| Plan Review Stops For Permit 00011033 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-06-29 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2001-06-29 |
Time |
15:36 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-29 00:00:00 | AS BUILTS RELEASED 6/29/01 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-01-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-16 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-16 00:00:00 | ADDITIONAL PERMIT FEES MUST BE PAID TO | | | THE CITY FOR THE INTERIOR FITUP. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-06 |
Time |
09:27 |
Rev Time |
1.50 |
| Received By |
drunnels |
Date |
2000-10-06 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-05-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-05-03 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NEEDS FL ENERGY CODE & IMPACT FEES |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-03-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-03-28 |
Time |
16:01 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
ENG |
|
| Notes |
| 2001-01-08 00:00:00 | CKLST ATTACHED TO APP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2001-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-06 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-06 |
Time |
09:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-22 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-22 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
21:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-11 |
Time |
21:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-09-13 |
Time |
14:20 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-09-13 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-05-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-05-03 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-09-13 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO **************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL COTINUOUS LOADS. 125% FOR | | | LIGHTING. | | | | | | PLEASE SUBMIT FOR REVIEW BEFORE ANY | | | ROUGH/ELECTRICAL INSPECTION IS CALLED IN | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-15 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-15 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE:AS REQ`D BY 240-13 OF THE NEC. | | | GFI PROTECTION FOR 1000AMPS OR MORE IS | | | REQ`DPLEASE SUBMIT PLANS SHOWING | | | MAIN BUS/EQUIPMENT MEETING THAT | | | REQ`MENT. | | | | | | 2)NOTE: PLEASE SHOW COMPLETE GROUNDING | | | ELECTRODE SYSTEM BEING INSTALLED. TO | | | INCLUDE ALL BLDG.STEEL,CWP,AND FOUND-TIO | | | -ATION STEEL. AS REQ`D PER 250-81 | | | | | | 3)NOTE: PAGE E-107 PLEASE NOTE ROOF TOP | | | GFI REC. REQ`D BY 210-63 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2000-06-02 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-06-02 |
Time |
11:57 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED | | | AFTER SPEKING WITH HAROLD PISKURA | | | THERE WILL BE NO CONFLICT IN LOWERING | | | THE FOUNDATION OF THE BUILDING. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2000-03-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-03-28 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
dlauderm |
Date |
2000-05-15 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED WITH PROVISO: | | | SEWER SYSTEM WILL BE DESIGN BY LNW TO | | | RUN DOWN TRINITY NOT AS SUBMITTED. | | | PERMISSION IS GRANTED TO CONSTRUCT | | | BUILDING AND SUBMIT NEW SANITARY PLAN. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2001-06-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-06 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-06 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2001-06-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-01 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-01 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2001-06-01 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FUTURE SECURITY GATES. | | | 2) DECORATIVE GATES LOCATED ON WEST SIDE | | | OF BUILDING IS NOT TO INTERFERE WITH | | | ANY EXITING FROM THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2001-01-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-10 |
Time |
