| Plan Review Stops For Permit 00011143 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-01-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-23 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-23 00:00:00 | PROVIDE PRODUCT APPROVALS FOR THE DOORS, | | | WINDOWS AND ROOF COVERING TO THE | | | BUILDING DIVISION BEFORE INSTALLATION. | | | | | | PROVIDE FIRE DESIGN NUMBER FOR THE 2 | | | HOUR RATED EAST WALL BEFORE | | | CONSTRUCTION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-02 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-02 |
Time |
14:54 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-19 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-19 |
Time |
12:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-10-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-17 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-17 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SIGN AND SEAL PLANS PER | | | FL. ADMINISTRATIVE CODES AND STATE STAT- | | | -UES. 61G15-23.002/ CHAPTER 471.025 | | | | | | 2)NOTE: PLEASE CORRELATE ELECTRICAL PLAN | | | TO FOUNDATION PLAN. OUTLETS/ROOMS DO | | | NOT MATCH.A-2 SHOWS FLOOR OUTLETS AND | | | SWITCHED RECEPTS NOT SHOWN ON A-2. | | | STORAGE AREA NOT SHOWN ON A-4?? | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR NEW LOADS BEING ADDED. LOAD CALCS | | | SHOWN ARE FOR NEW/OLD?? SHEET A-2 SHOWS | | | NEW 150AMP SERVICE WHICH IS NOT SHOWN ON | | | A-4?? | | | | | | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%.(LIGHTING ETC). | | | | | | 5)NOTE: PLEASE SHOWS LOADS FOR TRACK | | | LIGHTING SHOWN, PER 220-12B | | | | | | 6)NOTE: PLEASE SUBMIT PANEL SCHEDULES | | | FOR NEW EQUIPMENT BEING INSTALLED. | | | | | | 7)NOTE: PLEASE SHOW OUTLET LAYOUT THAT | | | CORRELATES TO FLOOR PLAN ON A-2. | | | | | | 8)NOTE: PLEASE CORRELATE LIGHITNG A-2 | | | AND A-4 | | | | | | 9)NOTE: PLEASE CLARIFY LOADS SHOWN FOR | | | HEAT. ??215-5 | | | | | | 10)NOTE: PLEASE SUBMIT MORE SPECS ON NEW | | | EQUIPMENT BEING INSTALLED. 215-5 | | | | | | 11)NOTE: PLEASE SUBMIT AIC RATINGS FOR\\ | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BRKRS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT PER 110-9 AND | | | 110-10. SHOW PER 215-5. | | | | | | 12)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | SYSTEM. EXISTING AND NEW. PLEASE NOTE | | | PER 250-50 ALL NEW BLDG. STEEL AND COLD | | | WATER PIPE TO HAVE GROUNDING ELECTRODE | | | CONNECTION. | | | | | | | | | 13)NOTE: PLEASE SEPARATE LOAD FOR NEW | | | PANELS AND EXISTING.215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2001-03-22 |
Time |
14:15 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-24 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-24 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2001-01-24 00:00:00 | 1) THE PLAN DOES NOT REFLECT THE | | | LOCATION OF THE REAR EXIT FOR THE | | | RESTAURANT. WILL THE LOCATION OF THE | | | NEW DUMPSTER ENCLOSURE BLOCK THE | | | OPENING OF THE DOOR. | | | 2) SITE PLAN DOES NOT REFLECT EXIT DOOR | | | LOCATIONS FOR THE NEW WAREHOUSE. | | | 3) A SET OF DOUBLE DOORS ON THE | | | FOUNDATION PLAN ARE NOT INDICATED TO | | | BE 1 1/2 FIRE RATED. THEY APPEAR TO BE | | | LOCATED IN A TWO HOUR FIRE WALL. | | | 4) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS. A SEPARATE PERMIT IS REQUIRED. | | | 5) THE SMOKE DETECTOR INSTALLED ON THE | | | CEILING IS WHAT TYPE. IS IT ELECTRIC, | | | BATTERY OR TIED INTO THE FIRE ALARM | | | SYSTEM. | | | 6) WHAT WILL BE STORED IN THE WAREHOUSE. | | | 7) DOES EXITING FROM THE RETAIL STORE | | | ENTER INTO THE NEW WAREHOUSE BEFORE | | | REACHING THE EXTERIOR OF THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-08 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-08 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO EMERGENCY LIGHTING EQUIPMENT | | | SHOWN. | | | 2) CLEARLY INDICATE EXIT LOCATIONS. | | | 3) WHY IS AN EXIT DOOR SHOWN LEADING | | | PERSONS THROUGH STORAGE ROOM. | | | 4) WHAT IS THE MANUAL FIRE ALARM BOX | | | CONNECTED TO. | | | 5) THE ROUND CIRCLES WITH SD WITHIN THEM | | | INDICATES WHAT. | | | 6) EXIT DISCHARGE LOCATIONS NOT | | | CLEARLY DEFINED. | | | 7) NO INTERIOR FINISH INFORMATION ON | | | PLANS. | | | 8) EXIT DOORS AND HARDWARE ARE TO BE | | | SHOWN. | | | 9) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-04-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-23 |
Time |
10:56 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-04-23 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2001-04-23 00:00:00 | *******************PROVISO************** | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS | | | PER 1997 SMC 406.1, WITH NOTIFICATION | | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS, NFPA 4-4.4.3. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2001-03-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-26 |
Time |
08:28 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-03-26 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2001-03-26 00:00:00 | *******************DENIED*************** | | | | | | NOTHING CHANGED - O.A. WAS NOT RELOCATED | | | NO EQUIPMENT INFORMATION SUBMITTED MODEL | | | NUMBER,SEER,HEAT,ETC. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-29 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-29 |
Time |
15:05 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-01-29 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2001-01-29 00:00:00 | *************DENIED******************* | | | PROVIDE INFORMATION ON MECHANICAL | | | EQUIPMENT. INCLUDE MODEL NUMBER, SEER | | | RATING, CFM, HEAT IF USED, ETC. | | | | | | RELOCATE OUTSIDE AIR INTAKE FROM AREA OF | | | CONDENSING UNIT, OR RELOCATE CONDENSING | | | UNIT. | | | | | | PROVIDE SPECIFICATION FOR DUCT MATERIAL | | | TO BNE USED AND DIFFUSER SIZES AND | | | RETURN AIR PATH TO EQUIPMENT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-08 |
Time |
09:15 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-11-08 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. INSUFFICIENT INFORMATION PROVIDED | | | FOR REVIEW. | | | 2. PROVIDE INFORMATION ON EQUIPMENTAND | | | MATERIAL TO BE USED. | | | 3. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-21 |
Time |
11:41 |
Rev Time |
0.25 |
| Received By |
tlarge |
Date |
2000-10-21 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO PLBG.THIS PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2001-08-10 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-10 |
Time |
15:30 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2000-12-27 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-10-11 |
Time |
11:50 |
Rev Time |
0.15 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-19 00:00:00 | SEE APPLICATION SIGNED BY SHIRLEY 12/27 | | 2001-01-08 00:00:00 | NEED HC ISLE BETWEEN 2 SPACES |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-01-28 |
Time |
13:39 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|