Plan Review Details - Permit 00011033
Plan Review Stops For Permit 00011033
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-06-29 Cont ID  
Sent By bstaples Date 2001-06-29 Time 15:36 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-06-29 00:00:00AS BUILTS RELEASED 6/29/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-01-16 Cont ID  
Sent By hpiskura Date 2001-01-16 Time 10:16 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-16 00:00:00ADDITIONAL PERMIT FEES MUST BE PAID TO
 THE CITY FOR THE INTERIOR FITUP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-10-06 Cont ID  
Sent By drunnels Date 2000-10-06 Time 09:27 Rev Time 1.50
Received By drunnels Date 2000-10-06 Time 09:27 Sent To  
Notes
2001-01-08 00:00:00REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-05-03 Cont ID  
Sent By hpiskura Date 2000-05-03 Time 16:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS FL ENERGY CODE & IMPACT FEES

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-03-28 Cont ID  
Sent By hpiskura Date 2000-03-28 Time 16:01 Rev Time 99.00
Received By hpiskura Date   Time   Sent To ENG
Notes
2001-01-08 00:00:00CKLST ATTACHED TO APP

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-06-06 Cont ID  
Sent By dpalmer Date 2001-06-06 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2001-06-06 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 08:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 21:46 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 21:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-13 Cont ID  
Sent By jleahy Date 2000-09-13 Time 14:20 Rev Time 1.00
Received By ndenmark Date 2000-09-13 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 18:48 Rev Time 0.00
Received By jleahy Date 2000-09-13 Time 13:58 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL COTINUOUS LOADS. 125% FOR
 LIGHTING.
  
 PLEASE SUBMIT FOR REVIEW BEFORE ANY
 ROUGH/ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-15 Cont ID  
Sent By dpalmer Date 2000-02-15 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2000-02-15 Time 12:38 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *****************
  
 1)NOTE:AS REQ`D BY 240-13 OF THE NEC.
 GFI PROTECTION FOR 1000AMPS OR MORE IS
 REQ`DPLEASE SUBMIT PLANS SHOWING
 MAIN BUS/EQUIPMENT MEETING THAT
 REQ`MENT.
  
 2)NOTE: PLEASE SHOW COMPLETE GROUNDING
 ELECTRODE SYSTEM BEING INSTALLED. TO
 INCLUDE ALL BLDG.STEEL,CWP,AND FOUND-TIO
 -ATION STEEL. AS REQ`D PER 250-81
  
