE OF SIGHT FROM CORRIDOR.)
  
 WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 DRY VENTS NOT PERMITTED PER SPC SEC.
 901.2,906.2.
  
 CLARIFY TERMINATION PT.OF RELIEF DRAIN
 FOR EWH.PLANS NOTE TO EXTERIOR AND ALSO
 TO MOP SINK.EITHER IS ACCEPTABLE PER SPC
  
 CLEANOUTS ARE REQD.IN HORIZONTAL
 DRAINAGE PIPE PER SPC SEC.710.2.1.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-04-06 Cont ID  
Sent By tlarge Date 2000-04-06 Time 16:00 Rev Time 0.00
Received By tlarge Date 2000-04-06 Time 16:00 Sent To  
Notes
2001-01-08 00:00:00URINAL SHALL COMPLY W/FACBC SEC.4.18.2
 THRU 4.18.4
  
 WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1,610.4.2.
  
 DRINKING FOUNTAIN ON 1ST.FLR.SHALL BE
 ACCESSIBLE TO THE PUBLIC PER SPC SEC.
 407.2.2.AND COMPLY W/FACBC SEC.4.15.
  
 SUBMIT A SANITARY RISER DIAGRAM THAT
 COMPLIES W/THE STANDARD PLUMBING CODE.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.(SUPPLY A PERMANENT
 LADDER OR RELOCATE EWH TO FLOOR.)++
  
 T & P VALVE DRAIN SHALL DISCHARGE TO
 EXTERIOR PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.507.8.4.
  
 ALL PUBLIC AND COMMON USE AREA TOILET
 ROOMS SHALL COMPLY W/FACBC SEC.4.1.3(11)
  
 CLEARLY SHOW DIMENSIONS (L X W) OF
 HANDICAP TOILET STALLS.COMPLY W/FACBC
 SEC.4.17.3 EXCEPTION :NEW CONSTRUCTION.
  
 DRINKING FOUNTAIN ON 2ND.FLR.SHALL
 COMPLY W/FACBC SEC.4.1.3.(10)(A)
  
 WATER HEATERS SHALL BE EQUIPPED W/PANS
 AND DRAINS PER COUNTYWIDE AMENDMENTS TO
 SPCSEC.507.8.1,507.8.3.
  
 CLARIFY USE OF ROOM CONTAINING DOUBLE
 SINK.IF THIS ROOM IS A BREAKROOM THE
 SINK SHALL COMPLY W/FACBC SEC.4.24.1-
 4.24.7.
  
 CLEARLY SIZE ALL VENTS ON SANITARY RISER
 COMPLY W/SPC TABLE 920.2,920.4.
  
 VENTING OF WATER CLOSETS SHALL COMPLY W/
 SPC SEC.906.2.1.,906.2.2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-31 Cont ID  
Sent By tlarge Date 2000-01-31 Time 09:42 Rev Time 2.00
Received By pschmitz Date 2000-01-31 Time 09:42 Sent To  
Notes
2001-01-08 00:00:00CITY PLACE APPROVAL REQD.ON PLANS.
  
 SHT.A-0-THE ADOPTED PLBG.CODE IS
 STANDARD PLUMBING CODE 1994 EDITION.
  
 SHT.A-5.3-SHOW MOUNTING HEIGHTS AND
 FIXTURE CLEARANCES OF PLUMBING FIXTURES
 AND ACCESSORIES.COMPLY W/FACBC.
  
 SHOW TURNING SPACE FOR WHEELCHAIR IN
 TOILET ROOMS PER FACBC SEC.4.2.3.
  
 MINIMUM TOILET FACILITIES SHALL COMPLY
 W/SPC SEC.407.1.4.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1.
  
 A DRINKING FOUNTAIN IS REQD.ON THE 1ST.
 AND SECOND FLOOR PER SPC TABLE 407.
  
 A VENT SHALL BE LOCATED BETWEEN THE TWO
 WATER CLOSETS AND COMPLY W/COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.3.
  
 WATER HEATER SHALL BE READILY ACESSIBLE
 PER SPC SEC.501.7.(A PERMANENTLY
 INSTALLED LADDER IS REQD.OR RELOCATE
 EWH TO FLOOR.)
  
 T & P VALVE DRAIN TERMINATION SHALL
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.507.8.4.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By bstaples Date 2000-02-01 Time 11:20 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLAN REVIEW NO ZONING APPROVAL