Plan Review Details - Permit 00011143
Plan Review Stops For Permit 00011143
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-23 Cont ID  
Sent By hpiskura Date 2001-01-23 Time 10:14 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-23 00:00:00PROVIDE PRODUCT APPROVALS FOR THE DOORS,
 WINDOWS AND ROOF COVERING TO THE
 BUILDING DIVISION BEFORE INSTALLATION.
  
 PROVIDE FIRE DESIGN NUMBER FOR THE 2
 HOUR RATED EAST WALL BEFORE
 CONSTRUCTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-02 Cont ID  
Sent By hpiskura Date 2000-11-02 Time 14:54 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-19 Cont ID  
Sent By dpalmer Date 2001-01-19 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2001-01-19 Time 12:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-17 Cont ID  
Sent By dpalmer Date 2000-10-17 Time 07:39 Rev Time 0.00
Received By dpalmer Date 2000-10-17 Time 07:39 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SIGN AND SEAL PLANS PER
 FL. ADMINISTRATIVE CODES AND STATE STAT-
 -UES. 61G15-23.002/ CHAPTER 471.025
  
 2)NOTE: PLEASE CORRELATE ELECTRICAL PLAN
 TO FOUNDATION PLAN. OUTLETS/ROOMS DO
 NOT MATCH.A-2 SHOWS FLOOR OUTLETS AND
 SWITCHED RECEPTS NOT SHOWN ON A-2.
 STORAGE AREA NOT SHOWN ON A-4??
  
 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR NEW LOADS BEING ADDED. LOAD CALCS
 SHOWN ARE FOR NEW/OLD?? SHEET A-2 SHOWS
 NEW 150AMP SERVICE WHICH IS NOT SHOWN ON
 A-4??
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.(LIGHTING ETC).
  
 5)NOTE: PLEASE SHOWS LOADS FOR TRACK
 LIGHTING SHOWN, PER 220-12B
  
 6)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR NEW EQUIPMENT BEING INSTALLED.
  
 7)NOTE: PLEASE SHOW OUTLET LAYOUT THAT
 CORRELATES TO FLOOR PLAN ON A-2.
  
 8)NOTE: PLEASE CORRELATE LIGHITNG A-2
 AND A-4
  
 9)NOTE: PLEASE CLARIFY LOADS SHOWN FOR
 HEAT. ??215-5
  
 10)NOTE: PLEASE SUBMIT MORE SPECS ON NEW
 EQUIPMENT BEING INSTALLED. 215-5
  
 11)NOTE: PLEASE SUBMIT AIC RATINGS FOR\\
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BRKRS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9 AND
 110-10. SHOW PER 215-5.
  
 12)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM. EXISTING AND NEW. PLEASE NOTE
 PER 250-50 ALL NEW BLDG. STEEL AND COLD
 WATER PIPE TO HAVE GROUNDING ELECTRODE
 CONNECTION.
  