 3)NOTE: PAGE E-107 PLEASE NOTE ROOF TOP
 GFI REC. REQ`D BY 210-63
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-06-02 Cont ID  
Sent By mgonzale Date 2000-06-02 Time 11:57 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 AFTER SPEKING WITH HAROLD PISKURA
 THERE WILL BE NO CONFLICT IN LOWERING
 THE FOUNDATION OF THE BUILDING.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-03-30 Cont ID  
Sent By hpiskura Date 2000-03-28 Time 16:01 Rev Time 0.00
Received By dlauderm Date 2000-05-15 Time 15:09 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISO:
 SEWER SYSTEM WILL BE DESIGN BY LNW TO
 RUN DOWN TRINITY NOT AS SUBMITTED.
 PERMISSION IS GRANTED TO CONSTRUCT
 BUILDING AND SUBMIT NEW SANITARY PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2001-06-06 Cont ID  
Sent By mcarsill Date 2001-06-06 Time 09:02 Rev Time 0.00
Received By mcarsill Date 2001-06-06 Time 09:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-06-01 Cont ID  
Sent By mcarsill Date 2001-06-01 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2001-06-01 Time 11:22 Sent To  
Notes
2001-06-01 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FUTURE SECURITY GATES.
 2) DECORATIVE GATES LOCATED ON WEST SIDE
 OF BUILDING IS NOT TO INTERFERE WITH
 ANY EXITING FROM THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2001-01-10 Cont ID  
Sent By mcarsill Date 2001-01-10 Time 12:40 Rev Time 1.00
Received By ndenmark Date 2001-01-10 Time 12:40 Sent To  
Notes
2001-01-29 00:00:00PREVIOUS NOTES TRANSFERRED TO PERMIT
 #01011195.REVIEW WAS DONE UNDER
 "SHELL" PERMIT...NEEDED TO APPLY FOR
 NEW PERMIT, MECH. ENG. CHANGED.
 PHK.
2001-01-10 00:00:001) WRONG LIFE SAFETY CODE REFERENCED ON
 SHEET A-001. SHOULD READ 1985 EDITION
 INSTEAD OF 1994 EDITION.
 2) PROVIDE SEPARATE PLANS AND PERMIT FOR
 FIRE SPRINKLER REMODEL.
 3) PROVIDE SEPARATE PLANS AND PERMIT FOR
 FIRE ALARM EQUIPMENT SHOWN ON DRAWINGS.
 SYSTEM TO BE CLASS A OR ADDRESSABLE. CUT
 SHEETS, WIRING DIAGRAM, FLOOR PLANS, AND
 BATTERY CALCULATIONS ARE TO BE PROVIDED.
 4) PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHTING LOCATIONS WITHIN TENANT SPACE.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR TENANT
 SPACE.
 6) PLEASE DISPLAY LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS. PLEASE PROVIDE
 RATING FOR EXTINGUISHERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-10-06 Cont ID  
Sent By mcarsill Date 2000-10-06 Time 09:07 Rev Time 0.00
Received By mcarsill Date 2000-10-06 Time 09:07 Sent To  
Notes
2001-01-08 00:00:001) PROVISIONS ARE TO BE MADE FOR FIRE
 AND PARAMEDICAL ACCESS THRU FUTURE
 SECURITY GATE. HOW DOES FIRE AND
 PARAMEDICAL UNITS ENTER THRU THE GATES.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-01 Cont ID  
Sent By rturnque Date 2000-08-01 Time 14:23 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-05-05 Cont ID  
Sent By rturnque Date 2000-05-05 Time 13:25 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE EXIT LIGHT ILLUMINATION
 THROUGHOUT
 FIRE ALARM SYSTEM SHALL BE CLASS "A"
 OR ADDRESSABLE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By rturnque Date 2000-01-28 Time 10:29 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-06-11 Cont ID  
Sent By pkrauss Date 2001-06-11 Time 13:37 Rev Time 0.40
Received By pkrauss Date 2001-06-11 Time 12:56 Sent To  
Notes
2001-06-11 00:00:00ENGINEER CHANGED.
  
 ADDED DRAWINGS M-001, M-104 THRU M-602.
  
 M-101 CONDENSATE NOTE TAKEN OFF PLAN.
  
 M-102 CHANGED LOCATION OF AHU 2.1 - 2.5.
  
 MECHANICAL PERMIT 00101457

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By ndenmark Date 2001-01-22 Time 08:50 Rev Time 0.00
Received By ndenmark Date 2001-01-22 Time 08:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 10:39 Rev Time 0.25
Received By ndenmark Date 2000-12-14 Time 10:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status A Date 2000-05-09 Cont ID  
Sent By ndenmark Date 2000-05-04 Time 15:51 Rev Time 1.50
Received By ndenmark Date 2000-05-04 Time 15:51 Sent To  
Notes
2001-01-08 00:00:00PROVISO: PROVIDE THE FOLLOWING
 1) PROVIDE INFORMATION ON OUTSIDE AIR
 REQUIREMENTS PER ASHRAE 62-89
 2) INSUFFICIENT DETAILS ON DUCTS FOR
 A/C SYTEMS
 3) 1997 SMC 610 REQUIRES FIRE PROTECTION
 OF FLOOR/CEILING ASSEMBLY. FIRE DAMPERS
 NOT SHOWN
 THE INFORMATION ABOVE IS TO BE PROVIDED
 PRIOR TO ANY BUILDOUT, THIS PERMIT APPLI
 CATION IS FOR SHELL ONLY NO MECHANICAL
 UNTIL INFORMATION PROVIDED FOR REVIEW
 AND ACCEPTED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-05-16 Cont ID  
Sent By ndenmark Date 2000-02-01 Time 08:48 Rev Time 1.00
Received By ndenmark Date 2000-02-01 Time 08:48 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED BY REVISION SEE LATEST NOTES*
  