12:40 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2001-01-10 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2001-01-29 00:00:00 | PREVIOUS NOTES TRANSFERRED TO PERMIT | | | #01011195.REVIEW WAS DONE UNDER | | | "SHELL" PERMIT...NEEDED TO APPLY FOR | | | NEW PERMIT, MECH. ENG. CHANGED. | | | PHK. | | 2001-01-10 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED ON | | | SHEET A-001. SHOULD READ 1985 EDITION | | | INSTEAD OF 1994 EDITION. | | | 2) PROVIDE SEPARATE PLANS AND PERMIT FOR | | | FIRE SPRINKLER REMODEL. | | | 3) PROVIDE SEPARATE PLANS AND PERMIT FOR | | | FIRE ALARM EQUIPMENT SHOWN ON DRAWINGS. | | | SYSTEM TO BE CLASS A OR ADDRESSABLE. CUT | | | SHEETS, WIRING DIAGRAM, FLOOR PLANS, AND | | | BATTERY CALCULATIONS ARE TO BE PROVIDED. | | | 4) PLEASE CLEARLY IDENTIFY EMERGENCY | | | LIGHTING LOCATIONS WITHIN TENANT SPACE. | | | 5) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR TENANT | | | SPACE. | | | 6) PLEASE DISPLAY LOCATIONS OF PORTABLE | | | FIRE EXTINGUISHERS. PLEASE PROVIDE | | | RATING FOR EXTINGUISHERS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-06 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-06 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PROVISIONS ARE TO BE MADE FOR FIRE | | | AND PARAMEDICAL ACCESS THRU FUTURE | | | SECURITY GATE. HOW DOES FIRE AND | | | PARAMEDICAL UNITS ENTER THRU THE GATES. | | | 2) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-08-01 |
Time |
14:23 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-05-05 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-05-05 |
Time |
13:25 |
Rev Time |
0.45 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE EXIT LIGHT ILLUMINATION | | | THROUGHOUT | | | FIRE ALARM SYSTEM SHALL BE CLASS "A" | | | OR ADDRESSABLE |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-01-28 |
Time |
10:29 |
Rev Time |
0.25 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-06-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-11 |
Time |
13:37 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-06-11 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2001-06-11 00:00:00 | ENGINEER CHANGED. | | | | | | ADDED DRAWINGS M-001, M-104 THRU M-602. | | | | | | M-101 CONDENSATE NOTE TAKEN OFF PLAN. | | | | | | M-102 CHANGED LOCATION OF AHU 2.1 - 2.5. | | | | | | MECHANICAL PERMIT 00101457 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-22 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
ndenmark |
Date |
2001-01-22 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-14 |
Time |
10:39 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-12-14 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
A |
Date |
2000-05-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-05-04 |
Time |
15:51 |
Rev Time |
1.50 |
| Received By |
ndenmark |
Date |
2000-05-04 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: PROVIDE THE FOLLOWING | | | 1) PROVIDE INFORMATION ON OUTSIDE AIR | | | REQUIREMENTS PER ASHRAE 62-89 | | | 2) INSUFFICIENT DETAILS ON DUCTS FOR | | | A/C SYTEMS | | | 3) 1997 SMC 610 REQUIRES FIRE PROTECTION | | | OF FLOOR/CEILING ASSEMBLY. FIRE DAMPERS | | | NOT SHOWN | | | THE INFORMATION ABOVE IS TO BE PROVIDED | | | PRIOR TO ANY BUILDOUT, THIS PERMIT APPLI | | | CATION IS FOR SHELL ONLY NO MECHANICAL | | | UNTIL INFORMATION PROVIDED FOR REVIEW | | | AND ACCEPTED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
A |
Date |
2000-05-16 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-02-01 |
Time |
08:48 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-02-01 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ACCEPTED BY REVISION SEE LATEST NOTES* | | | | | | INSUFFICIENT INFORMATION TO REVIEW | | | PROVIDE DETAILS ON OUTSIDE AIR PER | | | ASHRAE 62-89 | | | EXHAUST FANS ON SHT M-103 ARE LABELED TO | | | SERVE 1ST FLOOR WHAT SERVES SECOND FLOOR | | | PROVIDE DETAIL ON DUCT PENETRATING FROM | | | ROOF TO 1ST FLOOR | | | INDICATE ANY REQUIREMENTS FOR FIRE PROT- | | | ECTION AT ALL PENETRATIONS | | | PROVIDE DETAILS ON DUCT, SIZE, MATERIAL | | | AND LOCATION | | | PROVIDE CONDENSATE DRAIN INFORMATION | | | PROVIDE INFORMATION ON REQUIRED FAN SHUT | | | DOWN BY DUCT SMOKE DETECTORS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2001-06-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-15 |
Time |