  
 13)NOTE: PLEASE SEPARATE LOAD FOR NEW
 PANELS AND EXISTING.215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-03-22 Cont ID  
Sent By rturnque Date 2001-03-22 Time 14:15 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-01-24 Cont ID  
Sent By mcarsill Date 2001-01-24 Time 10:21 Rev Time 0.00
Received By mcarsill Date 2001-01-24 Time 10:20 Sent To  
Notes
2001-01-24 00:00:001) THE PLAN DOES NOT REFLECT THE
 LOCATION OF THE REAR EXIT FOR THE
 RESTAURANT. WILL THE LOCATION OF THE
 NEW DUMPSTER ENCLOSURE BLOCK THE
 OPENING OF THE DOOR.
 2) SITE PLAN DOES NOT REFLECT EXIT DOOR
 LOCATIONS FOR THE NEW WAREHOUSE.
 3) A SET OF DOUBLE DOORS ON THE
 FOUNDATION PLAN ARE NOT INDICATED TO
 BE 1 1/2 FIRE RATED. THEY APPEAR TO BE
 LOCATED IN A TWO HOUR FIRE WALL.
 4) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS. A SEPARATE PERMIT IS REQUIRED.
 5) THE SMOKE DETECTOR INSTALLED ON THE
 CEILING IS WHAT TYPE. IS IT ELECTRIC,
 BATTERY OR TIED INTO THE FIRE ALARM
 SYSTEM.
 6) WHAT WILL BE STORED IN THE WAREHOUSE.
 7) DOES EXITING FROM THE RETAIL STORE
 ENTER INTO THE NEW WAREHOUSE BEFORE
 REACHING THE EXTERIOR OF THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-08 Cont ID  
Sent By mcarsill Date 2000-11-08 Time 11:42 Rev Time 0.00
Received By mcarsill Date 2000-11-08 Time 11:42 Sent To  
Notes
2001-01-08 00:00:001) NO EMERGENCY LIGHTING EQUIPMENT
 SHOWN.
 2) CLEARLY INDICATE EXIT LOCATIONS.
 3) WHY IS AN EXIT DOOR SHOWN LEADING
 PERSONS THROUGH STORAGE ROOM.
 4) WHAT IS THE MANUAL FIRE ALARM BOX
 CONNECTED TO.
 5) THE ROUND CIRCLES WITH SD WITHIN THEM
 INDICATES WHAT.
 6) EXIT DISCHARGE LOCATIONS NOT
 CLEARLY DEFINED.
 7) NO INTERIOR FINISH INFORMATION ON
 PLANS.
 8) EXIT DOORS AND HARDWARE ARE TO BE
 SHOWN.
 9) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-04-23 Cont ID  
Sent By pkrauss Date 2001-04-23 Time 10:56 Rev Time 0.40
Received By pkrauss Date 2001-04-23 Time 10:56 Sent To  
Notes
2001-04-23 00:00:00*******************PROVISO**************
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS
 PER 1997 SMC 406.1, WITH NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS, NFPA 4-4.4.3.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-03-26 Cont ID  
Sent By pkrauss Date 2001-03-26 Time 08:28 Rev Time 0.25
Received By pkrauss Date 2001-03-26 Time 08:26 Sent To  
Notes
2001-03-26 00:00:00*******************DENIED***************
  
 NOTHING CHANGED - O.A. WAS NOT RELOCATED
 NO EQUIPMENT INFORMATION SUBMITTED MODEL
 NUMBER,SEER,HEAT,ETC.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-01-29 Cont ID  
Sent By ndenmark Date 2001-01-29 Time 15:05 Rev Time 0.50
Received By ndenmark Date 2001-01-29 Time 15:05 Sent To  
Notes
2001-01-29 00:00:00*************DENIED*******************
 PROVIDE INFORMATION ON MECHANICAL
 EQUIPMENT. INCLUDE MODEL NUMBER, SEER
 RATING, CFM, HEAT IF USED, ETC.
  
 RELOCATE OUTSIDE AIR INTAKE FROM AREA OF
 CONDENSING UNIT, OR RELOCATE CONDENSING
 UNIT.
  
 PROVIDE SPECIFICATION FOR DUCT MATERIAL
 TO BNE USED AND DIFFUSER SIZES AND
 RETURN AIR PATH TO EQUIPMENT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-08 Cont ID  
Sent By ndenmark Date 2000-11-08 Time 09:15 Rev Time 0.33
Received By ndenmark Date 2000-11-08 Time 09:13 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. INSUFFICIENT INFORMATION PROVIDED
 FOR REVIEW.
 2. PROVIDE INFORMATION ON EQUIPMENTAND
 MATERIAL TO BE USED.
 3. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 11:41 Rev Time 0.25
Received By tlarge Date 2000-10-21 Time 11:41 Sent To  
Notes
2001-01-08 00:00:00NO PLBG.THIS PERMIT.

Review Stop Z ZONING
Rev No 3 Status P Date 2001-08-10 Cont ID  
Sent By sgraham Date 2001-08-10 Time 15:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2000-12-27 Cont ID  
Sent By gjoyce Date 2000-10-11 Time 11:50 Rev Time 0.15
Received By lmartine Date   Time   Sent To  
Notes
2001-01-19 00:00:00SEE APPLICATION SIGNED BY SHIRLEY 12/27
2001-01-08 00:00:00NEED HC ISLE BETWEEN 2 SPACES

Review Stop Z ZONING
Rev No 1 Status F Date 2000-01-28 Cont ID  
Sent By gjoyce Date 2000-01-28 Time 13:39 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***