 INSUFFICIENT INFORMATION TO REVIEW
 PROVIDE DETAILS ON OUTSIDE AIR PER
 ASHRAE 62-89
 EXHAUST FANS ON SHT M-103 ARE LABELED TO
 SERVE 1ST FLOOR WHAT SERVES SECOND FLOOR
 PROVIDE DETAIL ON DUCT PENETRATING FROM
 ROOF TO 1ST FLOOR
 INDICATE ANY REQUIREMENTS FOR FIRE PROT-
 ECTION AT ALL PENETRATIONS
 PROVIDE DETAILS ON DUCT, SIZE, MATERIAL
 AND LOCATION
 PROVIDE CONDENSATE DRAIN INFORMATION
 PROVIDE INFORMATION ON REQUIRED FAN SHUT
 DOWN BY DUCT SMOKE DETECTORS

Review Stop P PLUMBING
Rev No 9 Status P Date 2001-06-15 Cont ID  
Sent By kstevens Date 2001-06-15 Time 10:24 Rev Time 0.33
Received By kstevens Date 2001-06-15 Time 10:24 Sent To  
Notes
2001-06-15 00:00:00REVISIONS FOR PLUMBING AS CLOUDED ON
 PAGES.

Review Stop P PLUMBING
Rev No 8 Status F Date 2001-06-13 Cont ID  
Sent By kstevens Date 2001-06-13 Time 10:20 Rev Time 0.75
Received By kstevens Date 2001-06-13 Time 10:19 Sent To  
Notes
2001-06-13 00:00:00REVIEW NOTES: FAILED
  
 PLEASE CLOUD OR DART ALL REVISIONS FOR
 THESE PAGES. UNABLE TO DETERMINE WHAT
 EXACTLY HAS BEEN REVISED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 7 Status P Date 2001-04-11 Cont ID  
Sent By jleech Date 2001-04-11 Time 19:08 Rev Time 0.50
Received By jleech Date 2001-04-11 Time 19:08 Sent To  
Notes
2001-04-11 00:00:00REVISION; RELOCATED BACK FLOW ON SITE
 PLAN.

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-04-08 Cont ID  
Sent By pschmitz Date 2001-04-08 Time 08:07 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-04-08 00:00:00900 GAL GREASE TANK,APPROVED.PLBG PERMIT
 APPLIED FOR # 01031126

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-01-19 Cont ID  
Sent By jleech Date 2001-01-19 Time 16:34 Rev Time 1.00
Received By jleech Date 2001-01-19 Time 16:34 Sent To  
Notes
2001-01-29 00:00:00PREVIOUS NOTES TRANSFERRED TO PERMIT
 #01011195.REVIEW WAS DONE UNDER
 "SHELL" PERMIT...NEEDED TO APPLY FOR
 NEW PERMIT, MECH. ENG. CHANGED.
 PHK.
2001-01-19 00:00:001.KITCHEN SINK SHT A-4 MUST COMPLY WITH
 97 FACBC 4.24.1 THRU 4.24.7.
  
 2.AIR CHAMBERS TO COMPLY WITH 94 SPC
 607.8.2.
  
 3. FIXTURE CONNECTION SCHEDULE SHOWS
 FLOOR DRAINS, BUT ARE NOT SHOWN ON
 DRAWINGS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096EXT. 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-06-12 Cont ID  
Sent By tlarge Date 2000-06-12 Time 18:41 Rev Time 1.25
Received By tlarge Date 2000-06-12 Time 18:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2000-05-17 Cont ID  
Sent By tlarge Date 2000-05-17 Time 18:07 Rev Time 3.00
Received By tlarge Date 2000-05-17 Time 18:07 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 REVISED PLUMBING SHEETS SHOWING ALL
 CORRECTIONS SHALL BE SUBMITTED FOR
 REVIEW PRIOR TO ISSUANCE OF PLUMBING
 PERMIT.ALL SHEETS SAHLL BE SIGNED AND
 SEALED PER FLA.STATUTE.
  
 SHOW SQ.FT.OF ROOF AREA DRAINED BY EACH
 DRAIN.COMPLY W/SPC SEC.1108.1,1108.2,
 1108.3.INCLUDE 1/2 AREA OF VERTICAL WALL
 PER SPC SEC.1108.3.
  
