Plan Review Details - Permit 00011238
Plan Review Stops For Permit 00011238
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-21 Cont ID  
Sent By dpalmer Date 2000-03-21 Time 20:03 Rev Time 0.00
Received By dpalmer Date 2000-03-21 Time 20:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-21 Cont ID  
Sent By dpalmer Date 2000-02-21 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2000-02-21 Time 08:17 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATION
 FOR THE ENTIRE SERVICE. YOU SHOW SERVICE
 SIZE...ADDITIONAL 80 AMPS??? IS THIS
 THE TOTAL LOAD ON HOUSE? IF SO PLEASE
 SHOW.INCLUDE SERVICE CONDUCTOR SIZES.
  
 2)NOTE: PLEASE THE REQ`MENTS FOR THE
 DEDICATED BATH(S) CIRCUT(S) AS PER ART:
 210-52D THEY ARE TO BE 20 AMP AND #12AWG
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-03-28 Cont ID  
Sent By cthirben Date 2000-03-28 Time 10:18 Rev Time 1.00
Received By cthirben Date 2000-03-28 Time 10:13 Sent To  
Notes
2001-01-08 00:00:00 
  
 ***************PROVISO******************
  
 1. INDICATE CFM'S ON EACH DROP
  
 2. EXHAUST FANS IN BATHROOM SMC 503.3.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-03-21 Cont ID  
Sent By cthirben Date 2000-03-21 Time 12:08 Rev Time 1.00
Received By cthirben Date 2000-03-21 Time 12:05 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 ******************DENIED****************
 1. DISTRIBUTION OF CFM TO DROP IN EACH
 NEEDSTO BE INDICATED ON PLANS
  
 2. EXHAUST FANS IN BATHROOM SMC 503.3.1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-02-26 Cont ID  
Sent By jleech Date 2000-02-26 Time 09:59 Rev Time 0.25
Received By jleech Date 2000-02-26 Time 09:58 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN. A/C PLAN REQUIRED WITH
 PERMIT APPLICATION FROM A/C CONTRACTOR.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-21 Cont ID  
Sent By tlarge Date 2000-03-21 Time 16:11 Rev Time 0.30
Received By tlarge Date 2000-03-21 Time 16:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-21 Cont ID  
Sent By tlarge Date 2000-02-21 Time 10:20 Rev Time 0.33
Received By tlarge Date 2000-02-21 Time 10:20 Sent To  
Notes
2001-01-08 00:00:00SHOW DIMENSIONS OF SHOWER(LXW).SHOWER
 SHALL BE A MIN.OF 30"WIDE AND 1024 SQ.IN
 OF FLOOR AREA.PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.409.8.2.1.
  
 LOCATION OF PLBG.FIXTURES ON SANITARY
 RISER SHALL CORRELATE W/FLOOR PLAN PER
 COUNTYWIDE AMENDMENTS TO SPC 104.2.1.
  
 TUB AND SHOWER NOT PROPERLY VENTED PER
 SPC SEC.901.2.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-28 Cont ID  
Sent By lmartine Date 2000-03-28 Time 15:03 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-02-29 Cont ID  
Sent By lmartine Date 2000-02-29 Time 07:43 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2000-02-02 Cont ID  
Sent By gjoyce Date 2000-02-02 Time 10:21 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By gjoyce Date 2000-02-01 Time 13:46 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS SURVEY