| Plan Review Stops For Permit 00011238 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-21 |
Time |
20:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-21 |
Time |
20:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-21 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-21 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATION | | | FOR THE ENTIRE SERVICE. YOU SHOW SERVICE | | | SIZE...ADDITIONAL 80 AMPS??? IS THIS | | | THE TOTAL LOAD ON HOUSE? IF SO PLEASE | | | SHOW.INCLUDE SERVICE CONDUCTOR SIZES. | | | | | | 2)NOTE: PLEASE THE REQ`MENTS FOR THE | | | DEDICATED BATH(S) CIRCUT(S) AS PER ART: | | | 210-52D THEY ARE TO BE 20 AMP AND #12AWG | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-03-28 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-03-28 |
Time |
10:18 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-03-28 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | ***************PROVISO****************** | | | | | | 1. INDICATE CFM'S ON EACH DROP | | | | | | 2. EXHAUST FANS IN BATHROOM SMC 503.3.1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-03-21 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-03-21 |
Time |
12:08 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-03-21 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | ******************DENIED**************** | | | 1. DISTRIBUTION OF CFM TO DROP IN EACH | | | NEEDSTO BE INDICATED ON PLANS | | | | | | 2. EXHAUST FANS IN BATHROOM SMC 503.3.1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2000-02-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-02-26 |
Time |
09:59 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2000-02-26 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO A/C PLAN. A/C PLAN REQUIRED WITH | | | PERMIT APPLICATION FROM A/C CONTRACTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-03-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-21 |
Time |
16:11 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-03-21 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-21 |
Time |
10:20 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-02-21 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHOW DIMENSIONS OF SHOWER(LXW).SHOWER | | | SHALL BE A MIN.OF 30"WIDE AND 1024 SQ.IN | | | OF FLOOR AREA.PER COUNTYWIDE AMENDMENTS | | | TO SPC SEC.409.8.2.1. | | | | | | LOCATION OF PLBG.FIXTURES ON SANITARY | | | RISER SHALL CORRELATE W/FLOOR PLAN PER | | | COUNTYWIDE AMENDMENTS TO SPC 104.2.1. | | | | | | TUB AND SHOWER NOT PROPERLY VENTED PER | | | SPC SEC.901.2. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-03-28 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-03-28 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-02-29 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-02-29 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2000-02-02 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-02-02 |
Time |
10:21 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-01 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-02-01 |
Time |
13:46 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NEEDS SURVEY |
|
|