Plan Review Details - Permit 00011188
Plan Review Stops For Permit 00011188
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-29 Cont ID  
Sent By ndenmark Date 2000-08-29 Time 07:51 Rev Time 0.33
Received By ndenmark Date 2000-08-29 Time 07:51 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.C/U TO BE ON SOLID CONCRETE PAD MIN. 3
 INCHES ABOVE FINISHED GRADE
 2.AREAS W/ 300 CFM OR MORE REQUIRES
 RETURN AIR FROM AREA

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-02-22 Cont ID  
Sent By jleech Date 2000-02-22 Time 16:07 Rev Time 0.25
Received By jleech Date 2000-02-22 Time 15:28 Sent To  
Notes
2001-01-08 00:00:00AIR HANDLER UNIT REQUIRES INFO.
 AMOUNT OF CFM PER SUPPLY AIR DUCT/GRILLE
 REQUIRE GRILLE SIZES
 INDICATE RETURN AIR GRILLE