 A PERMIT FOR THE DOMESTIC WATER AND FIRE
 SERVICE IS REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION.CONTACT PALM
 BEACH COUNT HEALTH DEPT.A PERMIT MAY
 ALSO BE REQD.FROM PALM BEACH COUNTY
 HEALTH DEPT.COUNTYWIDE AMENDMENTS TO
 SPC SEC.101.4.7.
  
 PLUMBING SHEETS SHOW DOMESTIC WATER
 SERVICE AS 3" AND CIVILS SHOW 2".CLARIFY
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED.
 COMPLY W/SPC SEC.901.2.
  
 VENTS FOR WATER CLOSETS SHALL COMPLY W/
 SPC SEC.920.2.(NO LESS THAN 1/2 THE
 DIAMETER OF THE DRAIN SERVED.)
  
 WATER HEATER ON 2ND FLOOR SHALL BE
 EQUIPPED W/PAN AND DRAIN PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.8.1.
  
 DRINKING FOUNTAINS ARE NOT SHOWN ON THE
 SANITARY OR WATER RISERS.COUNTYWIDE
 AMENBDMENTS TO SPC SEC.104.2.1.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-05-03 Cont ID  
Sent By tlarge Date 2000-05-03 Time 11:53 Rev Time 5.50
Received By tlarge Date 2000-05-03 Time 11:53 Sent To  
Notes
2001-01-08 00:00:00SHT.A-103-AN ADDITIONAL STALL IN THE
 WOMEN'S RESTROOM #207 IS REQD.TO COMPLY
 W/FACBC SEC.4.22.4.
  
 SHT.A-403-A FULLY ACCESSIBLE H.C.TOILET
 STALL IS REQD.IN THE WOMEN'S RESTROOM
 #119 WITH A LAVATORY LOCATED WITHIN THE
 STALL PER FACBC SEC.4.1.2.((6),4.17.3.
  
 SHT.A-403-AN ADDITIONAL STALL IN THE
 WOMEN'S RESTROOM #119 IS REQD.TO COMPLY
 W/FACBC SEC.4.22.4.
  
 DRINKING FOUNTAINS SHALL ALLOW FOR A
 FRONT APPROACH PER FACBC SEC.4.15.5(1),
 FIG.#27.
  
 WIDTH OF REQD.FULLY ACCESSIBLE STALL
 SHALL COMPLY W/FACBC SEC.4.17.3.(SEE
 EXCEPTION:NEW CONSTRUCTION.)
  
 SUBMIT COMPLETE ISOMETRIC DRAWING FOR
 THE STORM DRAINAGE SYSTEM.SHOW ALL PIPE
 SIZES,SQ.FOOT OF ROOF AREA DRAINED BY
 EACH DRAIN.COMPLY W/SPC SEC.1108.1,
 1108.2,1108.3.(INCLUDE 1/2 AREA OF
 PARAPET WALLS PER SPC SEC.1108.3)
  
 SUBMIT CALCULATIONS FOR SECONDARY
 (EMERGENCY )ROOF DRAINS.INCLUDE 1/2 OF
 VERTICAL AREA OF PARAPET WALLS PER SPC
 SEC.1108.3,1109.1,1109.2,1109.3 &
 APPENDIX "A".
  
 A PERMIT FOR THE DOMESTIC WATER AND FIRE
 SERVICE IS REQD.FROM DEP.CONTACT PALM
 BEACH COUNTY HEALTH DEPT.A PERMIT MAY
 ALSO BE REQD.FROM PALM BEACH COUNTY
 HEALTH DEPT.
  
 PLUMBING SHEETS SHOW WATER SERVICE AS 3"
 AND CIVILS SHOW 2".CLARIFY.
  
 FLOOR DRAINS NOT PROPERLY VENTED.COMPLY
 W/SPC 901.2.
  
 SHT.P-601-VENTS FOR WATER CLOSETS SHALL
 COMPLY W/SPC SEC.920.2.(NOT LESS THAN
 1/2 THE DIAMETER OF THE DRAIN SERVED.)
  
 SIZE TYPICAL WASTE STACKS FOR FIXTURES.
 COMPLY W/SPC SEC.920.2.
  
 WATER HEATER ON 2ND.FLOOR SHALL BE
 EQUIPPED W/PAN AND DRAIN PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.8.1.
  