10:24 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-06-15 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2001-06-15 00:00:00 | REVISIONS FOR PLUMBING AS CLOUDED ON | | | PAGES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-13 |
Time |
10:20 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2001-06-13 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2001-06-13 00:00:00 | REVIEW NOTES: FAILED | | | | | | PLEASE CLOUD OR DART ALL REVISIONS FOR | | | THESE PAGES. UNABLE TO DETERMINE WHAT | | | EXACTLY HAS BEEN REVISED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2001-04-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-11 |
Time |
19:08 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-04-11 |
Time |
19:08 |
Sent To |
|
|
| Notes |
| 2001-04-11 00:00:00 | REVISION; RELOCATED BACK FLOW ON SITE | | | PLAN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2001-04-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-04-08 |
Time |
08:07 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-08 00:00:00 | 900 GAL GREASE TANK,APPROVED.PLBG PERMIT | | | APPLIED FOR # 01031126 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-19 |
Time |
16:34 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-01-19 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2001-01-29 00:00:00 | PREVIOUS NOTES TRANSFERRED TO PERMIT | | | #01011195.REVIEW WAS DONE UNDER | | | "SHELL" PERMIT...NEEDED TO APPLY FOR | | | NEW PERMIT, MECH. ENG. CHANGED. | | | PHK. | | 2001-01-19 00:00:00 | 1.KITCHEN SINK SHT A-4 MUST COMPLY WITH | | | 97 FACBC 4.24.1 THRU 4.24.7. | | | | | | 2.AIR CHAMBERS TO COMPLY WITH 94 SPC | | | 607.8.2. | | | | | | 3. FIXTURE CONNECTION SCHEDULE SHOWS | | | FLOOR DRAINS, BUT ARE NOT SHOWN ON | | | DRAWINGS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-06-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-12 |
Time |
18:41 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-06-12 |
Time |
18:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2000-05-17 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-17 |
Time |
18:07 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
2000-05-17 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | REVISED PLUMBING SHEETS SHOWING ALL | | | CORRECTIONS SHALL BE SUBMITTED FOR | | | REVIEW PRIOR TO ISSUANCE OF PLUMBING | | | PERMIT.ALL SHEETS SAHLL BE SIGNED AND | | | SEALED PER FLA.STATUTE. | | | | | | SHOW SQ.FT.OF ROOF AREA DRAINED BY EACH | | | DRAIN.COMPLY W/SPC SEC.1108.1,1108.2, | | | 1108.3.INCLUDE 1/2 AREA OF VERTICAL WALL | | | PER SPC SEC.1108.3. | | | | | | A PERMIT FOR THE DOMESTIC WATER AND FIRE | | | SERVICE IS REQD.FROM THE DEPT.OF | | | ENVIRONMENTAL PROTECTION.CONTACT PALM | | | BEACH COUNT HEALTH DEPT.A PERMIT MAY | | | ALSO BE REQD.FROM PALM BEACH COUNTY | | | HEALTH DEPT.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.101.4.7. | | | | | | PLUMBING SHEETS SHOW DOMESTIC WATER | | | SERVICE AS 3" AND CIVILS SHOW 2".CLARIFY | | | | | | FLOOR DRAINS ARE NOT PROPERLY VENTED. | | | COMPLY W/SPC SEC.901.2. | | | | | | VENTS FOR WATER CLOSETS SHALL COMPLY W/ | | | SPC SEC.920.2.(NO LESS THAN 1/2 THE | | | DIAMETER OF THE DRAIN SERVED.) | | | | | | WATER HEATER ON 2ND FLOOR SHALL BE | | | EQUIPPED W/PAN AND DRAIN PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.507.8.1. | | | | | | DRINKING FOUNTAINS ARE NOT SHOWN ON THE | | | SANITARY OR WATER RISERS.COUNTYWIDE | | | AMENBDMENTS TO SPC SEC.104.2.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-05-03 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-03 |
Time |
11:53 |
Rev Time |
5.50 |
| Received By |
tlarge |
Date |
2000-05-03 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT.A-103-AN ADDITIONAL STALL IN THE | | | WOMEN'S RESTROOM #207 IS REQD.TO COMPLY | | | W/FACBC SEC.4.22.4. | | | | | | SHT.A-403-A FULLY ACCESSIBLE H.C.TOILET | | | STALL IS REQD.IN THE WOMEN'S RESTROOM | | | #119 WITH A LAVATORY LOCATED WITHIN THE | | | STALL PER FACBC SEC.4.1.2.((6),4.17.3. | | | | | | SHT.A-403-AN ADDITIONAL STALL IN THE | | | WOMEN'S RESTROOM #119 IS REQD.TO COMPLY | | | W/FACBC SEC.4.22.4. | | | | | | DRINKING FOUNTAINS SHALL ALLOW FOR A | | | FRONT APPROACH PER FACBC SEC.4.15.5(1), | | | FIG.#27. | | | | | | WIDTH OF REQD.FULLY ACCESSIBLE STALL | | | SHALL COMPLY W/FACBC SEC.4.17.3.