 DRINKING FOUNTAINS ARE NOT SHOWN ON THE
 SANITARY OR WATER RISERS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 WATER SUPPLY CONTROL FOR HOT WATER SHALL
 COMPLY W/SPC SEC.610.4.1.
  
 SUBMIT JOB SPECIFICATIONS FOR RE-REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-08 Cont ID  
Sent By tlarge Date 2000-02-08 Time 12:56 Rev Time 7.50
Received By tlarge Date 2000-02-08 Time 12:56 Sent To  
Notes
2001-01-08 00:00:00JOB SPEC 15400-7-2.07(5)-SPACING OF
 CLEANOUTS SHALL COMPLY W/SPC SEC.710.2.4
  
 SPEC.15400-9-2.13-HORIZONTAL SUPPORTS
 COPPER TUBING SHALL COMPLY W/SPC SEC.
 310.3.4.
  
 TOILET STALL DOOR IN MEN'S R.R.CANNOT
 SWING INTO CLEAR FLOOR SPACE FOR URINAL
 PER FACBC SEC.4.17.5.
  
 AN ADDITIONAL HANDICAP STALL IS REQD.IN
 THE WOMEN'S TOILET ROOM PER FACBC SEC.
 4.22.4.
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).(PROVISIONS SHALL BE
 MADE FOR PERSONS WHO HAVE TROUBLE
 BENDING OR STOOPING.)
  
 SHT.A403.-LAVATORY REQD.IN HANDICAP
 STALL PER FACBC SEC.4.17.3.(SEE RM.119)
  
 WALLS AND FLOORS TO A HEIGHT OF FOUR
 FEET SHALL BE NONABSORBENT MATERIAL PER
 SBC 1204.2.
  
 TOILET FLOOR PLAN ON A-403 DOESN'T
 CORRELATE W/OTHER PLANS.CLARIFY.
  
 THE WIDTH OF THE HANDICAP STALLS SHALL
 COMPLY W/FACBC SEC.4.17.3 (MIN.79"+2"
 FOR CLEANING.)
  
 LOCATION OF BACKFLOW DETECTION DEVICE
 SHALL BE DETERMINED BY CITY OF WPB
 UTILITIES,
  
 VENTS FOR FLOOR DRAINS SHALL COMPLY W/
 SPC SEC.906.2.1.(VENT SHALL RISE
 VERTICALLY TO A POINT 6" ABOVE FLOOD
 LEVEL RIM OF FIXTURE BEFORE OFFSETTING
 HORIZ.PROPERLY VENT FLOOR DRAINS.
  
 SHT.P-501-RELIEF LINE SHALL DRAIN TO
 EXTERIOR PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.507.6(3).
  
 SHT.P-101- 7 W.C.'S SHOWN ON FLOOR PLAN
 AND SIX ARE SHOWN ON ISOMETRIC.CLARIFY.
  
 CLEARLY SIZE ALL SECTIONS OF THE
 SANITARY RISERPER COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 INDICATE SLOPE OF PIPE FOR SANITARY
 SYSTEM.COMPLY W/SPC TABLE 714.1,714.2.
 SHOW FIXTURE UNIT LOAD ON SYSTEM.
  
 HOSE BIBBS REQUIRE SHUT-OFF VALVES PER
 SPC SEC.610.4.1.
  
 SUBMIT ISOMETRIC FOR COMPLETE STORM
 SYSTEM.SHOW SQ.FOOTAGE OF ROOF AREA
 DRAINED BY EA.DRAIN.COMPLY W/SPC SEC.
 1108.1,1108.2.
  
 SUBMIT CALCULATIONS FOR SECONDARY DRAIN-
 AGE.INCLUDE 1/2 VERTICAL AREA OF PARAPET
 WALL PER SPC SEC.1108.3.,1109.1,1109.2,
 1109.3.AND APPENDIX "A".
  
 APPROVALS REQD.FROM ENGINEERING FOR
 STORM WATER DRAINAGE AND FROM P.B.COUNTY
 HEALTH DEPT.FOR WATER MAIN INSTALLATION.
 SPC 101.4.7.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-02 Cont ID  
Sent By gjoyce Date 2000-03-02 Time 13:36 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***