(SEE | | | EXCEPTION:NEW CONSTRUCTION.) | | | | | | SUBMIT COMPLETE ISOMETRIC DRAWING FOR | | | THE STORM DRAINAGE SYSTEM.SHOW ALL PIPE | | | SIZES,SQ.FOOT OF ROOF AREA DRAINED BY | | | EACH DRAIN.COMPLY W/SPC SEC.1108.1, | | | 1108.2,1108.3.(INCLUDE 1/2 AREA OF | | | PARAPET WALLS PER SPC SEC.1108.3) | | | | | | SUBMIT CALCULATIONS FOR SECONDARY | | | (EMERGENCY )ROOF DRAINS.INCLUDE 1/2 OF | | | VERTICAL AREA OF PARAPET WALLS PER SPC | | | SEC.1108.3,1109.1,1109.2,1109.3 & | | | APPENDIX "A". | | | | | | A PERMIT FOR THE DOMESTIC WATER AND FIRE | | | SERVICE IS REQD.FROM DEP.CONTACT PALM | | | BEACH COUNTY HEALTH DEPT.A PERMIT MAY | | | ALSO BE REQD.FROM PALM BEACH COUNTY | | | HEALTH DEPT. | | | | | | PLUMBING SHEETS SHOW WATER SERVICE AS 3" | | | AND CIVILS SHOW 2".CLARIFY. | | | | | | FLOOR DRAINS NOT PROPERLY VENTED.COMPLY | | | W/SPC 901.2. | | | | | | SHT.P-601-VENTS FOR WATER CLOSETS SHALL | | | COMPLY W/SPC SEC.920.2.(NOT LESS THAN | | | 1/2 THE DIAMETER OF THE DRAIN SERVED.) | | | | | | SIZE TYPICAL WASTE STACKS FOR FIXTURES. | | | COMPLY W/SPC SEC.920.2. | | | | | | WATER HEATER ON 2ND.FLOOR SHALL BE | | | EQUIPPED W/PAN AND DRAIN PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.507.8.1. | | | | | | DRINKING FOUNTAINS ARE NOT SHOWN ON THE | | | SANITARY OR WATER RISERS.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | WATER SUPPLY CONTROL FOR HOT WATER SHALL | | | COMPLY W/SPC SEC.610.4.1. | | | | | | SUBMIT JOB SPECIFICATIONS FOR RE-REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-02-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-08 |
Time |
12:56 |
Rev Time |
7.50 |
| Received By |
tlarge |
Date |
2000-02-08 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | JOB SPEC 15400-7-2.07(5)-SPACING OF | | | CLEANOUTS SHALL COMPLY W/SPC SEC.710.2.4 | | | | | | SPEC.15400-9-2.13-HORIZONTAL SUPPORTS | | | COPPER TUBING SHALL COMPLY W/SPC SEC. | | | 310.3.4. | | | | | | TOILET STALL DOOR IN MEN'S R.R.CANNOT | | | SWING INTO CLEAR FLOOR SPACE FOR URINAL | | | PER FACBC SEC.4.17.5. | | | | | | AN ADDITIONAL HANDICAP STALL IS REQD.IN | | | THE WOMEN'S TOILET ROOM PER FACBC SEC. | | | 4.22.4. | | | | | | DRINKING FOUNTAINS SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).(PROVISIONS SHALL BE | | | MADE FOR PERSONS WHO HAVE TROUBLE | | | BENDING OR STOOPING.) | | | | | | SHT.A403.-LAVATORY REQD.IN HANDICAP | | | STALL PER FACBC SEC.4.17.3.(SEE RM.119) | | | | | | WALLS AND FLOORS TO A HEIGHT OF FOUR | | | FEET SHALL BE NONABSORBENT MATERIAL PER | | | SBC 1204.2. | | | | | | TOILET FLOOR PLAN ON A-403 DOESN'T | | | CORRELATE W/OTHER PLANS.CLARIFY. | | | | | | THE WIDTH OF THE HANDICAP STALLS SHALL | | | COMPLY W/FACBC SEC.4.17.3 (MIN.79"+2" | | | FOR CLEANING.) | | | | | | LOCATION OF BACKFLOW DETECTION DEVICE | | | SHALL BE DETERMINED BY CITY OF WPB | | | UTILITIES, | | | | | | VENTS FOR FLOOR DRAINS SHALL COMPLY W/ | | | SPC SEC.906.2.1.(VENT SHALL RISE | | | VERTICALLY TO A POINT 6" ABOVE FLOOD | | | LEVEL RIM OF FIXTURE BEFORE OFFSETTING | | | HORIZ.PROPERLY VENT FLOOR DRAINS. | | | | | | SHT.P-501-RELIEF LINE SHALL DRAIN TO | | | EXTERIOR PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.507.6(3). | | | | | | SHT.P-101- 7 W.C.'S SHOWN ON FLOOR PLAN | | | AND SIX ARE SHOWN ON ISOMETRIC.CLARIFY. | | | | | | CLEARLY SIZE ALL SECTIONS OF THE | | | SANITARY RISERPER COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | INDICATE SLOPE OF PIPE FOR SANITARY | | | SYSTEM.COMPLY W/SPC TABLE 714.1,714.2. | | | SHOW FIXTURE UNIT LOAD ON SYSTEM. | | | | | | HOSE BIBBS REQUIRE SHUT-OFF VALVES PER | | | SPC SEC.610.4.1. | | | | | | SUBMIT ISOMETRIC FOR COMPLETE STORM | | | SYSTEM.SHOW SQ.FOOTAGE OF ROOF AREA | | | DRAINED BY EA.DRAIN.COMPLY W/SPC SEC. | | | 1108.1,1108.2. | | | | | | SUBMIT CALCULATIONS FOR SECONDARY DRAIN- | | | AGE.INCLUDE 1/2 VERTICAL AREA OF PARAPET | | | WALL PER SPC SEC.1108.3.,1109.1,1109.2, | | | 1109.3.AND APPENDIX "A". | | | | | | APPROVALS REQD.FROM ENGINEERING FOR | | | STORM WATER DRAINAGE AND FROM P.B.COUNTY | | | HEALTH DEPT.FOR WATER MAIN INSTALLATION. | | | SPC 101.4.7. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-03-02 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-03-02 |
Time |
13:36 |
Rev Time |
0.50 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|